1
Kentucky
State Plumbing Law,
Regulations and Code Book
Revised 2-28-2017
DEPARTMENT OF HOUSING, BUILDINGS & CONSTRUCTION
DIVISION OF PLUMBING
101 SEA HERO RD., STE 100
FRANKFORT KY 40601
Phone: 502-573-0397
Website Address: dhbc.ky.gov/plb
E-mail Address: Plumbing@ky.gov
UNOFFICAL TEXT OF STATUTES AND
ADMINISTATIVE REGULATIONS
FOR INFORMATIONAL ONLY
Mathew G. Bevin, Governor
2
DEPARTMENT OF HOUSING,
BUILDINGS AND CONSTRUCTION
Steven A. Milby, Commissioner
Timothy R. House, Deputy Commissioner
DIVISION OF PLUMBING
David J. Moore, Director
VACANT, Assistant Director
Dennis J. Rodgers, Field Operations
Jeffrey Hardin, Field Operations
Floyd Schanz, Field Operations
Plan Reviewers
Geno Washington, Frankfort Office
Gloria Wetzel Frankfort Office
Frank Blevins, Lexington Office
Chris Quire, Louisville Office
Chris Stein, Edgewood Office
Mike McPherson, Bowling Green Office
AREA PLUMBING CONSULTANTS
Area Supervisor Area Phone number
David Beaven A 270-314-0563
Alan Lush B 502-262-9271
Mark Curry C 270-589-1848
George Kelley D
Connell Powell E 502-271-8601
Pat Quisenberry F 859-595-7090
Keith Centers G 859-229-3300
Rodney Adams H 606-359-3851
Vacant I
AREA COMPLIANCE
Mark Hayden West 270-339-0867
Doug King South 859-339-9152
Jeff Phelps East 606-224-9188
Vacant North
3
Area Plumbing Inspectors
Area A
Lynn Bundy 270-210-6293 Roy McGregor 270-339-8539
Raymond Dawes 207-505-2166 Mike Shocklee 270-977-2575
Jerry Dorris 270-577-5350 Mark Thomas
270-314-9933
Area B
John Baird 502-234-8844 Bob Maeser 270-331-9974
Jason Collins 270-307-7580 Gloria Wetzel 502-330-8522
Mike Haycraft 502-492-9724
Area C
Wendell Lawrence 859-583-0854 Rick Stamper 270-820-8059
David Mercer 270-349-6585 Charlie Stearns 606-521-8230
Earl Sandusky 270-401-3544 Mark Wyatt 270-779-0821
Area D
Gary Agnew 502-492-2661 William Hines 502-287-2745
Todd Haeberlin 502-262-3146 Craig Meredith 502-262-6429
Michael Hagan 502-593-4439 Bryan Watkins 502-224-6930
Area E
Bob Carmickle 502-517-5631 Matt Lewis 859-327-2191
Glen Kapfhammer 502-262-1839 Tom Wimsatt 502-220-2301
Area F
Frank Blevins 502-229-5592 Doug Havrilesko 859-595-1696
Donald Corn 859-333-5377 Dale Noble 859-582-7273
Joe Czarnecki 859-200-4922
Area G
Ricky Adams 606-359-3850 Dale Godsey 606-359-3849
Chris Ferguson 606-362-3495 Dewain Woolum 606-585-5579
Area H
Mike Cornelius 606-224-4909 Jeff Nolan 606-359-3853
Rob Dowden 606-813-6012 Joe Mike Wiese 606-219-1841
Area I
Patrick Kennedy 859-391-8513 Tom Parrish 859-298-8721
Jesse Long 502-229-6559 Chris Stein 502-229-6559
4
5
Kentucky Revised Statues
KRS 318
Includes enactments through the 2016 Regular Session
The KRS database was last updated on 2/28/2017
6
7
CHAPTER 318
PLUMBERS AND PLUMBING
Section
318.010 Definitions for chapter.
318.015 Application of chapter and of state plumbing code.
318.020 Apprentices, maintenance men, water company or district employees
exempt.
318.030 License and general liability insurance required.
318.040 Qualifications -- Examinations -- Reciprocity.
318.050 Fees.
318.054 License expiration -- Notice -- Renewal and revival fees -- Evidence of
completion of continuing education.
318.056 Repealed, 1966
318.057 Repealed, 1986.
318.060 Reexamination.
318.064 Revocation or suspension of license.
318.066 Hearing -- Appeal.
318.074 Officers of committee -- Meetings.
318.077 Hearing on amendments to code -- Appeals.
318.080 State Plumbers Examining Committee.
318.090 Inspectors -- Appointment, qualifications.
318.100 Advertising by licensee.
318.110 Company having licensed plumber may engage in plumbing business --
Notice of connection.
318.120 Employment of unlicensed plumber prohibited.
318.130 Kentucky State Plumbing Code -- Rules and regulations.
318.134 Installation permits -- Requisites -- Fees.
318.136 Trust and agency fund.
318.140 Adoption and enforcement of State Plumbing Code by local
governments -- Local inspectors - - Qualifications.
318.150 Materials and methods to be used.
318.160 Installation plans and specifications.
318.165 Requisites for providing permanent water supply.
318.170 Authority of agents of Department.
318.180 Enforcement of plumbing laws.
318.190 Jurisdiction for enforcement actions.
318.200 Water heating devices -- Serial numbers.
318.310 Repealed
318.320 Repealed
318.330 Repealed
318.990 Penalties.
8
318.010 Definitions for chapter.
As used in this chapter, unless the context requires otherwise:
(1) "Department" means Department of Housing, Buildings and Construction;
(2) "Journeyman plumber" means a person who engages or offers to engage, either as an occupation or
otherwise, in the construction, installation, alteration, maintenance, repair, remodeling or removal, and
replacement of plumbing under the supervision, direction, and responsibility of a master plumber;
(3) "Master plumber" means a person who assumes responsible charge, supervision, or direction of journeyman
plumbers, plumbers' apprentices, and other persons in the construction, installation, or alteration of plumbing or
who engages in, offers to engage in, or advertises or otherwise represents that he is permitted or qualified to
engage in the design, planning, superintending, contracting for, or responsible charge of plumbing;
(4) "Plumbing" means the art of installing in buildings the pipes for distributing the water supply, the fixtures for
using water and drainage pipes for removing waste water and sewage, together with fittings, appurtenances, and
appliances of various kinds, all within or adjacent to the building. It shall not include the installation of on-site
sewage disposal systems, except for the piping, fixtures, or other appurtenances needed within the building. It
shall include:
(a) The water service pipe which forms the connection between the property line and the building, other than
piping serving firefighting equipment;
(b) Private water supply systems;
(c) House sewers which convey the waste water and sewage from the building to the property line or other points
of disposal, but not including sewers located between manholes and sewers extending five (5) feet from a main
or manhole on private property;
(d) Storm sewers and rain water piping located within a building to a point two (2) feet outside of the building; and
(e) Medical gas piping;
(5) "Public building" means any building intended for public use or built with public funds and includes but is not
limited to the following: schools, industrial establishments, housing projects, restaurants, food-handling
establishments, private clubs, theaters including drive-ins, trailer coach parks, camping areas, hospitals, nursing
homes, hotels, motels, tourist courts, rooming houses, boarding houses, and other establishments furnishing
public sleeping accommodations;
(6) "Maintenance man" means a person employed to maintain and keep plumbing in good repair;
(7) "Apprentice" means a person in the process of learning the plumbing trade who assists and is under the
personal supervision of a licensed master or licensed journeyman plumber;
(8) "Farmstead" means a farm dwelling together with other farm buildings and structures incident to the operation
and maintenance of the farm situated on ten (10) acres or more of land which is located outside the corporate
limits of a municipality;
(9) "Person" means any individual, public or private corporation, political subdivision, government agency,
municipality, copartnership, association, firm, trust, estate, or other entity whatsoever;
(10) "Commissioner" means the commissioner of the Department of Housing, Buildings and Construction; and
(11) "Code" means the Kentucky State Plumbing Code.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1670, effective July 15, 2010. -- Amended 1996 Ky. Acts ch. 157,
sec. 1, effective July 15, 1996. -- Amended 1986 Ky. Acts ch. 354, sec. 5, effective July 15, 1986. -- Amended
1982 Ky. Acts ch. 392, sec. 6, effective July 15, 1982. -- Amended 1978 Ky. Acts ch. 117, sec. 49, effective July
1, 1978; and ch. 155, sec. 149, effective June 17, 1978. -- Amended 1976 Ky. Acts ch. 193, sec. 1; and ch. 299,
sec. 60. -- Amended 1974 Ky. Acts ch. 74, Art. VI, sec. 91. -- Amended 1970 Ky. Acts ch. 162, sec. 1. -- Amended
1960 Ky. Acts ch. 222, sec. 1, effective June 16, 1960. -- Recodified 1942 Ky. Acts ch. 208, sec. 1, effective
October 1, 1942, from Ky. Stat. sec. 3909b.
9
318.100 Advertising by licensee.
No person shall advertise or hold himself or herself out as a licensed master or licensed journeyman plumber
within the Commonwealth of Kentucky unless he or she is a holder of a license from the department in accordance
with the provisions of this chapter.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1683, effective July 15, 2010. -- Amended 1976 Ky. Acts ch. 299,
sec. 69. -- Amended 1974 Ky. Acts ch. 126, sec. 6. -- Amended 1960 Ky. Acts ch. 222, sec. 14, effective June 16,
1960. -- Recodified 1942 Ky. Acts ch. 208, sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-5.
318.015 Application of chapter and of state plumbing code.
(1) This chapter applies and shall be in full force and effect in all counties of the Commonwealth.
(2) The state plumbing code promulgated by the department under the provisions of this chapter applies and shall
be in full force and effect for all public buildings regardless of location in the Commonwealth.
(3) This chapter shall not apply to farmsteads.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1671, effective July 15, 2010. -- Amended 1976 Ky. Acts ch. 299,
sec. 61. -- Amended 1974 Ky. Acts ch. 126, sec. 1. -- Amended 1968 Ky. Acts ch. 194, sec. 1. -- Created 1960
Ky. Acts ch. 222, sec. 2.
318.020 Apprentices, maintenance men, water company or district employees exempt.
(1) Nothing contained in this chapter shall be construed as prohibiting the employment of an apprentice to assist
a journeyman plumber in his duties.
(2) This chapter shall not apply to anyone who is employed or acts as a maintenance man.
(3) This chapter shall not apply to persons employed by any water company, water district or sanitation district, in
the laying, maintenance, and operation of its mains and other appurtenances in the conduct of its business.
(4) The provisions of this chapter relating to the licensure of plumbers shall apply to all persons engaged in the
practice of plumbing.
History: Amended 1974 Ky. Acts ch. 126, sec. 2. -- Amended 1968 Ky. Acts ch. 194, sec. 2. -- Amended 1960
Ky. Acts ch. 222, sec. 3. -- Recodified 1942 Ky. Acts ch. 208, sec. 1, effective October 1, 1942, from Ky. Stat. sec.
3909b.
318.030 License and general liability insurance required.
(1) No person shall engage in plumbing or engage in or work at the trade of plumbing:
(a) Unless he or she is the holder of a valid and effective active master plumber's license duly issued by the
department in accordance with the provisions of this chapter; or
(b) Unless he or she is the holder of a valid and effective journeyman plumber's license duly issued by the
department in accordance with the provisions of this chapter.
(2) (a) No person, firm, or corporation shall engage in plumbing or engage in or work at the trade of plumbing
unless the person, firm, or corporation maintains general liability insurance in an amount not less than two hundred
fifty thousand dollars ($250,000) and submits proof of compliance with workers' compensation and unemployment
insurance laws of the Commonwealth.
(b) Proof of insurance required in this subsection shall be submitted to the department prior to issuance or renewal
of the active master plumber license required under this chapter.
(c) No license shall be valid without insurance as required in this subsection, and insurance carriers shall notify
the department upon cancellation of the insurance of any licensee required to maintain insurance.
(d) The insurance required in this subsection shall not apply to an employee of a person, firm, or corporation
engaged in plumbing as defined in this chapter.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1672, effective July 15, 2010. -- Amended 2004 Ky. Acts ch. 40,
sec. 1, effective July 13, 2004. -- Amended 1974 Ky. Acts ch. 126, sec. 3. -- Amended 1968 Ky. Acts ch. 194, sec.
3. -- Amended 1960 Ky. Acts ch. 222, sec. 4. -- Recodified 1942 Ky. Acts ch. 208, sec. 1, effective October 1,
1942, from Ky. Stat. sec. 3909
10
318.040 Qualifications -- Examinations -- Reciprocity.
(1) An applicant for a master or journeyman plumber's license shall:
(a) Be at least eighteen (18) years of age;
(b) Be of good moral character;
(c) Be a citizen of the United States or be a resident alien who is authorized to work in the United States; and
(d) Possess all the other qualifications that may be prescribed by administrative regulations of the commissioner.
(2) Except as otherwise provided in this chapter, no master or journeyman plumber's license shall be issued
except upon a successful passage of an examination as prescribed by the department.
(3) Examinations for a license as a master plumber or journeyman plumber shall be conducted at times and places
fixed by the regulations of the commissioner. Applicants for an examination shall furnish the information required
by the commissioner and shall receive from the department due notice of the time and place of the examination.
(4) The department shall prepare or cause to be prepared under its supervision examinations consisting of written
and practical tests with such questions and tests by which the department will determine:
(a) With respect to master plumber's license applicants, that applicants are qualified in view of the definitions,
provisions, and purposes of this chapter to carry on responsibly, reasonably, and competently, the activities which
a licensed master plumber is authorized to engage in by this chapter; and
(b) With respect to journeyman plumber's license applicants, their knowledge and competency to carry on the
activities which a licensed journeyman plumber is authorized to engage in by this chapter.
(5) The examination papers shall be preserved by the department for a period of one (1) year.
(6) The department may issue a license to any person who holds a valid license in another state if that state has
a statewide plumbing code and, in the opinion of the Plumbing Code Committee, the other state's examination is
at least equal to that of Kentucky and the other state agrees to reciprocate with Kentucky.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1673, effective July 15, 2010. -- Amended 1994 Ky. Acts ch. 202,
sec. 1, effective July 15, 1994. -- Amended 1990 Ky. Acts ch. 45, sec. 1, effective July 13, 1990. -- Amended 1978
Ky. Acts ch. 117, sec. 50, effective July 1, 1978. -- Amended 1974 Ky. Acts ch. 74, Art. VI, sec. 107(22). --
Amended 1960 Ky. Acts ch. 222, sec. 5, effective June 16, 1960. -- Recodified 1942 Ky. Acts ch. 208, sec. 1,
effective October 1, 1942, from Ky. Stat. sec. 3909b-4.
318.050 Fees.
Each application for a license as a master or journeyman plumber shall be accompanied by a reasonable fee as
established by the department.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1674, effective July 15, 2010. -- Amended 1976 Ky. Acts ch. 193,
sec. 2. -- Amended 1960 Ky. Acts ch. 222, sec. 6, effective June 16, 1960. -- Recodified 1942 Ky. Acts ch. 208,
sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-1.
11
318.054 License expiration -- Notice -- Renewal and revival fees -- Evidence of completion of continuing
education.
(1) The initial license for a master or journeyman plumber shall expire on the last day of the licensee's birth month
in the following year. The department may reduce the license fee on a pro rata basis for initial licenses issued for
less than twelve (12) months. Renewed licenses shall expire on the last day of the licensee's birth month of each
year after the date of issuance of the renewed license.
(2) The department shall require an applicant for renewal of a license to show evidence of completing the
continuing education requirements set forth by the department, with advice from the State Plumbing Code
Committee, in its administrative regulations issued under KRS 318.130.
(3) The department shall send each licensed master and journeyman plumber a notice advising them that the
annual license renewal fee is due. The notice shall be sent to the licensee's last known address no later than thirty
(30) days prior to the expiration of the license. The annual license renewal fee shall be a reasonable fee set by
regulation of the department. The fee for the renewal of a master plumber's license shall exceed the fee charged
for a journeyman plumber's license.
(4) Any master or journeyman plumber who fails to renew his license prior to expiration may have his license
renewed upon payment of the required renewal fee, a revival fee, and upon showing the completion of continuing
education requirements. The revival fee for a master plumber shall be five dollars ($5) and for a journeyman
plumber three dollars ($3). If the renewal and revival fees are not paid one hundred eighty (180) days after the
license expires, such licenses shall be automatically canceled by operation of law for nonpayment; provided,
however, that such licenses may be reinstated upon payment of all delinquent renewal fees plus a revival fee of
ten dollars ($10) for a master plumber and six dollars ($6) for a journeyman plumber. Upon presentation of proper
evidence, the department may waive payment of any renewal or revival fee specified herein for persons serving
on active duty in the Armed Forces of the United States.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1675, effective July 15, 2010. -- Amended 2006 Ky. Acts ch. 167,
sec. 2, effective July 1, 2007. -- Amended 2005 Ky. Acts ch. 182, sec. 3, effective June 20, 2005. -- Amended
1976 Ky. Acts ch. 299, sec. 62. -- Created 1960 Ky. Acts ch. 222, sec. 7, effective June 16, 1960.
318.060 Reexamination.
An applicant who fails an examination shall be eligible upon reapplication for the next regular examination upon
the payment of an additional application fee. Applications shall be canceled one (1) year after receipt thereof, in
the event the applicant fails to appear for examination.
Effective: June 16, 1960
History: Amended 1960 Ky. Acts ch. 222, sec. 9, effective June 16, 1960. -- Recodified 1942 Ky. Acts ch. 208,
sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-1.
318.064 Revocation or suspension of license.
The department may revoke or suspend any plumber's license issued by it upon proof that the licensee has:
(1) Knowingly violated the provisions of this chapter or the Kentucky State Plumbing Code, or the rules and
regulations of the department;
(2) Practiced fraud or deception in applying for or obtaining a license;
(3) Is incompetent to perform services as a licensed master plumber or a licensed journeyman plumber;
(4) Permitted his or her license to be used directly or indirectly by another to obtain or perform plumbing work or
services; or
(5) Is guilty of such other unprofessional or dishonorable conduct of a character likely to deceive or defraud the
public.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1676, effective July 15, 2010. -- Amended 1976 Ky. Acts ch. 299,
sec. 63. -- Created 1960 Ky. Acts ch. 222, sec. 10, effective June 16, 1960.
12
318.066 Hearing -- Appeal.
(1) No license shall be suspended or revoked by the department unless a hearing has been conducted or an
opportunity afforded therefor in accordance with KRS Chapter 13B.
(2) A licensee aggrieved by a final order of the department suspending or revoking a license may appeal therefrom
to the Circuit Court of the county in which the principal office of the office is located in accordance with KRS
Chapter 13B.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1677, effective July 15, 2010. -- Amended 1996 Ky. Acts ch. 318,
sec. 274, effective July 15, 1996. -- Amended 1980 Ky. Acts ch. 114, sec. 77, effective July 15, 1980. -- Amended
1978 Ky. Acts ch. 117, sec. 51, effective July 1, 1978. -- Amended 1976 Ky. Acts ch. 299, sec. 64. -- Amended
1974 Ky. Acts ch. 315, sec. 56. -- Amended 1966 Ky. Acts ch. 255, sec. 249. -- Created 1960 Ky. Acts ch. 222,
sec. 11.
318.071 State Plumbing Code Committee -- Members -- Compensation -- Terms -- Vacancies.
(1) There is hereby created a State Plumbing Code Committee which shall be established within the Department
of Housing, Buildings and Construction for administrative purposes. The State Plumbing Code Committee shall
consist of seven (7) members, one (1) of whom shall be a builder member of the Home Builders Association of
Kentucky, one (1) of whom shall be a member of the Association of General Contractors, one (1) of whom shall
be a member of the Kentucky Master Plumbers Association, one (1) of whom shall be a member of the Kentucky
Society of Professional Engineers (who shall have a background in sanitary engineering), one (1) of whom shall
be a member of the American Institute of Architects, one (1) of whom shall be a member of the United Association
of Journeyman Plumbers, and one (1) of whom shall be a member of the Mechanical Contractors Association.
Each member of the State Plumbing Code Committee shall receive twenty-five dollars ($25) per day for attending
each meeting and shall be reimbursed for all necessary expenses. The members of the committee shall be
appointed by the Governor from lists of three (3) names submitted by the above mentioned organizations.
(2) Each member shall be appointed for and hold office a term of two (2) years or until his or her successor is
appointed and qualified.
(3) At all times in the filling of vacancies of membership on the committee the balance of representation set out in
subsection (1) shall be maintained.
Effective: July 15, 2010 History: Amended 2010 Ky. Acts ch. 24, sec. 1678, effective July 15, 2010. -- Amended
1978 Ky. Acts ch. 117, sec. 52, effective July 1, 1978; Ky. Acts ch. 154 sec. 32, effective June 17, 1978; and ch.
155, sec. 150, effective June 17, 1978. -- Amended 1976 Ky. Acts ch. 299, sec. 65. -- Created 1966 Ky. Acts ch.
79, secs. 2, 4, and 5
318.074 Officers of committee -- Meetings.
The committee shall elect from its members one (1) to serve as chairman, one (1) as vice chairman, and the
commissioner of the Department of Housing, Buildings and Construction or his or her designee shall serve as ex
officio member of the committee (without a vote) and secretary. The committee shall meet at least quarterly and
upon special call by the chairman or the secretary.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1679, effective July 15, 2010. -- Amended 1978 Ky. Acts ch. 117,
sec. 53, effective July 1, 1978; and ch. 155, sec. 151, effective June 17, 1978. -- Amended 1976 Ky. Acts ch.
193, sec. 3; and ch. 299, sec. 66. -- Created 1966 Ky. Acts ch. 79, sec. 3.
13
318.077 Hearing on amendments to code -- Appeals.
The committee shall hold hearings, upon adequate notice to affected parties specifying the matters to be
considered before the submission to the commissioner of its suggested amendments to the code. No
amendment of the code or any other related regulation shall be issued or promulgated by the department
without the prior review and comment of the committee under the requirements of KRS 198B.030(8) and (9) and
198B.040(11). Any person aggrieved by any rule, regulation, or amendment approved by the department, within
30 days after such action has become final, may appeal therefrom to the Circuit Court. For the purposes of this
section, "persons aggrieved" shall include any person directly or indirectly injured or threatened with injury on
account of any such regulation, rule, or amendment, whether or not such person was a party to the proceedings
out of which the order, rule, regulation, or amendment arose.
Effective: June 8, 2011
History: Amended 2011 Ky. Acts ch. 100, sec. 20, effective June 8, 2011. -- Amended 2010 Ky. Acts ch. 24, sec. 1680,
effective July 15, 2010. -- Amended 2006 Ky. Acts ch. 256, sec. 9, effective July 12, 2006. -- Amended 1978 Ky. Acts ch. 117,
sec. 54, effective July 1, 1978; and ch. 155, sec. 152, effective June 17, 1978. -- Amended 1976 Ky. Acts ch. 193, sec. 4; and
ch. 299, sec. 67. -- Created 1966 Ky. Acts ch. 79, sec. 6.
318.080 State Plumbers Examining Committee.
(1) In order to conduct examinations for persons to qualify as licensed master plumbers or journeyman
plumbers, the department shall appoint as examiners the following persons to a State Plumbers Examining
Committee: An employee of the department and three (3) other persons who shall be licensed either as master
or journeyman plumbers. The commissioner shall be an ex officio examiner and permanent commissioner of the
committee. With the exception of the issuance of any order involving the revocation, suspension or cancellation
of a master or journeyman plumber's license, the commissioner may delegate to a subordinate employee in the
department the power to be present and participate, including the right to vote, as his or her representative at
any meeting, hearing or other proceeding of the State Plumbers Examining Committee. Plumber examiners
shall serve at the pleasure of the department.
(2) The department shall appoint assistant plumber examiners who shall be qualified licensed master or
journeyman plumbers who shall serve at the pleasure of the department. Assistant plumber examiners shall
perform such duties as are delegated to them by the State Plumbers Examining Committee.
(3) Plumber examiners and assistant plumber examiners shall receive no compensation for their services but
shall be reimbursed for their necessary traveling expenses.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1681, effective July 15, 2010. -- Amended 1978 Ky. Acts ch. 117, sec. 55,
effective July 1, 1978; and ch. 155, sec. 153, effective June 17, 1978. -- Amended 1976 Ky. Acts ch. 299, sec. 68. -- Amended
1974 Ky. Acts ch. 74, Art. VI, sec. 92. -- Amended 1970 Ky. Acts ch. 92, sec. 87. -- Amended 1960 Ky. Acts ch. 222, sec. 12,
effective June 16, 1960. -- Recodified 1942 Ky. Acts ch. 208, sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-1.
318.090 Inspectors -- Appointment -- Qualifications.
(1) The department shall appoint and assign plumbing inspectors to each county subject to the provisions of this
chapter.
(2) Each plumbing inspector shall have at least eight (8) years experience as a journeyman or master plumber.
At the time of his or her appointment he or she shall be licensed in accordance with the provisions of this
chapter.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1682, effective July 15, 2010. -- Amended 1974 Ky. Acts ch. 126, sec. 5. --
Amended 1968 Ky. Acts ch. 194, sec. 5. -- Amended 1960 Ky. Acts ch. 222, sec. 13. -- Recodified 1942 Ky. Acts ch. 208, sec.
1, effective October 1, 1942, from Ky. Stat. sec. 3909b-9.
318.110 Company having licensed plumber may engage in plumbing business -- Notice of connection.
A company or individual principal may engage in the business of plumbing within any county of the Commonwealth
if some person connected with such a company or individual principal in responsible charge of the plumbing work
is a licensed master plumber. Any master plumber, in responsible charge of plumbing work for a company or
individual engaged in the plumbing business, shall notify the department at any time he or she commences or
severs his or her connection with the company or individual principal.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1684, effective July 15, 2010. -- Amended 1978 Ky. Acts ch. 384, sec. 106,
effective June 17, 1978. -- Amended 1968 Ky. Acts ch. 194, sec. 6. -- Amended 1960 Ky. Acts ch. 222, sec. 15. -- Recodified
1942 Ky. Acts ch. 208, sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-7.
14
318.100 Advertising by licensee.
No person shall advertise or hold himself or herself out as a licensed master or licensed journeyman plumber
within the Commonwealth of Kentucky unless he or she is a holder of a license from the department in
accordance with the provisions of this chapter.
Effective: July 15, 2010 History: Amended 2010 Ky. Acts ch. 24, sec. 1683, effective July 15, 2010. -- Amended 1976 Ky.
Acts ch. 299, sec. 69. -- Amended 1974 Ky. Acts ch. 126, sec. 6. -- Amended 1960 Ky. Acts ch. 222, sec. 14, effective June
16, 1960. -- Recodified 1942 Ky. Acts ch. 208, sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-5.
318.110 Company having licensed plumber may engage in plumbing business -- Notice of connection.
A company or individual principal may engage in the business of plumbing within any county of the
Commonwealth if some person connected with such a company or individual principal in responsible charge of
the plumbing work is a licensed master plumber. Any master plumber, in responsible charge of plumbing work
for a company or individual engaged in the plumbing business, shall notify the department at any time he or she
commences or severs his or her connection with the company or individual principal.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1684, effective July 15, 2010. -- Amended 1978 Ky. Acts ch. 384, sec. 106,
effective June 17, 1978. -- Amended 1968 Ky. Acts ch. 194, sec. 6. -- Amended 1960 Ky. Acts ch. 222, sec. 15. -- Recodified
1942 Ky. Acts ch. 208, sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-7.
318.120 Employment of unlicensed plumber prohibited.
No person or corporation who assumes responsible charge and direction of other persons in the installation of
plumbing shall employ or engage any person not licensed under this chapter to perform and install plumbing.
Provided, however, that this section shall not be deemed to prohibit the employment or use of an apprentice as
defined in this chapter.
History: Amended 1974 Ky. Acts ch. 126, sec. 7. -- Amended 1968 Ky. Acts ch. 194, sec. 7. -- Amended 1960 Ky. Acts ch.
222, sec. 16. -- Recodified 1942 Ky. Acts ch. 208, sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b.
318.130 Kentucky State Plumbing Code -- Rules and regulations.
In order to administer this chapter, the department shall promulgate and thereafter from time to time may amend
a code to be known as the Kentucky State Plumbing Code, regulating the construction, installation, and
alteration of plumbing and plumbing fixtures and appliances, house sewers and private water supplies, and
methods and materials to be used therein within this state, using as a minimum standard the basic principles of
the National Plumbing Code Coordinating Committee, as evidenced by that committee's final report of 1951 with
variations thereof or additions thereto as the committee considers are warranted by local, climatic, or other
conditions. The code may also designate the number of plumbing fixtures for public buildings. The department
may adopt any other reasonable rule or regulation to administer this chapter if the rule or regulation has been
subject to review and comment by the committee under the requirements of KRS 198B.030(8) and (9) and
198B.040(11). No rules or regulations so approved by the committee shall become effective except upon
adoption by the department, in satisfaction of the requirements of KRS Chapter 13A. The department shall
furnish to the committee proposed amendments to the code for the committee's review and comment prior to
their adoption by the department. The department shall not promulgate any rules or regulations related to this
chapter without granting the committee the opportunity to comment on the administrative regulation.
Effective: June 8, 2011
History: Amended 2011 Ky. Acts ch. 100, sec. 21, effective June 8, 2011. -- Amended 2010 Ky. Acts ch. 24, sec. 1685,
effective July 15, 2010. -- Amended 2006 Ky. Acts ch. 256, sec. 10, effective July 12, 2006. -- Amended 1982 Ky. Acts ch.
392, sec. 7, effective July 15, 1982. -- Amended 1976 Ky. Acts ch. 193, sec. 5; and ch. 299, sec. 70. -- Amended 1968 Ky.
Acts ch. 152, sec. 147. -- Amended 1966 Ky. Acts ch. 79, sec. 1. -- Amended 1960 Ky. Acts ch. 222, sec. 17. -- Recodified
1942 Ky. Acts ch. 208, sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-2.
Legislative Research Commission Note (10/5/90). Pursuant to KRS 7.136(1), KRS Chapter 13A has been substituted for
the prior reference to KRS Chapter 13 in this statute. The sections in KRS Chapter 13 were repealed by 1984 Ky. Acts ch.
417, § 36 and KRS Chapter 13A was created in that same chapter of the 1984 Ky. Acts
15
318.134 Installation permits -- Requisites -- Fees. (1) No person, firm, or corporation shall:
(a) Construct, install, or alter, or cause to be constructed, installed, or altered, any plumbing without first having
procured a plumbing installation permit therefor from the department;
(b) Use or continue to use, or permit the use or continued use of, any plumbing constructed, installed, or altered
under a plumbing installation permit issued therefor where the department through a duly authorized inspector,
employee, or agent, finds that the plumbing was not constructed, installed, or altered in accordance with such
permit and the Kentucky State Plumbing Code.
(2) All applications for plumbing installation permits shall be accompanied by plans and specifications of the
proposed plumbing installation, location, and construction of the water supply system to be used. If an on-site
sewage disposal system that does not have a surface discharge is proposed, a valid on-site sewage disposal
permit issued by the Cabinet for Health and Family Services or its designated agent shall accompany the
application.
(3) The department shall fix a reasonable schedule of fees and charges to be paid for plumbing installation
permits and the necessary inspections incident thereto. The department shall also fix a reasonable schedule of
fees and charges to be paid for necessary inspections of the construction, installation, or alteration of plumbing
in public buildings.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1686, effective July 15, 2010. -- Amended 2005 Ky. Acts ch. 99,
sec. 600, effective June 20, 2005. -- Amended 1998 Ky. Acts ch. 426, sec. 551, effective July 15, 1998. --
Amended 1982 Ky. Acts ch. 392, sec. 8, effective July 15, 1982. -- Amended 1978 Ky. Acts ch. 244, sec. 2,
effective June 17, 1978. -- Amended 1976 Ky. Acts ch. 299, sec. 71. -- Amended 1974 Ky. Acts ch. 126, sec. 8.
-- Amended 1968 Ky. Acts ch. 194, sec. 8. -- Created 1960 Ky. Acts ch. 222, sec. 18
318.136 Trust and agency fund.
All license fees, permit and inspection fees and charges, and other moneys collected by the department, under
the provisions of this chapter and the rules and regulations of the department adopted hereunder, shall be paid
into the State Treasury and credited to a trust and agency fund to be used by the department in carrying out the
provisions of this chapter. No part of this fund shall revert to the general fund of the Commonwealth. All moneys
held in a trust and agency fund or other fund to the credit of the department for the administration and enforcement
of this chapter on June 16, 1960, are hereby transferred to the trust and agency fund herein created.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1687, effective July 15, 2010. -- Amended 1976 Ky. Acts ch. 299,
sec. 72. -- Created 1960 Ky. Acts ch. 222, sec. 19, effective June 16, 1960.
2016-2018 Budget Reference. See State/Executive Branch Budget, 2016 Ky. Acts ch. 149, Pt. I, L, 8, (1) at 1094.
318.140 Adoption and enforcement of State Plumbing Code by local governments -- Local inspectors --
Qualifications.
(1) Any local government may, by ordinance, enact the Kentucky State Plumbing Code, regulating the
construction, installation, or alteration of plumbing within such local government, providing for the issuance of
plumbing installation permits and fixing permit and inspection fees. Two (2) or more local governments may, by
ordinance of each local government, enact the plumbing code as described in this section which shall be jointly
enforced and administered by said local governments within their boundaries. Agreements for joint enforcement
shall conform to the provisions of KRS Chapter 65. The department may authorize any such local government or
combination of local governments to administer, carry out, and enforce the Kentucky State Plumbing Code and
the rules and regulations of the department relating thereto and to issue permits and make inspections thereunder
within such local government, in which event a permit issued under the provisions of the local government
plumbing code ordinance shall be deemed a permit issued by the department; provided, however, that inspectors
of the department shall have concurrent jurisdiction with local government plumbing inspectors in the enforcement
in such local governments of the Kentucky State Plumbing Code.
(2) Any local government enacting a plumbing code ordinance may appoint and fix the compensation of local
government plumbing inspectors. No person shall be eligible for appointment as a local government plumbing
inspector unless he or she has at least eight (8) years' experience as a master or journeyman plumber. At the
time of his or her appointment, he or she shall be licensed in accordance with the provisions of this chapter.
(3) Nothing contained in this chapter shall be construed as prohibiting a local government from collecting
occupational license fees from persons, firms, or corporations engaged in the plumbing business.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1688, effective July 15, 2010. -- Amended 1978 Ky. Acts ch. 117, sec. 56,
effective July 1, 1978. -- Amended 1976 Ky. Acts ch. 299, sec. 73. -- Amended 1960 Ky. Acts ch. 222, sec. 20, effective June
16, 1960. -- Recodified 1942 Ky. Acts ch. 208, sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-8.
16
318.150 Materials and methods to be used.
No person shall use unsafe or defective material in the work of plumbing or drainage. Only the best known
methods of installing materials, fixtures, appurtenances and appliances, including water supply piping, waste,
ventilating and soil piping, and sewage piping shall be employed.
Effective: June 16, 1960
History: Amended 1960 Ky. Acts ch. 222, sec. 21, effective June 16, 1960. -- Recodified 1942 Ky. Acts ch. 208,
sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-3.
318.160 Installation plans and specifications.
Except as otherwise provided by law or by regulation of the department, no person shall construct, install, or
extensively alter any plumbing, sewerage, or water supply system of any public building or establishment
without having first obtained the approval of the department in writing. Detailed plans and specifications of the
proposed facility showing the plumbing system, sewage disposal system, and water supply system shall be
submitted to the department prior to the construction or alteration of the facility. In the event no public sewer is
available, the plan shall include the proposed type of sewage disposal system. In the event a sewage subsoil
drainage system is used, or some other type of on-site sewage disposal system that does not have a surface
discharge, the application for construction, installation, or alteration of such system shall be submitted to the
Cabinet for Health and Family Services or its designated agent. All other plans and specifications shall be
submitted in triplicate to the department. The department shall notify the applicant in writing of the approval or
disapproval of the plans. The construction, installation, or alteration shall be done in accordance with the
approved plans.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1689, effective July 15, 2010. -- Amended 2005 Ky. Acts ch. 99, sec. 601,
effective June 20, 2005. -- Amended 1998 Ky. Acts ch. 426, sec. 552, effective July 15, 1998. -- Amended 1982 Ky. Acts ch.
392, sec. 9, effective July 15, 1982. -- Amended 1978 Ky. Acts ch. 244, sec. 3, effective June 17, 1978. -- Amended 1976 Ky.
Acts ch. 299, sec. 74. -- Created 1960 Ky. Acts ch. 222, sec. 22, effective June 16, 1960.
318.165 Requisites for providing permanent water supply.
No permanent water supply shall be provided to any building by any public utility or water district where the interior
plumbing system has not been installed and approved in accordance with the provisions of KRS Chapter 318 and
the State Plumbing Code.
History: Created 1974 Ky. Acts ch. 126, sec. 9.
318.170 Authority of agents of department.
For the purpose of enforcing the provisions of this chapter and the State Plumbing Code, officers, agents, and
inspectors of the department shall have the power and authority to enter upon premises at all reasonable times
for the purpose of making inspections, to interrogate all persons and to require the production of plumbing
installation permits and other evidence. Officers, agents, and inspectors of the department are empowered to
issue a stop order to any owner, agent, or occupant of real property whenever the plumbing thereon is found by
the officer, agent or inspector of the department to be in violation of this chapter or the State Plumbing Code.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1690, effective July 15, 2010. -- Created 1960 Ky. Acts ch. 222, sec. 23, effective
June 16, 1960
.
318.180 Enforcement of plumbing laws.
(1) Notwithstanding the existence or pursuit of any other remedy (civil or criminal) the department, or its officers,
agents, or inspectors, are hereby authorized to institute and maintain actions to restrain and enjoin any violation
of this chapter, the State Plumbing Code, or the rules and regulations of the department relating thereto.
(2) City, county and Commonwealth's attorneys, and the Attorney General, shall within their respective
jurisdictions represent the department, its officers, agents, and inspectors, in the enforcement of the provisions of
this chapter, the State Plumbing Code, and the rules and regulations of the department relating thereto, but when
the department deems it necessary, it may employ, at its discretion, special attorneys to assist the department, or
its officers, agents, or inspectors, and may pay reasonable compensation, fees and other costs from any
unexpended plumbing funds.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1691, effective July 15, 2010. -- Amended 1976 Ky. Acts ch. 299, sec. 75. --
Created 1960 Ky. Acts ch. 222, sec. 24, effective June 16, 196
17
318.190 Jurisdiction for enforcement actions.
(1) The Circuit Court where the violation occurs shall have jurisdiction and venue in all civil and injunctive
actions instituted by the department for the enforcement of the provisions of KRS Chapter 318 and the State
Plumbing Code and the orders issued thereunder.
(2) The Franklin Circuit Court shall hold concurrent jurisdiction and venue in all civil and injunctive actions
instituted by the department, or upon the secretary's request by the Attorney General, for the enforcement of the
provisions of KRS Chapter 318, the State Plumbing Code and the orders issued thereunder and other rules and
regulations of the department.
(3) The District Court where the violation occurs shall have jurisdiction and venue in all criminal actions for the
enforcement of the provisions of KRS Chapter 318 and the State Plumbing Code and the orders issued
thereunder. The Franklin Circuit Court shall hold concurrent jurisdiction and venue on all appeals of criminal
actions for the enforcement of the provisions of KRS Chapter 318 and the State Plumbing Code and the orders
issued thereunder.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1692, effective July 15, 2010. -- Amended 1984 Ky. Acts ch. 45,
sec. 1, effective July 13, 1984. -- Amended 1976 Ky. Acts ch. 193, sec. 6; and ch. 299, sec. 76. -- Created 1974
Ky. Acts ch. 126, sec. 10.
318.200 Water heating devices -- Serial numbers.
(1) No water heating device shall be sold or offered for sale in the Commonwealth of Kentucky unless it contains
a serial number on it. As used in this section, "water heating device" means any pressure vessel which heats,
stores, and supplies potable water for domestic or commercial purposes other than for space heating.
(2) All retailers, wholesalers, and installers selling or offering for sale a water heating device shall, within thirty
(30) days of the date of sale, forward a list of names and addresses of purchasers along with the serial numbers
of the devices purchased to the department or to the appropriate agency of county or city government having
jurisdiction.
Effective: July 15, 2010
History: Amended 2010 Ky. Acts ch. 24, sec. 1693, effective July 15, 2010. -- Amended 1992 Ky. Acts ch. 5, sec.
1, effective July 14, 1992. -- Created 1984 Ky. Acts ch. 272, sec. 1, effective July 13, 1984.
Penalties
318.990 Penalties.
Any person who violates any provision of this chapter or any regulation adopted hereunder or any provision of
the State Plumbing Code shall be fined not less than ten dollars ($10) nor more than one hundred dollars ($100)
or imprisoned for not more than ninety (90) days or both for each offense. Each day the violation continues shall
constitute a separate offense.
Effective: June 16, 1960
History: Amended 1960 Ky. Acts ch. 222, sec. 25, effective June 16, 1960. -- Recodified 1942 Ky. Acts ch. 208,
sec. 1, effective October 1, 1942, from Ky. Stat. sec. 3909b-10.
18
Basic
Principles
19
Basic Principles
The department is directed by KRS 318.130 through the State Plumbing Code Committee to adopt and put into
effect a State Plumbing Code. This code is founded upon certain basic principles or environmental sanitation and
safety through properly designed acceptably installed and adequately maintained plumbing systems. Some of the
details of plumbing construction may vary but the basic sanitary and safety principles desirable and necessary to
protect the health of the people are the same everywhere. The establishment of trade jurisdictional areas is not
within the scope of the code. The inclusion of a material even though indicated as approved for purposes of this
code, does not infer unqualified endorsement as to its selection of serviceability in any or every installation. As
interpretations may be required, and as unforeseen situations arise which are not specifically covered in this code,
the Department has traditionally used and will continue to use the following twenty-two principles to define the
intent
Principle No. 1. All occupied premises shall have potable water. All premises intended for human habitation,
occupancy, or use shall be provided with a supply of potable water. Such a water supply shall not be connected
with unsafe water sources, nor shall it be subject to the hazards of backflow or back-siphonage.
Principle No. 2. Adequate water required. Plumbing fixtures, devices, and appurtenances shall be supplied with
water in sufficient volume and at pressures adequate to enable them to function properly and without undue
noise under normal conditions of use.
Principle No. 3. Hot water required. Hot water shall be supplied to all plumbing fixtures which normally need or
require hot water for their proper use and function.
Principle No. 4. Water conservation. Plumbing shall be designed and adjusted to use the minimum quantity of
water consistent with proper performance and cleaning.
Principle No. 5. Safety devices. Devises for heating and storing water shall be so designed and installed as to
guard against dangers from explosion or overheating,
Principle No. 6. Use public sewer where available. Every building with installed plumbing fixtures and intended
for human habitation, occupancy, or use, and located on premises where public sere is on or passes said
premises within a reasonable distance shall be connected to the sewer.
Principle No. 7. Required plumbing fixtures. Each family dwelling unit shall have at least one water closet, one
lavatory, one kitchen-type sink, and one bathtub or shower to meet the basic requirements of sanitation and
personal hygiene. All other structures for human habitation shall be equipped with sufficient sanitary facilities.
Plumbing fixtures shall be made of durable, smooth, non-absorbent and corrosion resistant material and shall be
free from concealed fouling surfaces.
Principle No. 8. Drainage system shall be designed, constructed and maintained to guard against fouling,
deposit of solids and clogging, and with adequate cleanouts so arranged that the pipes may be readily cleaned.
Principle No. 9. Durable materials and good workmanship. The piping of the plumbing system shall be of
durable material, free from defective workmanship and so de3signed and constructed as to give satisfactory
service for its reasonable expected life.
Principle No. 10. Fixture traps. Each fixture directly connected to the drainage system shall be equipped with a
liquid seal trap.
20
Principle No. 11. Trap seal shall be protected. The drainage system shall be designed to provide an adequate
circulation of air in all pipes with no danger of siphonage, aspiration, or forcing of trap seals under conditions of
ordinary use.
Principle No. 12. Exhaust of foul air to outside. Each vent terminal shall extend to the outer air and be so
installed as to minimize the possibilities of clogging and the return of foul air to the building.
Principle No. 13. Test and plumbing system. The plumbing system shall be subjected to such tests as will
effectively disclose all leaks and defects in the work or the material.
Principle No. 14. Exclude certain substances from the plumbing system. No substance which will clog or
accentuate clogging of pipes, produce explosive mixtures, destroy the pipes or their joints, or interfere unduly
with the sewage-disposal process shall be allowed to enter the building drainage system.
Principle No. 15. Prevent contamination. Proper protection shall be provided to prevent contamination of food,
water, sterile goods, and similar materials by backflow of sewage. When necessary, the fixtures, device, or
appliance shall be connected indirectly with the building drainage system.
Principle No. 16. Light and ventilation. No water closet or similar fixture shall be located in a room or
compartment which is not properly lighted and ventilated.
Principle No. 17. Individual sewage disposal systems. If water closets or other plumbing fixtures are installed in
buildings where there is no sewer within a reasonable distance, suitable provision shall be made for disposing of
the sewage by some accepted method of sewage treatment and disposal.
Principle No. 18. Prevent sewer flooding. When a plumbing system is subject to backflow of sewage from the
public sewer, suitable provision shall be made to prevent its overflow in the building.
Principle No. 19. Proper maintenance. Plumbing systems shall be maintained in a safe and serviceable
condition from the stand point of both mechanics and health.
Principle No. 20. Fixtures shall be accessible. All plumbing fixtures shall be so installed with regard to spacing
as to be accessible for their intended use and for cleaning.
Principle No. 21. Structural Safety. Plumbing shall be installed with due regard to preservation of the strength
of structural members and prevention of damage to walls and other surfaces through fixture usage.
Principle No. 22. Protect ground and surface water. Sewage or other waste shall not be discharged into surface
or sub-surface water unless it has first been subjected to some acceptable form of treatment.
21
22
Kentucky
State Plumbing Code
815 KAR Chapter 20
23
815 KAR 20:010. Definitions for 815 KAR Chapter 20.
RELATES TO: KRS 132.010(9), (10), Chapter 318
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department to promulgate an
administrative regulation establishing the Kentucky State Plumbing Code to regulate plumbing. This administrative
regulation establishes definitions for terms used in 815 KAR Chapter 20.
Section 1. Definitions. (1) "ABS" means acrylonitrile-butadiene-styrene.
(2) "Administrative authority" means the Department of Housing, Buildings and Construction or any person or
agency authorized by the department to administer and enforce the provisions of the state plumbing code.
(3) "Air break" means a piping arrangement for a drainage system in which a drain from a fixture, appliance, or
device discharges indirectly into another fixture, receptacle, or interceptor at a point below the flood level rim.
(4) "Air gap" means, for a drainage system, the unobstructed vertical distance through the free atmosphere
between the outlet of waste pipe and the flood level rim of the receptacle into which it is discharging.
(5) "Air gap" means, for a water distribution system, the unobstructed vertical distance through the free
atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture, or
other device and the flood level rim of the receptacle.
(6) "Anchors" means "supports" as defined by this administrative regulation.
(7) "Apprentice" is defined by KRS 318.010(7).
(8) "Approved" means accepted or acceptable under an applicable specification stated or cited in this code.
(9) "Area drain" means a receptacle designed to collect surface or storm water from an open area.
(10) "Aspirator" means a fitting or device supplied with water or other fluid under positive pressure, which passes
through an integral orifice or "constriction" causing a vacuum. Aspirators are often referred to as "suction"
apparatus and are similar in operation to an ejector.
(11) "ASTM" means American Society for Testing and Materials.
(12) "Autopsy table" means a fixture or table used for postmortem examination of a body.
(13) "Backflow" means the flow of water or other liquids, mixtures, or substances into the distributing pipes of a
potable supply of water from any source or sources other than its intended source. Back siphonage is one type of
backflow.
(14) "Backflow connection" means any arrangement whereby backflow may occur (see "cross connection" as
defined by this administrative regulation).
(15) "Backflow preventer" means a device or means to prevent backflow.
(16) "Backflow preventer, reduced pressure zone type" means an assembly of differential valves and check
valves, including an automatically opened spillage port to the atmosphere.
(17) "Back siphonage" means the flowing back of used, contaminated, or polluted water from a plumbing fixture
or vessel or other sources into a potable water supply pipe due to a negative pressure in a pipe.
(18) "Basement" means the lowest level of a dwelling unit, which is wholly or partly below the ground level in
which the entrance and exit is made by use of a stairway or other mechanical means and which may or may not
have an entrance and exit at the basement floor level.
(19) "Basement floor drain" means a drain placed in the basement floor of a residence that does or does not
receive sanitary waste water.
(20) "Battery of fixtures" means any group of two (2) or more similar adjacent fixtures that discharge into a
common horizontal waste or soil branch.
(21) "Bedpan hopper" means "clinical sink" as defined by this administrative regulation.
(22) "Bedpan steamer or boiler" means a fixture used for scalding bedpans or urinals by direct application of
steam of boiling water.
(23) "Bedpan unit" means a small workroom in the nursing area designed and equipped for emptying, cleaning,
and sometimes for steaming bedpans, and for no other purpose.
(24) "Bedpan washer and sterilizer" means a fixture designed to wash bedpans and to flush the contents into
the sanitary drainage system. It can also provide for disinfecting utensils by scalding with steam or hot water.
(25) "Bedpan washer hose" means a device supplied with hot and cold water and located adjacent to a water
closet or clinical sink to be used for cleaning bedpans.
(26) "Boiler blow-off" means an outlet on a boiler to permit emptying or discharge of sediment.
(27) "Boiler blow-off tank" means a vessel designed to receive the discharge from a boiler blow-off outlet and
to cool the discharge to a temperature that permits its safe discharge to the drainage system.
(28) "Branch" means that part of the piping system that extends horizontally, at a slight grade, with or without
lateral or vertical extensions or vertical arms, from the main to receive fixture outlets not directly connected to the
main.
(29) "Branch, fixture" means "fixture branch" as defined by this administrative regulation.
24
(30) "Branch interval" means a distance along a soil or waste stack corresponding in general to a story height,
but in no case less than eight (8) feet, within which the horizontal branches from one (1) floor or story of a building
are connected to the stack.
(31) "Branch vent" means a vent connecting one (1) or more individual vents with a vent stack or stack vent.
(32) "Building" means a structure having walls and a roof designed and used for the housing, shelter, enclosure,
or support of persons, animals or property.
(33) "Building classification" means the arrangement of buildings in classes according to occupancy.
(34) "Building drain" means that part of the lowest piping of a drainage system that receives the discharge from
soil, waste, or other drainage pipes inside the walls of the building and conveys it to the building sewer beginning
two (2) feet outside the building wall.
(35) "Building drain; combined" means a building drain that conveys both sewage and storm water or other
drainage.
(36) "Building drain; sanitary" means a building drain that conveys sewage only.
(37) "Building drain; storm" means a building drain that conveys storm water or other drainage but not sewage.
(38) "Building gravity drainage system" means a drainage system that drains by gravity into the building sewer.
(39) "Building sewer" means that part of the drainage system that extends from the end of the building drain and
conveys its discharge to a public sewer, private sewer, individual sewage-disposal system, or other point of
disposal.
(40) "Building sewer; combined" means a building sewer that conveys both sewage and storm water or other
drainage.
(41) "Building sewer; sanitary" means a building sewer that conveys sewage only.
(42) "Building sewer; storm" means a building sewer that conveys storm water or other drainage but no sewage.
(43) "Building subdrain" means that portion of a drainage system that does not drain by gravity into the building
sewer.
(44) "Cesspool" means a lined and covered excavation in the ground that receives a discharge of domestic
sewage or other organic wastes from a drainage system, so designed as to retain the organic matter and solids,
but permitting the liquids to seep through the bottom and sides.
(45) "Circuit vent" means a branch vent that serves two (2) or more traps and extends from the downstream side
of the highest fixture connection of a horizontal branch to the vent stack.
(46) "Clinical sink" or “bedpan hopper” means a fixture for the rinsing of bedpans and soiled linens.
(47) "Code" is defined by KRS 318.010(11).
(48) "Combination fixture" means a fixture combining one (1) sink and laundry tray or a two (2) or three (3)
compartment sink or laundry tray in one (1) unit.
(49) "Combined building drain" means "building drain; combined" as defined by this administrative regulation.
(50) "Combined building sewer" means "building sewer; combined" as defined by this administrative regulation.
(51) "Combination waste and vent system" means a specially designed system of waste piping embodying the
horizontal wet venting of one (1) or more sinks or floor drains by means of a common waste and vent pipe
adequately sized to provide free movement of air above the free water surface in the drain.
(52) "Common vent" means a vent connecting at the junction of two (2) fixture drains and serving as a vent for
both fixture drains.
(53) "Conductor" means a pipe inside the building that conveys storm water from the roof to a storm or combined
building drain.
(54) "Continuous vent" means a vertical vent that is a continuation of the drain to which it connects.
(55) "Continuous waste" means a drain from two (2) or more fixtures connected to a single trap.
(56) "Cross connection" means any physical connection or arrangement between two (2) otherwise separate
piping systems, one (1) of which contains potable water and the other either water of unknown or questionable
safety or steam, gas, or chemical whereby there could be a flow from one (1) system to the other, the direction of
flow depending on the pressure differential between the two (2) systems. (See "backflow" and "back siphonage"
as defined by this administrative regulation.)
(57) "Dead end" means a branch leading from a soil, waste or vent pipe, building drain, or building sewer, and
terminating at a developed length of two (2) feet or more by means of a plug, cap, or other closed fitting.
(58) "Developed length" means the length of a pipe line measured along the center line of the pipe and fittings.
(59) "Diameter" means the nominal diameter as designated commercially.
(60) "Domestic sewage" means the waterborne wastes derived from ordinary living processes.
(61) "Double offset" means two (2) changes of direction installed in succession or series in a continuous pipe.
(62) "Downspout" means "leader" as defined by this administrative regulation.
(63) "Drain" means any pipe that carries waste water or waterborne wastes in a building drainage system.
(64) "Drainage pipe" means "drainage system" as defined by this administrative regulation.
25
(65) "Drainage system"(a) Means all the piping, within public or private premises, which conveys sewage, rain
water, or other liquid wastes to a point of disposal; and
(b) Does not mean:
1. The mains of a public sewer system;
2. A private or public sewage-treatment or disposal plant; or
3. Plumbing appliances.
(66) "Drainage system" means, for building gravity, a drainage system that drains by gravity into the building
sewer.
(67) "Drainage system" means, for a sub-building, "building sub-drain" as defined by this administrative
regulation.
(68) "Dry well" means "leaching well" as defined by this administrative regulation.
(69) "Dual vent" means "common vent" as defined by this administrative regulation.
(70) "Durham system" means a soil or waste system in which all piping is of threaded pipe, tube, or other rigid
construction, using recessed drainage fittings to correspond to the types of piping.
(71) "Dwelling unit" means one (1) or more rooms with provision for living, sanitary, and sleeping facilities
arranged for the use of one (1) family or individual.
(72) "DWV" means drain, waste, and vent piping as used in common plumbing practice.
(73) "Effective opening" means the minimum cross-sectional area at the point of water supply discharge,
measured or expressed in terms of diameter of a circle, or if the opening is not circular, the diameter of a circle of
equivalent cross-sectional area.
(74) "Ejector" means "aspirator" as defined by this administrative regulation.
(75) "Existing work" means a plumbing system or any part thereof installed prior to the effective date of this
code.
(76) "Farm" as associated with "farmstead" as defined by KRS 318.010(8), means property with a bona fide
"agricultural land" or "horticultural land" use as defined by KRS 132.010(9) and (10) and qualified by and registered
with the PVA in that county.
(77) "Fire line" means a system of pipes and equipment used exclusively to supply water for extinguishing fires.
(78) "Fixture" means "plumbing fixture" as defined by this administrative regulation.
(79) "Fixture branch" means the piping distance between a soil, waste, and vent stack and the fixture trap.
(80) "Fixture drain" means the drain from the trap of a fixture to the junction of that drain with any other drain
pipe.
(81) "Fixture supply" means the water supply pipe connecting a fixture to a branch water supply pipe or directly
to a main water supply pipe.
(82) "Fixture unit, drainage (d.f.u.)" means a measure of the probable discharge into the drainage system by
various types of plumbing fixtures. The drainage fixture-unit valve for a particular fixture depends on its volume
rate of drainage discharge, on the time duration of a single drainage operation, and on the average time between
successive operations. (Note: In general, on small systems, one (1) drainage fixture unit approximates one (1)
cubic foot per minute.)
(83) "Fixture unit, supply (s.f.u.)" means a measure of the probable hydraulic demand on the water supply by
various types of plumbing fixtures. The supply fixture-unit valve for a particular fixture depends on its volume rate
of supply, on the time duration of a single supply operation, and on the average time between successive
operations.
(84) "Flood level" means "flood level rim" as defined by this administrative regulation.
(85) "Flood level rim" means the edge of the receptacle from which water overflows.
(86) "Flooded" means the condition that results at the point the liquid in a container or receptacle rises to the
flood-level rim.
(87) "Floor drain" means a drain placed in the floor of a building for the purpose of receiving sanitary waste
water.
(88) "Floor pantry" means a workroom in the nursing area designed and equipped to prepare supplemental diets
or beverages, and to assemble food trays at meal times if used in conjunction with decentralized food service.
(89) "Flow pressure" means the pressure in the water supply pipe near the faucet or water outlet while the faucet
or water outlet is wide-open and flowing.
(90) "Flush valve" means a device located at the bottom of a tank for slushing water closets and similar fixtures.
(91) "Flushing type floor drain" means a drain that is equipped with an integral water supply enabling flushing
of the drain receptor and trap.
(92) "Flushometer valve" means a device that discharges a predetermined quantity of water to fixtures for
flushing purposes and is closed by direct water pressure.
(93) "Frost-proof closet" means a hopper with no water in the bowl and with the trap and water supply control
valve located below frost line.
26
(94) "Grade" means the fall (slope) of a line of pipe in reference to a horizontal plane. In drainage it is usually
expressed as the fall in a fraction of an inch per foot length of pipe.
(95) "Grade plane" means a reference plane representing the average of finished ground level adjoining the
building at exterior walls. Where the finished ground level slopes away from the exterior walls, the reference plane
is established by the lowest points within the area between the building and the lot line or, where the lot line is
more than six (6) feet (1,829 mm) from the building, between the building and a point six (6) feet (1,829 mm) from
the building.
(96) "Grease interceptor" means "interceptor" as defined by this administrative regulation.
(97) "Grease trap" means "interceptor" as defined by this administrative regulation.
(98) "Grillage" means sand, pea gravel, or limestone rock sizes #57 and smaller used for bedding for piping
systems.
(99) "Hangers" means "supports" as defined by this administrative regulation.
(100) "Horizontal branch drain" means a drain branch pipe extending laterally from a soil or waste stack or
building drain, with or without vertical sections or branches, which receives the discharge from one (1) or more
fixture drains and conducts it to the soil or waste stack or to the building drain.
(101) "Horizontal pipe" means any pipe or fitting that makes an angle of less than forty-five (45) degrees with
the horizontal.
(102) "Hose bibb" means a sill cock, wall hydrant, or similar faucet with a downward angled threaded nozzle.
(103) "Hot water" means water at a temperature of not less than 120 degrees Fahrenheit.
(104) "House drain" means "building drain" as defined by this administrative regulation.
(105) "House sewer" means "building sewer" as defined by this administrative regulation.
(106) "Indirect waste pipe" means a waste pipe not directly connected with the drainage system, but which
discharges into the drainage system through an air break or air gap into a trap, fixture, receptor, or interceptor.
(107) "Individual sewage disposal system" means a system for disposal of domestic sewage by means of a
septic tank, cesspool, or mechanical treatment, designed for use apart from a public sewer to serve a single
establishment or building.
(108) "Individual vent" means a pipe installed to vent a fixture drain. It connects with the vent system above the
fixture served or terminates outside the building into the open air.
(109) "Individual water supply" means a supply other than an approved public water supply which serves one
(1) or more families.
(110) "Industrial floor drain" means a drain placed in the floor of a building other than in a toilet room or shower
room to receive waste water.
(111) "Industrial wastes" means liquid wastes resulting from the processes employed in industrial and
commercial establishments.
(112) "Insanitary" means contrary to sanitary principles; injurious to health.
(113) "Interceptor" means a device designed and installed so as to separate and retain deleterious, hazardous,
or undesirable matter from normal wastes while permitting normal sewage or liquid wastes to discharge into the
drainage system by gravity.
(114) "Installed" means altered, changed, or a new installation.
(115) "Invert" means the lowest portion of the inside of any horizontal pipe.
(116) "Kitchen sink unit" means a sink, double or single compartment, food waste disposer, and dishwasher
placed in a unit so arranged that the dishwasher abuts the sink.
(117) "Lavatory" means a hand basin, such as in a bathroom.
(118) "Leaching well or pit" means a pit or receptacle having porous walls that allow the contents to seep into
the ground.
(119) "Leader" means an exterior drainage pipe for conveying storm water from roof or gutter drains.
(120) "Liquid waste" means the discharge from any fixture, appliance, area or appurtenance, which does not
contain fecal matter.
(121) "Load factor" means the percentage of the total connected fixture unit flow that is likely to occur at any
point in the drainage system.
(122) "Local vent stack" means a vertical pipe to which connections are made from the fixture side of traps and
through which vapor and foul air can be removed from the fixture or device used on bedpan washers.
(123) "Local ventilating pipe" means a pipe through which foul air is removed from a room or fixture.
(124) "Loop vent" means a circuit vent that loops back to connect with a stack vent instead of a vent stack.
(125) "Main" means the horizontal, vertical, and continuous piping that receives the waste, soil, main, or individual
vents from fixture outlets, or traps, directly or through branch pipes.
(126) "Main sewer" means "public sewer" as defined by this administrative regulation.
(127) "Main vent" means the principal artery of the venting system to which vent branches can be connected.
(Manufacturer's Floor Drain. See "industrial floor drain" as defined by this administrative regulation.)
(128) "Multiple dwelling" means a building containing more than two (2) dwelling units.
27
(129) "Nominal pipe size" means a standard expression in inches and fractions thereof to designate the
approximate inside diameter of a pipe, conduit, or tube.
(130) "Non-potable water" means water not safe for drinking, personal, or culinary use.
(131) "Nuisance" means dangerous to human life or detrimental to health; whatever building, structure, or
premise is not sufficiently ventilated, sewered, drained, cleaned or lighted, in reference to its intended or actual
use; and whatever renders the air or human food or drink or water supply unwholesome.
(132) "Nurses' station" means an area in the nursing unit separated from the corridor by counter or desk,
designed to permit nurses to record and file each patient's history and progress, observation, and control of
corridor, preparation of medicines, and maintain contact with patients, the hospital, and the outside by local and
public means of communication.
(133) "Offset" means a combination of elbows or bends that bring one (1) section of the pipe out of line but into
a line parallel with the other section.
(134) "Oil interceptor" means "interceptor" as defined by this administrative regulation.
(135) "Person" is defined by KRS 318.010(9).
(136) "Pitch" means "grade" as defined by this administrative regulation.
(137) "Plumbing" is defined by KRS 318.010(4).
(138) "Plumbing appliance" means any one (1) of a special class of plumbing fixture that is intended to perform
a special function. Its operation and control may be dependent upon one (1) or more energized components, such
as motors, controls, heating elements, or pressure or temperature-sensing elements. Fixtures can operate
automatically through one (1) or more of the following actions:
(a) A time cycle;
(b) A temperature range;
(c) A pressure range;
(d) A measured volume or weight; or
(e) Manual adjustment or control by the user or operator.
(139) "Plumbing appurtenance" means a manufactured device, or a prefabricated assembly of component
parts, and is an adjunct to the basic piping system and plumbing fixtures. An appurtenance demands no additional
water supply, nor does it add any discharge load to a fixture or the drainage system. It is presumed that it performs
some useful function in the operation, maintenance, servicing, economy, or safety of the plumbing system.
(140) "Plumbing fixture": (a) means a receptacle or device that is either permanently or temporarily connected
to the water distribution system of the premises, and demands a supply of water therefrom, or it discharges used
water, liquid-borne waste materials, or sewage either directly or indirectly to the drainage system of the premises,
or that requires both a water supply connection and a discharge to the drainage system of the premises; and
(b) Does not mean piping that carries water or sewage.
(141) "Plumbing inspector" means a duly authorized employee or agent of the Department of Housing, Buildings
and Construction who is charged with the responsibility of inspecting plumbing installations and with the
enforcement of the state plumbing laws and code.
(142) "Plumbing repair" means as used in the code to mean replacing a part or putting together that which is
torn or broken.
(143) "Plumbing system" means the following: appliances and water heaters; the water supply distributing pipes;
the fixtures and fixture traps; the soil, waste and vent pipes; the house drain and house sewer; the storm water
drainage within a building with their devices, appurtenances and connections all within and adjacent to the
building.
(144) "Pool" means "swimming pool" as defined by this administrative regulation.
(145) "Potable water" means water free from impurities present in amounts sufficient to cause disease or harmful
physiological effects and conforming in its bacteriological and chemical quality to the requirements of the Division
of Water in 401 KAR Chapter 8 or the administrative regulations of the Department of Housing, Buildings and
Construction.
(146) "Private or private use" means, in the classification of plumbing fixtures, private applies to fixtures in
residences and apartments and to fixtures in private bathrooms of hotels as well as similar installations in other
buildings where the fixtures are intended for the use of a family or an individual.
(147) "Private sewer" means a sewer, serving two (2) or more buildings, privately owned, and not directly
controlled by public authority.
(148) "Public or public use" means, in the classification of plumbing fixtures, public applies to fixtures in general
toilet rooms of schools, gymnasiums, hotels, railroad stations, public buildings, bars, public comfort stations, and
other installations (whether pay or free) where a number of fixtures are installed so that the fixtures use is similarly
unrestricted.
(149) "Public sewer" means a common sewer directly controlled by public authority.
(150) "Public water main" means a water supply pipe for public use controlled by public authority.
(151) "PVC" means polyvinyl chloride.
28
(152) "Receptor" means a fixture or device that receives the discharge from indirect waste pipes.
(153) "Relief vent" means an auxiliary vent that permits additional circulation of air in or between drainage and
vent systems.
(154) "Replace" means to put something new or rebuilt in the place of that which was existing.
(155) "Return offset" means a double offset installed so as to return the pipe to its original alignment.
(156) "Revent pipe" means "individual vent" as defined by this administrative regulation.
(157) "Rim" means an unobstructed open edge of a fixture.
(158) "Riser" means a water supply pipe that extends vertically one (1) full story or more to convey water to
branches or to a group of fixtures.
(159) "Roof drain" means a drain installed to receive water collecting on the surface of a roof and to discharge it
into a leader or a conductor.
(160) "Roughing-in" means the installation of all parts of the plumbing system that can be completed prior to the
installation of fixtures. This includes drainage, water supply, vent piping, and the necessary fixture supports.
(161) "Safe waste" means "indirect waste pipe" as defined by this administrative regulation.
(162) "Sand interceptor" means "interceptor" as defined by this administrative regulation.
(163) "Sand trap" means "interceptor" as defined by this administrative regulation.
(164) "Sanitary sewer" means a sewer that carries sewage and excludes storm, surface, and ground water.
(165) "Scrub sink" means a device usually located in the operating suite to enable operating personnel to scrub
their hands prior to operating procedures. The hot and cold water supply is activated by a knee-action mixing
valve or by wrist or pedal control.
(166) "Seepage well or pit" means a covered pit with open-jointed lining into which septic tank effluent is received
that will seep or leach into the surrounding porous soil.
(167) "Separator" means "interceptor" as defined by this administrative regulation.
(168) "Septic tank" means a watertight receptacle that receives the discharge of a building sanitary drainage
system or part thereof, and is designed and constructed so as to digest organic matter through a period of
detention and allow the liquids to discharge into the soil outside of the tank through a system of open joint or
perforated piping, or a seepage pit.
(169) "Sewage" means any liquid waste containing animal or vegetable matter in suspension or solution, including
liquids containing chemicals in solution.
(170) "Sewage ejector" means a device for lifting sewage by entraining it in a high velocity jet of steam air or
water.
(171) "Side vent" means a vent connecting to the drain pipe through a fitting at an angle not greater than forty-
five (45) degrees to the vertical.
(172) "Size of pipe and tubing" means "diameter" as defined by this administrative regulation.
(173) "Slope" means "grade" as defined by this administrative regulation.
(174) "Soil pipe" means any pipe that conveys the discharge of water closets or similar fixtures, with or without
the discharges from other fixtures, to the house drain.
(175) "Soil vent" means "stack vent" as defined by this administrative regulation.
(176) "Special wastes" means wastes that require special treatment before entry into the normal plumbing
system.
(177) "Special waste pipe" means pipes that convey special wastes.
(178) "Stack" means any vertical line of soil, waste, or vent piping.
(179) "Stack group" means a group of fixtures located adjacent to the stack so that by means of proper fittings,
vents can be reduced to a minimum.
(180) "Stack vent" means the extension of a soil or waste stack above the highest horizontal drain connected to
the stack.
(181) "Stack venting" means a method of venting a fixture or fixtures through the soil or waste stack.
(182) "Sterilizer, boiling type" means a fixture (non-pressure type), used for boiling instruments, utensils, and
other equipment (used for disinfection). Some devices are portable; others are connected to the plumbing system.
(183) "Sterilizer, instrument" means a device for the sterilization of various instruments.
(184) "Sterilizer, pressure instrument washer-sterilizer" means a fixture (pressure vessel) designed to both
wash and sterilize instruments during the operating cycle of the fixture.
(185) "Sterilizer, pressure (autoclave)" or "autoclave" means a fixture (pressure vessel) designed to use steam
under pressure for sterilizing.
(186) "Sterilizer, utensil" means a device for the sterilization of utensils as used in hospital services.
(187) "Sterilizer vent" means a separate pipe or stack, indirectly connected to the building drainage system at
the lower terminal, which receives the vapors from non-pressure sterilizers, or the exhaust vapors from the
pressure sterilizers, and conducts the vapors directly to the outer air. Sometimes a sterilizer vent is referred to as
vapor, steam, atmospheric, or exhaust vent.
(188) "Sterilizer, water" means a device for sterilizing water and storing sterile water.
29
(189) "Still" means a device used in distilling liquids.
(190) "Storm drain" means building storm drain.
(191) "Storm sewer" means a sewer used for conveying rain water, surface water, condensate, cooling water,
or similar liquid wastes.
(192) "Subsoil drain" means a drain that collects subsurface water and conveys it to a place of disposal.
(193) "Sump" means a tank or pit, which receives sewage or liquid waste, located below the normal grade of the
gravity system and that is emptied by mechanical means.
(194) "Sump pump" means a mechanical device, other than an ejector or bucket, for removing sewage or liquid
waste from a sump.
(195) "Supports" means devices for supporting and securing pipe, fixtures, and equipment.
(196) "Swimming pool" means any structure, basin, chamber, or tank containing any artificial body of water for
swimming, diving, wading or recreational bathing.
(197) "Trap" means a fitting or device that provides a liquid seal to prevent the emission of sewer gases without
materially affecting the flow of sewage or waste water through it.
(198) "Trap arm" means that portion of a fixture drain between a trap and its vent.
(199) "Trap primer" means a device or system of piping to maintain a water seal in a trap, typically installed
where infrequent use of the trap would result in evaporation of the trap seal, such as floor drains.
(200) "Trap seal" means the vertical distance between the crown weir and the top of the dip of the trap.
(201) "Utility room" means a workroom in the patient nursing area, designed and equipped to facilitate
preparation, cleaning, and incidental sterilizing of the various supplies, instruments, and utensils involved in
nursing treatment and care, exclusive of medications handled in nurses' stations and bedpan cleaning and
sterilizing.
(202) "Vacuum" means any pressure less than exerted by the atmosphere.
(203) "Vacuum breaker" means "backflow preventer" as defined by this administrative regulation.
(204) "Vacuum breaker, non-pressure type (atmospheric)" means a vacuum breaker that is not designed to
be subjected to static line pressure.
(205) "Vacuum breaker, pressure type" means a vacuum breaker designed to operate under conditions of static
line pressure.
(206) "Vent pipe" means any pipe provided to ventilate a house drainage system and to prevent tray siphonage
and back pressure.
(207) "Vent system" means a pipe or pipes installed to provide a flow of air to or from a drainage system or to
provide a circulation of air within the system to protect trap seals from siphonage and back pressure.
(208) "Vertical pipe" means any pipe or fitting that makes an angle of forty-five (45) degrees or less with the
vertical.
(209) "Wall hung water closet" means a wall mounted water closet installed in such a way that no part of the
water closet touches the floor.
(210) "Waste pipe and special waste" means any pipe that receives the discharge of any fixture (except water
closets or similar fixtures) and discharges to the house drain, soil, or waste stacks. If a pipe does not connect
directly with a house drain, waste, or soil stack, the pipe is considered to contain special waste.
(211) "Water distributing pipe" means a pipe within the building or on the premises that conveys water from the
water-service pipe or meter to the point of usage.
(212) "Water lifts" means "sewage ejector" as defined by this administrative regulation.
(213) "Water outlet" means a discharge opening through which water is supplied to a fixture, into the atmosphere
(except into an open tank that is part of the water supply), to a boiler or heating system, or to any devices or
equipment requiring water to operate but that are not part of the plumbing system.
(214) "Water riser pipe" means "riser" as defined by this administrative regulation.
(215) "Water service pipe" means the pipe from the water main or other source of potable water supply to the
water distributing system of the building served.
(216) "Water supply stub" means a vertical pipe less than one (1) story in height supplying one (1) or more
fixtures.
(217) "Water supply system" means the water service pipe, the water-distributing pipes, and the necessary
connecting pipes, fittings, control valves, and all appurtenances in or adjacent to the building or premises.
(218) "Well, bored" means a well-constructed by boring a hole in the ground with an auger and installing a casing.
(219) "Well, drilled" means a well-constructed by making a hole in the ground with a drilling machine of any type
and installing casing and screen.
(220) "Well, driven" means a well-constructed by driving a pipe in the ground. The drive pipe is usually fitted with
a well point and screen.
(221) "Well, dug" means a well-constructed by excavating a large diameter shaft and installing a casing.
(222) "Wet vent" means a vent that receives the discharge of wastes other than from water closets.
30
(223) "Yoke vent" means a pipe connecting upward from a soil or waste stack to a vent stack for the purpose of
preventing pressure changes in the stack. (Recodified from 401 KAR 1:010, 7-5-1978; Am. 9 Ky.R. 827; eff. 2-2-
1983; 12 Ky.R. 1659; eff. 5-6-1986; 13 Ky.R. 779; eff. 11-11-1986; 950; eff. 12-2-1986; 14 Ky.R. 1116; eff. 1-4-
1988; 16 Ky.R. 2758; 17 Ky.R. 1092; eff. 8-22-1990; 20 Ky.R. 3112; eff. 7-7-1994; TAm eff. 8-9-2007; 43 Ky.R.
615, 987; eff. 1-6-2017.)
31
815 KAR 20:012. Sections declared independent.
RELATES TO: KRS Chapter 318
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: The office is directed by KRS 318.130 through the State
Plumbing Code Committee to adopt and put into effect a State Plumbing Code. This administrative regulation
relates to the sovereignty of each section as it relates to other sections of the code. As KRS 446.090 provides for
severability of statutes, so does this administrative regulation provide for the severability of plumbing code
provisions.
Section 1. Sections Declared Independent. If any part of this code shall be held unconstitutional, the remaining
parts shall remain in force, unless the remaining parts are so essentially and inseparably connected with and
dependent upon the unconstitutional part that it is apparent that the General Assembly or the office would not
have enacted the remaining parts without the unconstitutional part, or unless the remaining parts, standing alone,
are incomplete and incapable of being executed in accordance with the intent of the General Assembly. (12 Ky.R.
1967; Am. 13 Ky.R. 237; eff. 7-2-86; TAm eff. 8-9-2007; Recodified from 815 KAR 20:001, 3-24-2010.)
815 KAR 20:015. Fees and refunds.
RELATES TO: KRS 318.050, 318.054, 318.134
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.050, 318.054, and 318.134 authorize the office to
establish license and permit fees. KRS 318.130 requires the department to establish a State Plumbing Code and
authorizes the department to promulgate reasonable rules or administrative regulations to administer KRS
Chapter 318. This administrative regulation establishes methods of payment of fees, a penalty for returned
payments, and the requirements to receive a refund of installation permit payments.
Section 1. Fees. (1) Fees payable to the Division of Plumbing shall be paid by:
(a) Money order;
(b) Check;
(c) Credit card;
(d) Debit card;
(e) Electronic funds transfer; or
(f) United States coins and currency.
(2) All fees shall be made payable to the Kentucky State Treasurer.
Section 2. Returned Payments. (1) If a fee is returned to the Division of Plumbing for nonpayment, the payor
shall be assessed a fee of thirty-five (35) dollars, except if proof of fault of the financial institution is provided.
(2) A company or individual notified of a returned payment shall, for a period of six (6) months, make all payments
to the Division of Plumbing by:
(a) Cashier’s check;
(b) Certified check;
(c) Money order;
(d) Electronic funds transfer; or
(e) United States coins and currency.
Section 3. Permit Refunds. A refund for an installation permit shall be given if:
(1) The refund request is made within twelve (12) months of purchase;
(2) Work has not begun on the project for which the permit was issued; and
(3) A processing fee of twenty (20) dollars is received by the Division of Plumbing.
(33 Ky.R. 3308; Am. 4172; eff. 7-6-2007; 41 Ky.R. 1197; eff. 3-6-2015.)
32
815 KAR 20:018. Kentucky Housing, Buildings and Construction Advisory Committee budget review
and responsibility.
RELATES TO: KRS 318.071, 318.136, 318.170, EO 2009-535
STATUTORY AUTHORITY: KRS 318.130, EO 2009-535
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the Department of Housing, Buildings,
and Construction to promulgate administrative regulations which put into effect a State Plumbing Code.
Additionally, KRS 318.130 authorizes the office to adopt reasonable rules or administrative regulations, after
review by the Kentucky Housing, Buildings and Construction Advisory Committee, to administer KRS Chapter
318. EO 2009-535, effective June 12, 2009, reorganized the Department of Housing, Buildings and Construction
as the Department of Housing, Buildings, and Construction, and established the commissioner, rather than
executive director, as the head of the department. This administrative regulation establishes quarterly reviews of
the Division of Plumbing's budget and fee schedule by the Kentucky Housing, Buildings and Construction Advisory
Committee,
Section 1. Budget Review. (1) The following shall be provided at least quarterly to each member of the Kentucky
Housing, Buildings and Construction Advisory Committee, by the Division of Plumbing:
(a) A current fiscal year detailed financial report consisting of current balances;
(b) A revenue report showing all revenue sources of the Division;
(c) Expenditure summaries showing expenditures including total personnel costs and operating expenses; and
(d) Any transfers made or scheduled, either to or from the Division's trust and agency funds established in KRS
318.136.
(2) The detailed report shall be delivered to each committee member at least ten (10) business days prior to each
quarterly meeting of the Kentucky Housing, Buildings and Construction Advisory Committee.
Section 2. If the Division's trust fund balance exceeds $500,000:
(1) Kentucky Housing, Buildings and Construction Advisory Committee, shall:
(a) Review the Division's staffing;
(b) Review the following fees:
1. Examination;
2. License;
3. Plumbing installation; and
4. Medical gas permitting;
(c) Review the division's current level of service; and
(d) Recommend changes needed to maintain or improve the division's level of service and accurately balance
revenues with expenditures.
(2) The division shall prepare for the Kentucky Housing, Buildings and Construction Advisory Committee, review:
(a) A staffing report detailing personnel levels, personnel costs, and personnel goals; and
(b) Fee proposals with projected effects to the division's balances from each fee. (36 Ky.R. 2271; Am.36 Ky.R.
68; 8-6-2010.)
33
815 KAR 20:020. Parts or materials list.
RELATES TO: KRS 318.010, 318.015, 318.130, 318.150, 318.200
STATUTORY AUTHORITY: KRS 198B.040(10), 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department, after review by
the Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate an administrative
regulation establishing the Kentucky State Plumbing Code regulating plumbing, including the methods and
materials that may be used in Kentucky. This administrative regulation establishes an "approved parts or materials
list" containing the parts and materials that have been approved for use in Kentucky.
Section 1. Definitions. (1) "ABS" means acrylonitrile-butadiene-styrene pipe.
(2) "APML" means the "Approved Parts or Materials List".
(3) "ASTM" means American Society for Testing Materials.
(4) "Code" is defined by KRS 318.010(11).
(5) "Committee" means the Department of Housing, Buildings and Construction Advisory Committee.
(6) "Department" means Department of Housing, Buildings, and Construction.
(7) "Parts or materials" means all types of fittings and piping used in the soil, waste and vent systems, house
sewers, potable water supply, plumbing fixtures, appurtenances, and mechanical sewage systems in plumbing
systems.
(8) "Person" is defined by KRS 318.010(9).
(9) "PVC" means polyvinyl chloride pipe.
Section 2. Approved Parts or Materials List (APML). (1) A part or material manufactured or produced
according to a specification listed in the code shall be considered approved if it meets the latest edition of the
specification.
(2) A part or material shall not be used in a drainage or plumbing system, other than those currently authorized
by the code, unless the use of the part or material has been considered by the committee and approved by the
department as being equal to or better than other similarly approved items for inclusion in the APML. The APML
may specify methods of installation or restrictions applicable to a particular part or material.
Section 3. Amending the APML. (1) A person may petition the committee, in writing, no later than fourteen (14)
days prior to the committee's next scheduled meeting for the purpose of amending the APML. The request shall
include:
(a) A description of the part or material for which approval is sought;
(b) Available technical data;
(c) A listing of other authorities which have approved the use of the part or material; and
(d) Any other pertinent information requested by the committee.
(2)(a) The committee shall consider all parts or materials for which approval is sought and shall forward its
recommendations within thirty (30) days to the department
(b) A hearing shall be held before the committee if requested by a person having an interest in the subject matter
within thirty (30) days following the determination of the committee.
(c) Upon approval of a recommendation by the department, the APML shall be amended by listing the new part
or material in Section 5 of this administrative regulation.
Section 4. Custody of the APML. The Director, Division of Plumbing, shall maintain an up-to-date APML and
make it available for inspection during regular office hours. Copies of the APML may be obtained by mailing a
self-addressed stamped envelope to the Division of Plumbing, Department of Housing, Buildings, and
Construction, 101 Sea Hero Road, Frankfort, Kentucky 40601-5405.
Section 5. Content of Approved Parts or Materials List. The following list of parts or materials have been
reviewed by the Department of Housing, Buildings and Construction Advisory Committee and approved by the
department and shall be allowed for installation in Kentucky:
(1) Flexible three-fourths (3/4) inch hot and cold water connectors for hot water heaters, minimum wall
thickness,..032;
(2)(a) Flushmate water closet tank;
(b) Microphor company. Two (2) quart flush toilets;
34
(c) Jomar 3 and 4 water conserver water closets to operate efficiently on three and one-half (3 1/2) gallons of
water per flush;
(d) Superinse toilet that operates on one (1) gallon of water per flush as manufactured by Universal Rundle for
the Thetford Wastewater Treatment Systems;
(e) IFO Sanitar AB Model-3160 and 3180 China Water Closet equipped with a Fluidmaster 4003A-F77 Ballcock;
(f) Cashsaver MX (quantum 150-1) Water Closet Combination and Flushmate II Flushometer/Tank as
manufactured by Mansfield Plumbing Products; and
(g) Dual flush water closets by Caroma, USA. The water closets shall use eight-tenths (.8) gallons for the short
flush cycle and one and six-tenths (1.6) gallons for the full flush cycle;
(3) Tubular traps with gasket in trap seal;
(4)(a) Polyethylene sump pump basin. Polyethylene sump pump basin shall be constructed of polyethylene
material and shall be provided with a sump cover;
(b) Liberty Pump Model 402, Laundry Tray Pump for pipe size one and one-half (1 1/2) inch for light commercial
and household usage;
(c) Zoeller Drain pump and HiLo Industries Power Drain for pipe sizes one and one-half (1 1/2) inch and two (2)
inch for light commercial and household usage;
(d) Little Giant Pump Company, Drainosaur Water Removal System, Model #WRS-6. This approval shall be
limited to two (2) drainage fixture units because it has a one and one-half (1 1/2) inch drain;
(e) Add A Drain (Waste Discharge System) as manufactured by Lunsford and Associates;
(f) Sta-Rite Pump Corporation, laundry tray system approved for residential and light commercial use; and
(g) Electric Drain System as manufactured by Myers for light commercial and household usage;
(5)(a) No-caulk roof flashing. No-caulk roof flashing shall be eighteen (18) inch by eighteen (18) inch galvanized
iron base with a neoprene boot forming a water tight seal with the stack that it serves;
(b) Polyethylene roof flashing. Polyethylene roof flashing shall have a base which shall extend six (6) inches in all
directions from the base of a stack and shall have a boot with a preformed thermoplastic rubber gasket;
(c) Dektite pipe flashing system to be used on metal building decks for plumbing vent stacks as manufactured by
Buildex Corporation;
(d) Oatey eighteen (18) inch by eighteen (18) inch no caulk thermoplastic flashing, one (1) piece construction,
positive double seal in three (3) inch only;
(e) Carlisle syntec systems. Vent flashings for sureseal and Brite-Ply roofing systems as required by Carlisle
Corporation;
(f) Trocal roofing systems. Vent flashings for Trocal roofing systems as required by Dynamit Nobel of American,
Inc;
(g) Masterflash Pipe Flashing system for plumbing vent stacks as manufactured by Aztec Washer Company; and
(h) Hi-Tuff Roofing Systems pipe flashing system for plumbing vent stacks as required by J.P. Stevens and
Company, Inc;
(6)(a) Kitchen sink faucet. Kitchen sink faucets may have corrugated supply piping if the piping has a wall thickness
equal to Type M copper pipe;
(b) Sink and lavatory faucets and pop-up lavatory assembly parts manufactured by CPVC plastic as manufactured
by Nibco Co.; and
(c) Series 1000 Automatic Faucets as Manufactured by Hydrotek USA, Inc;
(7) Lab-Line Enfield L-E acid waste systems, one and one-half (1 1/2) through four (4) inch inside measurement
for above and below ground installation on acid waste. Underground shall be laid on six (6) inches of sand grillage
and shall be:
(a) Backfilled by hand and tamped six (6) inches around piping; and
(b) Surrounded by six (6) inches of sand grillage;
(8) Floor drains, shower drains, urinal drains and clean-outs manufactured by Plastic Oddities, Inc;
(9) Tubular plastic components conforming to ASTM F409-75, bathtub waste and overflow, traps, continuous sink
wastes and extension tubes as manufactured by J & B Products Corporation;
(10)(a) Water heaters. Heat pump water heaters as manufactured by:
1. Dec International, Inc., Therma-Stor Products Group; or
2. Steibel Eltron Accelera 300. If the water heater is shipped with a 100 PSI Pressure and Temperature Relief
Valve, it shall be replaced with a 150 PSI Pressure and Temperature Relief Valve; and
(b) Water heaters, point of use or instantaneous;
1. In-Sink-Erator's Ultra System. For instant hot water to serve individual fixtures, Model #777W, W, WH, WA and
WHA, W-152 and W-154;
2. Eemax Electric Tankless water heaters.
a. Nonpressure type without the requirement of a temperature and pressure relief valve; or
b. The pressure type with the requirements that the temperature and pressure relief valve be of a one-half (1/2)
inch short shank valve and be installed with the product;
35
3. Vitaclimate Control Systems, Inc. - Heatrae Instantaneous Water Heaters Models 7000 and 9000, pressure
type, point of use water heater, which shall be equipped with an approved temperature and pressure relief valve
installed so that the thermo couple of the relief valve extends into the heat chamber discharge;
4. Paloma Automatic Instantaneous Gas Water Heaters Numbers PH-6DN, PH-6DP, PH-12A-DN, PH-12A-DP,
PH-12M-DN, PH-12M-DP, PH-16A-DN, PH-16A-DP, PH-16M-DN, PH-16M-DP, PH-24A-DN, PH-24A-DP, PH-
24M-DN and PH-24M-DP;
5. Rinnai Gas Fired Instantaneous Water Heaters Model Numbers REU-95GS-2R, REU-95GS-3R, REU-90, REU-
130, REU-V2520 FFU-US, REU-V2520 FFUC-US, REU-V2020W-US, REU-V2020WC-US, and REU-V1616W-
US pressure type, which shall be equipped with an approved pressure relief valve;
6. Elkay Aqua-Temp tankless water heaters - nonpressure type without the requirement of a temperature and
pressure relief valve;
7. International Technology Sales Corporation AEG Telefunken MDT instantaneous water heater, which shall be
equipped with an approved pressure relief valve;
8. International Technology Sales Corporation Zanker Faucet Model W05U without a temperature and pressure
relief valve;
9. Amtrol hot water maker model numbers WH7P, WH7 and WH7C with a minimum three-fourths (3/4) inch inlet
and outlet;
10. Chronomite Laboratories, Inc. - instantaneous water heater, which shall be equipped with an approved
pressure relief valve;
11. Chronomite Instant-Flow Tankless Water Heater without a temperature and pressure relief valve;
12. Nova Hot Water Generator Models: VES5/10, VES6/12, VES7/14, VES8/16, VES9/18 and VES11/22 as
manufactured by Hot Water Generators, Inc;
13. Aqua Star tankless gas water heaters, model numbers 125 VP and 80 VP, which shall be equipped with an
approved pressure relief valve;
14. Ariston electric water heaters, model numbers P-15S and P-10S, which shall be equipped with an approved
pressure relief valve;
15. Vaillant Corporation gas fired point of use water heater.
16. Trinom Hot Man Tankless Water Heater as manufactured by Siemens;
17. Field Controls Company Power Venter - Models PVAE and SWG for use in conjunction with gas and oil fired
water heaters;
18. Acutemp Instantaneous Water Heater as manufactured by Keltech, Inc., Model #100/208; #100/240;
#150/208; #150/240; #180/208; #180/240; #153/208; #153/240; #183/208; #183/240; #183/480 and #C183/480;
19. Hot Aqua Instantaneous Tankless Electric Water Heaters, Model Numbers, 18/125PC, 24/125PC, 24/120,
32/120, 24/240, 36/240, 48/240, 59/240, 70/240, 24/208, 35/208, 46/208, 60/208, 28/277, 42/277, 55/277, 69/277,
24/120-P, 59/240-P, 46/208-P, 55/277-P, 18/125PC and 24/125PC. This product shall not be approved for
supplying hot water for showers.
20. Stiebel Eltron Tankless Water Heater.
a. Models DHC 3, DHC 6 and DHC 8 approved for use with lavatories and sinks;
b. Models Tempra/DHC-E 8/10 and DHC-E 12;
c. Models Mini 2, Mini 3, Mini 4, and Mini 6 Point of Use tankless electric water heaters; and
d. Models 12/2 Plus, 15/15 Plus, 20/20 Plus, 24/24 Plus, 29 Plus, and 36 Plus;
21. Bosch Aqua Star tankless water heater. Models 125X, 125B, 125S, 125BS, 125FX and 38B. All models shall
be installed with pressure relief valves;
22. Controlled Energy Corporations "Powerstream" tankless water heater;
23. Ariston mini tank electric water heaters in 2.5, 4 and 6 gallon models;
24. Powerstar PS19T and PS28T Electric Instantaneous Water Heater, as manufactured by Controlled Energy
Corporation, to be installed with pressure relief valves;
25. Aquastar AQ240 FX (LP, NG) gas fired instantaneous water heater, as manufactured by Controlled Energy
Corporation, to be installed with pressure relief valve;
26. S.E.T.S. Tankless Water Heater Models: #220, #180, #165 and #145 to be installed with temperature and
pressure relief valve.
27. Rinnai Continuous Flow Water Heaters: Models 2532FFU(-C), 2532W(-C), 2532FFU and 2424W(-C) all
requiring an approved pressure relief valve;
28. Noritz American Corporation Tankless, Instantaneous Water Heater Models: N-042, N-063 to be installed with
pressure relief valve;
29. Takagi Industrial Company USA, Inc., Instantaneous Water Heaters, Models: T-KLS; T-K JR; T-K2; T-KD20
to be installed with pressure relief valve;
30. Envirotech Systems ESI 2000 Series Tankless Water Heaters, all requiring an approved pressure relief valve;
31. Quietside Instantaneous Water Heater Models: QVW8 - 100, 120, 175. All models shall be equipped with an
approved temperature and pressure relief valve and temperature preset at 120 degrees;
36
32. Seisco Tankless Water Heaters Model:
a. Point-of-Use Single Chamber Models: POU24, POU30, POU35, POU40, POU45, POU55, POU60, POU70,
POU73, POU78, POU80, POU90, POU140, SC90, and SC140. These models shall not require the installation of
a temperature and pressure relief valve;
b. Residential Single Phase Models: RA14, RA16, RA18, RA22, RA24, RA28, and RA32. These models shall not
require the installation of a temperature and pressure relief valve;
c. Commercial Single Phase Models: CA14, CA16, CA18, CA22, CA24, CA28, and CA32. These models shall not
require the installation of a temperature and pressure relief valve;
d. Commercial Three (3) Phase Models: CA9-3, CA10-3, CA12-3, and CA14-3. These models shall not require
the installation of a temperature and pressure relief valve; and
e. Electric Mini-Tank Models: SMT2.5, SMT4, and SMT6. These models require the installation of a temperature
and pressure relief valve supplied by the manufacturer;
(11) Compression joints. Fail-safe hot and cold water systems;.
(12) Orion fittings for acid waste piping systems for above and below ground;
(13) R & G Slone Manufacturing Company. Fuseal mechanical joint for the connection of polypropylene and waste
piping;
(14) Johns Manville Flex I drain roof drain system;
(15) Hydrocide liquid membrane (HLM) to be used as a shower pan material conforming to ASTM C836-76. The
density of the material shall be at least one-sixteenth (1/16) inch thick;
(16) Scotch-Clad brand waterproofing system as manufactured by the 3M Company for thin-set installation of
ceramic and quarry tile in shower stalls, bathrooms, janitorial closets limited to those applications on concrete
floors and using metallic soil and waste piping;
(17) Elkay Aqua-chill water dispensers;
(18) Flexible connectors for hot and cold potable water supply in plumbing fixture connections as manufactured
by Aqua-Flo Corporation limited to thirty (30) inch length except dishwashers which shall be forty-eight (48) inches
maximum;
(19)(a) Delta Faucet Company's quick-connect fitting known as "grabber" to be used with hot and cold potable
water installations above ground only;
(b) REMCO Angle Stop Quick connect valve for use with hot and cold potable water installations above ground
only; and
(c) Red White Valve Corporation. Reduced port polypropylene ball valves designed for installation on fusion
welded polypropylene piping systems compliant with NSF standards 61 and 14 and ASTM F2389;
(20) Interceptors:
(a) Town and Country plastic interceptors to be used as a grease trap;
(b) Grease recovery unit (GRU) as manufactured by Lowe Engineering, Lincoln Park, NJ;
(c) Scienco, Inc., models SI-101-20G, SI-104-35G, SI-102-50G and SI-103-100G with PVC solvent connections;
(d) Rockford separators for grease, oil, hair and solids in various styles and sizes and being more specifically
model series G, G LO, G M, G LOM, GF, GFE, GAS, GPS, GSS, OS, RHS, GSC, RMS, RSD, SD, SDE, GTD,
and RTD that are used for their intended purpose and installed in accordance to the manufacturer's specification
and the plumbing code;
(e) Grease interceptors as manufactured by Enpoco, Inc. of St. Charles, IL;
(f) Grease Traps U.S.A.: Polypropylene grease trap, model number GT-25, as certified by the Plumbing and Drain
Institute;
(g) Schier Grease Interceptors Trapper II Series meeting ASME 112.14.3 Model numbers 1820, 2025, 2635 and
3050;
(h) Schier Grease Interceptors Great Basin Series meeting ASME 112.14.3 Model numbers GB-75 and GB-250
approved only with the installation of two-directional, accessible cleanouts on the inlet and the outlet. The
discharge of garbage disposals shall not be permitted; and
(i) Thermaco Inc. models TZ600 (150 GPM), TZ 400 (75 GPM), and the TZ 160 (35 GPM). These interceptors
shall be installed with a full size vent (three (3) or four (4) inches as applicable per manufacturer’s instructions to
the model being installed), located on the outlet side of the interceptor and returned to the vent stack or located
so that it terminates a minimum of twelve (12) inches above the ground;
(21) Plastic Oddities Srv (sewer relief vent) clean-out;
(22) Contech A-2000 - a PVC corrugated pipe with smooth interior meeting or exceeding all the material and
service test requirements of ASTM D-3034-06 except dimensions at the time of manufacture;
(23) Nonchemical water treatment to control lime scale and corrosion buildup superior water conditioners as
manufactured by Kemtune, Inc;
(24) Eljer plumbing ware - Elgers ultra one/G water closet;
37
(25) (a) "Power Flush" and "Quik Jon" as manufactured by Zoeller Company, which shall have a three (3) inch
vent and alternate additional waste openings shall be located in the pump chamber above the top of the base
chamber; and
(b) Hydromantic JB-1 System as manufactured by Hydromantic Pumps, Inc.;
(26) Exemplar Energy garden solar water heater;
(27) ProSet systems for pipe penetrations in fire rated structures. System A for copper and steel pipe. System C
using solvent weld joints only. Proset E-Z flex coupling shall be approved for similar or dissimilar materials;
(28)(a) ABS and PVC backwater valves, Models 3281, 3282, 3283 and 3284 for solvent cement joints only as
manufactured by Canplas Industries;
(b) Flood-Gate Automatic Backwater Valve as manufactured by Bibby-Ste-Croix; and
(c) Fullport Backwater Valve as manufactured by Mainline Backflow Products, Inc.;
(29) Clamp-All Corporation Pipe Coupling Systems shall be approved size for size on dissimilar materials on new
or existing installations. The use of Snap-All Increaser/Reducer transition bushings shall be included in this
approval;
(30) Mission Rubber Company "Band-Seal Specialty Coupling" shall be approved as a transition between any
combination of the following materials: cast iron, copper, galvanized steel, schedule 40 PVC and ABS and SDR
35;
(31)(a) Laticrete 9235 Waterproof Membrane to be used as a safing material for floors and walls in showers,
bathtubs and floor drain pans;
(b) Ultra-Set as manufactured by Bostik Construction Products to be used as a water proofing material;
(32) DFW Elastomeric PVC coupling manufactured by DFW Plastics, Inc. for use on building sewers;
(33)(a) Fernco Lowflex Shielded Couplings, approved for connecting extra heavy, no-hub and service weight cast
iron pipe, DWV PVC and ABS pipe, SDR 35 sewer pipe, galvanized steel pipe and copper pipe or as a transition
between any of these materials in soil waste and vent systems above or below grade; and
(b) Fernco Proflex Shielded Couplings: Series 3000 for service weight cast iron to plastic, steel or extra cast iron
in sizes one and one-half (1 1/2) inch to four (4) inch, Series 3001 for cast iron, plastic or steel to copper in sizes
one and one-half (1 1/2) inch to two (2) inch, Series 3003 for copper to copper in one and one-half (1 1/2) inch;
(34) TBA drain, waste and vent pipe, schedule 40 PVC piping marked "meets dimensional specifications of ASTM
D-2665". This pipe shall have been tested for the tensile strength, durability, of ASTM D-2665 except that it is
made from recycled, unused plastics rather than virgin materials;
(35) Blucher-Josam stainless steel pipe, fittings and drains for disposal of corrosive wastes;
(36) Paul Panella Industries Hostalen GUR UHMW Polymer Cleanout approved for use on sewers of Schedule
40 PVC, ABS and SDR in four (4) inch and six (6) inch sizes;
(37) Advanced Drainage Systems, Inc., Series 35 polyethylene corrugated sewer pipe with a smooth interior in
sizes four (4) inch through twenty-four (24) inches for underground storm water drainage within a building;
(38) "Flowguard Gold" one (1) step CPVC cement for joining copper tube size CPVC piping systems through two
(2) inches without the requirement of a cleaner or primer;
(39) E-Z Trap Adapter as manufactured by S & S Enterprises to be used as connection between chrome plated
P trap and PVC waste line;
(40)(a) Canplas Industries LTD Specialty DWV Fittings: Part #3628 ABS or PVC forty-five (45) degree Discharge
Closet Flange, Part #2321 Appliance (dishwasher) Wye, Part #3650A Closet Flange Kit for Concrete Installations;
and
(b) Flo-Bowl Waxless Leakless Toilet System as manufactured by Flo-Bowl Systems Inc.;
(41)(a) Conbraco 78-RV Series In-Line Water Heater Shut-Off Thermal Expansion Control Valve preset at 125
psi to relieve thermal expansion; and
(b) Watts Regulator BRV Expansion Relief Valve to relieve thermal expansion;
(42) Plastic Productions PVC "Quick Stub" approved as a solvent weld transition between tubular PVC and
schedule 40 PVC;
(43) HubSett In Line Test Coupling: PVC and ABS test couplings produced by HubSett Manufacturing Inc. for
testing soil waste and vent systems;
(44) Viega/Ridgid ProPress System: Copper press fittings for joining copper water tubing and using an elastomeric
o-ring that forms the joint;
(a) The fitting shall be made by pressing the socket joint under pressure in accordance with the manufacturer’s
installation requirements; and
(b) This system shall be approved for pipe sizes one-half (1/2) inch through four (4) inch for above slab installations
only;
(45) TRIC Trenchless Systems for replacement sewers in four (4) inch and six (6) inch sizes;
(a) A video camera tape of the existing sewer shall be made to determine proper alignment and reviewed by the
plumbing inspector;
38
(b) After the installation is complete, another tape shall be reviewed by the plumbing inspector to ensure that the
installation was successful;
(c) The sewer shall be tested according to 815 KAR 20:150; and
(d) The interior heat fusion bead shall be removed to provide a smooth surface with no obstruction;
(46) Envirovac Inc.: Evac Vacuum Systems Condensate Collection System approved for condensate collection
and the discharge from lavatories only;
(47) Macerating Systems from Sanitary-for-All, consisting of a sump with a macerating pump, with or without a
macerating toilet. The sump shall be air tight and provided with a minimum one and one-fourth (1 1/4) inch vent.
These systems shall be installed in accordance with the manufacturer’s recommendations and shall not be used
as a primary means of waste disposal;
(48) Rhino Wet Waste Interceptor manufactured by Ecosystems Inc. to be used as a prefiltration of wet wastes
before discharging to a grease trap or interceptor;
(49) Quick Snap Multi Level Flange as manufactured by Jett Plumbing Products, Inc;
(50) Sioux Chief Manufacturers Stainless Steel Swivel Ring Closet Flange;
(51) Service Weight and No-Hub Cast Iron Pipe and Fittings furnished by DWV Casting Company complying with
ASTM A74, A888 and CIPI 301-00;
(52) American Pipe Lining, Inc. APL 2000, which is an epoxy lining used in restoring water distribution systems.
The use of APL 2000 shall be subject to the conditions established in paragraphs (a) through (d) of this subsection.
(a) A plumbing construction permit shall be required.
(b) Installation shall be by a licensed plumber.
(c) Water quality shall be tested before and after each project.
(d) A water distribution system treated with APL 2000 shall be clearly marked on all exposed piping and water
heater with the following notice: "FLAMELESS TECHNIQUES MUST BE USED FOR ALL REPAIRS AND
MODIFICATIONS TO THIS PIPING SYSTEM";
(53) Base Products Corporation;
(a) Water powered pump: base pump. Each model shall:
1. Be installed with a reduced pressure principle backflow preventer with copper piping only;
2. Be approved for groundwater removal only; and
3. Require incoming water pressure of 50 psi to operate; and
(b) Battery back-up pump: hydro pump;
(54) Perma-Liner Industries, Inc, Lateral Lining System.
(a) This system shall be approved for pipe sizes three (3) inches through eight (8) inches for interior and exterior
installations;
(b) Interior applications shall be videoed before and after installation and shall have a water or air test as required
by 815 KAR 20:150, Section 4(2) or (3);
(c) Exterior applications shall be videoed before and after and shall have a smoke test to comply with 815 KAR
20:150, Section 4(6); and
(d) A permit shall be obtained prior to an exterior or interior application;
(55) Stainless steel piping system for potable water applications manufactured by Victaulic for above ground
applications only;
(56) Wallgate Classic Model CME recessed and molded hand washer/dryer;
(57) MaxLiner.(a) This system shall be approved for pipe sizes three (3) inch through ten (10) inch for
interior and exterior installations;
(b) Interior applications shall be videoed before and after installation and shall have a water or air test as required
in 815 KAR 20:150, Section 4(2) or (3);
(c) Exterior applications shall be videoed before and after installation and shall have a smoke test to comply with
815 KAR 20:150, Section 4(6); and
(d) Permits shall be required for both interior and exterior applications;
(58) Nuflow Technologies Inc., Nuflow System;
(a) This system shall be approved for pipe sizes one and one-half (1 1/2) inch through twelve (12) inch for interior
and exterior installations;
(b) Interior applications shall be videoed before and after installation and shall have a water or air test as required
in 815 KAR 20:150, Section 4(2) or (3);
(c) Exterior applications shall be videoed before and after installation and shall have a smoke test to comply with
815 KAR 20:150, Section 4(6); and
(d) Permits shall be required for both interior and exterior applications;
(59) Schluter Shower System for waterproofing tiled shower installations installed per manufacturer
recommendations;
(60) WATCO Manufacturing Watco Flex and Watco Flex 900 Innovator tub waste and overflow;
(61) J.R. Smith MFG. CO. THE BOSS TEE Series 4505 cleanout tee;
39
(62) Pipe Patch NO-Dig Repair System by Source One Environmental.
(a) The repair shall require a plumbing installation permit issued by the department; and
(b) After the repair has been completed, the building sewer shall be inspected, tested with either a water or a
smoke test, and approved by the department;
(63) PHIX Cartridge Systems. The PHIX cartridge system shall be approved for use as a point-source or in-line
acid neutralization system;
(64) SharkBite Evopex polymer fittings meeting ASSE Standard 1061. The use of SharkBite Evopex polymer
fittings shall be approved for underground burial except the fitting shall not be buried:
(a) Under or encased in concrete, or
(b) Underground beneath a building; and
(65) SharkBite Universal DZR brass fittings or SharkBite EvoPEX DZR brass transition fittings meeting ASSE
Standard 1061. The use of these fittings shall be approved for underground burial if the fitting is:
(a) Wrapped with self-fusing, formaldehyde and chloride-free, fully cured silicone tape with a minimum thickness
of 0.020 inches;
(b) Not buried under or encased in concrete; and
(c) Not buried underground beneath a building. (Recodified from 401 KAR 1:011, 7-5-1978; Am. 14 Ky.R. 1123;
eff. 1-4-1988; 15 Ky.R. 1580; 1799; eff. 2-3-1989; 2446; eff. 7-26-1989; 16 Ky.R. 901; eff. 1-12-1990; 2274; eff.
6-7-1990; 17 Ky.R. 472; eff. 10-14-1990; 2266; eff. 3-13-1991; 3278; eff. 7-519-91; 18 Ky.R. 1228; 1884; eff. 12-
8-1991; 2717; eff. 4-3-1992; 19 Ky.R. 295; 730; eff. 9-10-1992; 997; 1383; eff. 12-8-1992; 2503; eff. 7-12-1993;
20 Ky.R. 650; eff. 11-8-1993; 2159; eff. 3-14-1994; 21 Ky.R. 575; eff. 10-10-1994; 22 Ky.R. 796; eff. 12-7-1995;
1383; eff. 3-7-1996; 2119; eff. 7-5-1996; 23 Ky.R. 1754; 2501; eff. 12-11-1996; 3972; eff. 6-25-1997; 24 Ky.R.
957; eff. 12-15-1997; 2460; eff. 12-15-1997; 25 Ky.R. 2959; 26 Ky.R. 386; eff. 8-16-1999; 1046; eff. 1-11-2000;
27 Ky.R. 228; eff. 9-11-2000; 1348; eff. 1-15-2001; 3163; 28 Ky.R. 87; eff. 7-16-2001; 937; eff. 12-19-2001; 2271;
eff. 7-15-2002; 29 Ky.R. 2988; eff. 8-13-2003; 30 Ky.R. 1601; eff. 2-16-2004; 2390; 31 Ky.R. 85; eff. 8-6-2004; 32
Ky.R. 365; 657. eff. 11-4-2005; 32 Ky.R. 2357; 33 Ky.R. 400; eff. 9-1-2006; 400; 3258; eff. 7-6-2007; 34 Ky.R.
1232; 1744; eff. 2-1-2008; 35 Ky.R. 2582; 36 Ky.R. 80; 7-29-2009; 37 Ky.R. 186; 732; eff. 10-1-2010; 39 Ky.R.
151; 485; eff. 10-5-2012; 39 Ky.R. 2203; eff. 8-2-2013; 43 Ky.R. 455, 685; eff. 11-16-2016.)
40
815 KAR 20:030. License application; qualifications for examination, examination requirements,
expiration, renewal, revival, or reinstatement of licenses.
RELATES TO: KRS 318.010, 318.020, 318.040, 318.050, 318.054
STATUTORY AUTHORITY: KRS 318.040(1)(d), (2), (3), 318.050, 318.054(3)
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.040(1)(d) authorizes the commissioner of the
Kentucky Department of Housing, Buildings and Construction to promulgate administrative regulations
establishing qualifications for a master or journeyman plumber’s license. KRS 318.040(2) and (3) require the
department to promulgate administrative regulations establishing examination requirements. KRS 318.050
requires the department to establish reasonable application fees for licensure as a master or journeyman plumber.
KRS 318.054(3) requires the department to establish reasonable renewal fees for master or journeyman
plumbers. This administrative regulation establishes the application and examination requirements and the
application and renewal fees.
Section 1. Applications for Examination for Master or Journeyman Plumber's Licenses. (1) An application
for examination for a master or journeyman plumber's license shall be submitted to the department of Housing,
Buildings and Construction on:
(a) Form PLB-1, Application for License as a Master Plumber; or
(b) Form PLB-2, Application for License as a Journeyman Plumber.
(2) The application shall:
(a) Be properly signed and notarized;
(b) Be accompanied by an examination fee of:
1. $150 to take the master plumber's examination; or
2. Fifty (50) dollars to take the journeyman plumber's examination; and
(c) Include a passport-sized, color photograph of the applicant taken within the past six (6) months.
(3) The application fee shall be submitted with the application.
(4) The application fee shall be paid by United States coin and currency, post office or express money order, bank
draft, or certified check payable to the Kentucky State Treasurer.
(5) After passing the examination, an applicant for a master plumber's license shall remit a license fee of $250.
(6) After passing the examination, an applicant for a journeyman's license shall remit a license fee of sixty (60)
dollars.
Section 2. Examinations for Master or Journeyman Plumber's Licenses. (1) Examination of applicants.
(1) Regular examination of applicants for a master or journeyman plumber's license shall be conducted during the
months of February, May, August, and November of each year.
(b) A special examination may be conducted at other times as the Department of Housing, Buildings and
Construction directs.
(2) Time and place of examination. Notice of the time and place of examination shall be given by United States
mail at least one (1) week prior to the date of examination to each person who has an approved application on
file.
(3) An applicant who fails to attend or successfully complete an examination for which he or she has been
scheduled may request to reschedule or retake the examination within one (1) year from the date of the applicant’s
first notice of examination as established in subsection (2) of this section. The requirements established in
paragraphs (a) through (d) of this subsection shall apply to a rescheduled examination.
(a) The applicant shall complete and submit a new application form and examination fee as required by Section
1 of this administrative regulation. An applicant proceeding pursuant to this section shall not be required to
resubmit:
1. The photograph required by Section 1(2)(c) of this administrative regulation; or
2. Proof of compliance with Sections 4 or 5 of this administrative regulation. An applicant for a journeyman
plumber’s license who has achieved a passing score on only the written or practical portion of the examination,
but not both portions, may apply to retake the portion that he or she failed during the initial examination if the
reexamination is completed within one (1) year from the date of the applicant’s first notice of examination as
established in subsection (2) of this section.
(c) An applicant for a journeyman plumber’s license who has failed to achieve a passing score on the retaken
portion of the examination may apply to retake the entire examination if the reexamination is completed within one
(1) year from the date of the applicant’s first notice of examination as established in subsection (2) of this section.
(d) The application of an applicant for a master or journeyman plumber’s license who fails to successfully complete
his or her examination within one (1) year from the date of the applicant’s first notice of examination as established
in subsection (2) of this section shall be void.
1. An applicant whose application has become void pursuant to this subsection may reapply.
41
2. Reapplication shall be accomplished by complying with this administrative regulation as if the applicant were a
first-time applicant.
(4) Materials required for journeyman plumbers' examinations. An applicant for a journeyman plumber's license
shall furnish the materials required for the practical examination, which are established in the List of Required
Examination Materials that is included as part of the application.
(5) The testing requirements shall be designed by the State Plumbing Examining Committee and shall be more
complex for the master's examination than the journeyman's examination.
Section 3. Renewals of Master and Journeyman Plumber's Licenses. (1) Renewal fees. The annual license
renewal fee shall be:
(a) $250 for a master plumber; and
(b) Sixty (60) dollars for a journeyman plumber.
(2) Continuing education. The continuing education requirements established in 815 KAR 20:032 shall be met.
(3) Inactive master renewal.
(a) To place or keep a master plumber's license in inactive status, the master plumber shall pay annually an
inactive fee of $125.
(b) An inactive master plumber shall not secure a plumbing permit, advertise, represent himself or herself as a
qualified master plumber, or otherwise engage in the work of a master plumber.
(c) To reactivate a master plumber’s license, the inactive master plumber shall first pay an additional $125 and
comply with the continuing education requirements established in 815 KAR 20:032.
(4) Inactive journeyman renewal.
(a) To place or keep a journeyman plumber's license in inactive status, the journeyman plumber shall pay annually
an inactive fee of thirty (30) dollars.
(b) An inactive journeyman plumber shall not represent himself or herself as a qualified journeyman plumber or
otherwise engage in the work of a journeyman plumber.
(c) To reactivate a journeyman plumber’s license, the inactive journeyman plumber shall first pay an additional
thirty (30) dollars and comply with the continuing education requirements established in 815 KAR 20:032.
(5) Remittance of renewal fees. The renewal fee shall be paid by United States coin and currency, post office or
express money order, bank draft, or certified check payable to the Kentucky State Treasurer.
Section 4. Requirements for Master Plumber Applicants. Pursuant to KRS 318.040(1)(d), each person shall
meet the requirements established in subsections (1) through (4) of this section to become licensed as a master
plumber.
(1)(a) An applicant shall have:
1. A valid journeyman plumber's license for a minimum of two (2) years within the past five (5) years immediately
preceding application; and
2. Been actively employed in plumbing under the supervision of a licensed master plumber for a minimum of two
(2) years; or
(b) The applicant shall be a Kentucky licensed engineer sufficiently experienced in mechanical engineering. The
sufficiency of experience shall be determined based upon the number and complexity of the applicant's past
mechanical engineering projects.
(2) An applicant shall successfully complete the examination developed and administered by the State Plumbing
Examining Committee. The examination shall be designed to demonstrate that the applicant:
(a) Understands KRS Chapter 318 and 815 KAR Chapter 20;
(b) Is capable of the design of a plumbing system; and
(c) Understands the technical and practical installation techniques and principles for a safe and sanitary plumbing
system.
(3) The examination shall include:
(a) Answering written questions pertaining to basic principles of plumbing and KRS Chapter 318 and 815 KAR
Chapter 20; and
(b) Inserting the proper pipe size on a prepared drawing that indicates all stacks, wastes, and vents and the
plumbing fixtures connected thereto.
1. The proper sizing of main stacks shall be given more importance than other piping.
2. Deductions shall be required for oversized piping and for undersized piping.
(4) The passing grade for the total examination for a master plumber shall be eighty (80) percent, with a minimum
of seventy-five (75) percent obtained for each portion of the examination established in subsection (3)(a) and (b)
of this section.
42
Section 5. Requirements for Journeyman Plumber Applicants. Pursuant to KRS 318.040(1)(d), an applicant
shall meet the requirements established in subsections (1) through (3) of this section to become licensed as a
journeyman plumber. (1) An applicant shall have completed two (2) consecutive years’ experience as an
apprentice plumber.
(a) Proof of this requirement shall be satisfied by submission of:
1. A W-2 form;
2. An affidavit of a Kentucky licensed master plumber; or
3. A plumbing license issued by another state.
(b) Completion of a committee approved course shall be the equivalent of one (1) year of experience. An applicant
may only substitute one (1) year of experience if the applicant completes a committee approved course.
(2) An applicant shall successfully complete the practical and written examination developed and administered by
the State Plumbing Examining Committee. The examination shall be designed to demonstrate the practical and
technical understanding of plumbing principles and the ability to apply those principles for a safe and sanitary
plumbing system. The examination shall include:
(a) Answering written questions pertaining to basic principles of plumbing and KRS Chapter 318 and 815 KAR
Chapter 20;
(b) Inserting the proper pipe size on a prepared drawing that indicates all stacks, wastes, and vents and the
plumbing fixtures connected thereto.
1. The proper sizing of main stacks shall be given more importance than other piping.
2. Deductions shall be required for oversized piping and for undersized piping; and
(a) Completing a practical section in which the applicant shall demonstrate the ability to properly install plumbing
by engaging in certain activities such as properly installing a no hub cast-iron project and soldering copper solder
connections.
(3) The passing grade for the total examination for a journeyman plumber shall be seventy-five (75) percent, with
a minimum of seventy (70) percent obtained for each portion of the examination established in subsection (2)(a),
(b), and (c) of this section.
Section 6. A master plumber or journeyman plumber shall notify the department of the name of the
plumber's business and its address, employer, and the employer’s address each time a change of
employment is made.
Section 7. Incorporation by Reference. (1) The following material is incorporated by reference:
(a) Form PLB-1, "Application for License as a Master Plumber", August 2014; and
(b) Form PLB-2, "Application for License as a Journeyman Plumber", August 2014.
(2) This material may be inspected, copied, or obtained, subject to applicable copyright law, at the Department of
Housing, Buildings and Construction, 101 Sea Hero Road, Suite 100, Frankfort, Kentucky 40601-5412, Monday
through Friday, 8 a.m. to 4:30 p.m. (Recodified from 803 KAR 4:010, 4-1-1982; Am. 8 Ky.R. 1174; eff. 6-2-1982;
11 Ky.R. 1917; eff. 7-9-1985; 13 Ky.R. 1651; eff. 4-14-1987; 15 Ky.R. 2286; 16 Ky.R. 17; eff. 7-7-1989; 18 Ky.R.
2432; eff. 3-7-1992; 19 Ky.R. 1893; eff. 5-10-1993; 21 Ky.R. 1384; eff. 1-9-1995; 25 Ky.R. 2467; 2902; eff. 5-26-
1999; 27 Ky.R. 3374; eff. 8-15-2001; 32 Ky.R. 2361; 33 Ky.R. 403; eff. 8-10-1906; 34 Ky.R.1237; 1747; eff. 2-1-
2008; 37 Ky.R. 2757; 38 Ky.R. 20; eff. 8-5-2011; 41 Ky.R. 1199; 1795; eff. 3-6-2015.)
43
815 KAR 20:032. Continuing education requirements for plumbers.
RELATES TO: KRS 318.054, 318.130
STATUTORY AUTHORITY: KRS 318.054, 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 authorizes the department to adopt and
put into effect a State Plumbing Code. KRS 318.054 authorizes the department, after review by the Kentucky
Housing, Buildings and Construction Advisory Committee, to adopt continuing education requirements for
plumbers. This administrative regulation establishes those requirements.
Section 1. Master Plumbers. (1) Each master plumber shall provide proof of completion of eight (8) hours of
continuing education prior to license renewal. The required continuing education shall be received within twelve
(12) months prior to renewal except as provided in subsection (3) of this section.
(2) Continuing education courses shall relate to one (1) or more of the following:
(a) Business;
(b) Job safety;
(c) The Kentucky state plumbing code; or
(d) Items directly related to the plumbing trade.
(3) A licensed master plumber who accumulates more than the eight (8) hours of continuing education required
annually, may carry forward the excess credit hours into the two (2) successive educational years for the purpose
of satisfying the minimum requirement for those two (2) years.
(a) Carry forward credits shall be limited to a total of twelve (12) hours.
(b) All excess credits above the total of twelve (12) hours shall remain on the licensed master plumber's records
but shall not be carried forward.
(4) A licensed master plumber teaching or participating as a panel member in an approved continuing education
course for plumbing shall be granted one (1) credit hour for each fifty (50) minutes of actual instruction time.
Section 2. Journeyman Plumbers. (1) Each journeyman plumber shall provide proof of completion of eight (8)
hours of continuing education prior to license renewal. The required continuing education shall be received within
twelve (12) months prior to renewal except as provided in subsection (3) of this section.
(2) Continuing education courses shall consist of a minimum of two (2) hours on job safety. The other six (6) hours
shall consist of:
(a) The Kentucky state plumbing code;
(b) Job safety; or
(c) Items directly related to the plumbing trade.
(3) A licensed journeyman plumber who accumulates more than the eight (8) hours of continuing education
required annually, may carry forward the excess credit hours into the two (2) successive educational years for the
purpose of satisfying the minimum requirement for those two (2) years.
(a) Carry forward credits shall be limited to a total of twelve (12) hours.
(b) All excess credits above the total of twelve (12) hours shall remain on the licensed journeyman plumber's
records but shall not be carried forward.
(4) A licensed journeyman plumber teaching or participating as a panel member in an approved continuing
education course for plumbing shall be granted one credit hour for each fifty (50) minutes of actual instruction
time.
Section 3. Combined Master and Journeyman Licenses. An individual who is a holder of both a master and a
journeyman license shall meet the continuing education requirements of Section 1 of this administrative regulation.
Section 4. Inactive Master Licenses. (1) An inactive master plumber shall not required to complete continuing
education to maintain inactive status.
(2) If the inactive licensed plumber wishes to activate his or her license to the status of an active master plumber,
he or she shall meet the requirements of Section 1 of this administrative regulation.
(3) Any excess continuing education credit hours that a master plumber may be carrying forward shall not count
towards continuing education requirements for re-activation of an inactive license.
44
Section 5. Delinquent Licenses. (1) Except as provided in subsection (2) of this section prior to reinstatement,
an individual whose master or journeyman license is delinquent shall complete the total number of continuing
education hours per year that the license has been delinquent.
(2)The number of hours necessary for reinstatement shall not exceed forty (40) hours.
Section 6. Continuing Education Courses. (1) All continuing education shall be completed in one (1) or more
courses approved by the department and the Kentucky Housing, Buildings and Construction Advisory Committee,
for master and journeyman plumbers pursuant to 815 KAR 20:034.
(2) Continuing education courses shall be offered only by providers approved by the department and the Kentucky
Housing, Buildings and Construction Advisory Committee, pursuant to 815 KAR 20:034. (34 Ky.R. 1330; Am.
1749; eff. 2-1-2008; 37 Ky.R. 864; Am. 1212; eff. 12-3-2010.)
45
815 KAR 20:034. Requirements for approval of continuing education courses and providers.
RELATES TO: KRS 318.054, 318.130
STATUTORY AUTHORITY: KRS 318.130, 318.054
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.054 authorizes the department, after review by
the State Plumbing Code Committee, to adopt continuing education requirements for plumbers. This
administrative regulation establishes the process by which providers of continuing education courses are
approved and registered with the department and continuing education courses approved.
Section 1. Requirements for Continuing Education Providers. (1) Continuing education providers shall either
be a:
(a) Trade association with affiliation to the plumbing trade;
(b) Trade school;
(c) College;
(d) Technical school;
(e) Business dedicated solely to providing continuing education and that provides at least one (1) course quarterly
within each congressional district;
(f) Plumbing contracting company that employs full-time training personnel to conduct continuing education
programs providing continuing education for journeymen only; or
(g) Plumbing manufacturer or distributor that employs full-time training personnel to conduct continuing education
programs providing continuing education for journeymen only.
(2) Provider Registration. The department shall maintain a list of approved continuing education course providers.
An approved provider shall meet the criteria established in Section 2 of this administrative regulation.
(3)(a) Each continuing education course provider shall register with the department as required by subsection (3)
of this section before submitting course materials for department approval.
(b) Registration shall be valid for two (2) years from the date of issuance.
(4) Course providers shall register on Form PLB-3 provided by the department and shall include the following:
(a) The company name, mailing address, email address, telephone, and fax numbers of the provider;
(b) Contact person; and
(c) The fee, if any, to be charged to participants.
(5) Each course provider shall report to the department any change to the information submitted in the initial
application within thirty (30) days after the change takes effect.
(6) For each course approved the provider shall distribute to each applicant in attendance a questionnaire for the
purpose of rating the course.
(a) Questionnaires shall include:
1. Name of the course;
2. Date the course was taken;
3. Questions ranking the quality of the course;
4. Questions ranking the quality of the course materials provided; and
5. Questions ranking the quality of the instructor.
(b) Completed questionnaires shall be submitted with license renewal applications.
Section 2. Continuing Education Course Approval. (1) A separate application for approval shall be submitted
to the department on Form PLB-4 provided by the department for each course offered by a course provider.
(2) An application for approval of a continuing education course shall be submitted only by approved providers
registered with the department. Applications shall be submitted at least thirty (30) days prior to the course offering.
(3) A continuing education course shall provide instruction in at least one (1) of the subject areas specified in
Section 3 of this administrative regulation.
(4) The course application shall include the following:
(a) A course syllabus;
(b) Name of the course;
(c) Name and registration number of the provider;
(d) Name of the instructor or presenter along with his or her qualifications;
(e) The amount of actual time needed to present the course;
(f) The objectives of the course; and
(g) A statement of the practicality of the course to the plumbing trade.
(5) Content changes made to the course shall require subsequent submission to the department for review and
approval.
(6) Course approval shall be valid for two (2) years from the date approved by the department.
(7) The office shall issue a course number for each approved course. The course number and the provider’s
number shall appear on all advertisements and certificates for the course.
46
(8) Providers shall submit to the department a quarterly schedule including date and locations of courses by
January 1, April 1, July 1, and October 1 annually and the department shall be notified at least thirty (30) days
prior to a course's offering of changes made to scheduled courses.
(9) Providers may submit additional courses to their quarterly schedule if done at least thirty (30) days prior to the
course offerings.
(10) The department shall receive written notification of scheduling changes at least ten (10) working days prior
to the originally scheduled course date by fax or e-mail to the Director of Plumbing.
(11) Cancellations.
(a) The provider shall give notice of cancellation no less than five (5) working days prior to a scheduled class
unless the Governor declares a state of emergency or other conditions exist that would preclude a five (5) day
notification of cancellation;
(b) If the scheduled class is canceled, providers shall, at the option of the registrant, issue a full refund or allow
the registrant to attend a rescheduled course;
(c) A registrant who notifies a provider of cancellation prior to five (5) working days of a scheduled course may
choose either a full refund or to attend a subsequent course; and
(d) Providers shall not cancel a course with ten (10) or more registrants, unless cancellation is the result of an
emergency.
Section 3. Continuing Education Course Content. (1) All courses shall contain information beneficial in the
day-to-day operation of a plumbing business.
(2) Courses relating to business shall include one (1) or more of the following:
(a) Business law;
(b) Accounting practices; or
(c) Insurance.
(3) Courses relating to job safety shall directly relate to the construction trade.
(4) Courses related to the Kentucky state plumbing code shall include one (1) or more of the following:
(a) KRS Chapter 318;
(b) Basic plumbing principles;
(c) 815 KAR 20:001 through 815 KAR 20:195;
(d) Kentucky Building Code; or
(e) Kentucky Residential Code.
(5) Providers requesting approval of courses for topics not listed in this section shall demonstrate the relevancy
of the topic to the plumbing trade.
Section 4. Continuing Education Course Records. (1) Each registered course provider shall establish and
maintain for three (3) years the following records for each approved course:
(a) Certificates of completion as provided in subsection (2) of this section;
(b) An attendance sign-in and sign-out sheet; and
(c) A course syllabus.
(2) Certificates of completion.
(a) Each registered course provider shall issue a certificate of completion for each participant who enrolled and
completed an approved continuing education course.
(b) Certificates of completion shall contain the following information about the individual participant:
1. Name;
2. Address;
3. License number or numbers;
4. Date of attendance; and
5. Course or courses completed.
(c) One (1) copy of each certificate of completion shall be:
1. Sent to the department electronically;
2. Retained on file by the provider in compliance with subsection (1) of this section; and
3. Given to the participant upon completion of the course.
Section 5. Online continuing education shall:
(1) Be provided by a continuing education provider approved in accordance with Section 1 of this administrative
regulation;
(2) Include a minimum of six (6) personal security questions, per course, consisting of:
(a) One (1) random security question at each log-in; and
(b) Remaining security questions at intervals not to exceed twenty (20) minutes;
47
(3) Allow course participants access to the course for a minimum of thirty (30) days following receipt of payment
for the course;
(4) Make available online the course certificate of completion for twelve (12) months to any licensee who
completes an online course;
(5) Retain a record of all course applications and completions for a minimum of three (3) years; and
(6) Be capable of storing course content questions as follows:
(a) Stored content questions shall equal 150 percent of the content questions required; and
(b) Duplicate questions shall not be permitted.
(7) A minimum of four (4) content questions, chosen randomly from stored content questions, shall be answered
during each twenty (20) minutes of continuing education programming.
(8) Notification of correct and incorrect answers, prior to completion of the online course and issuance of a
certificate of completion, shall not be permitted.
Section 6. Online Courses. Online courses shall meet all requirements of this administrative regulation and 815
KAR 20:032.
Section 7. Course Audits. (1) Records requested in writing by the department shall be delivered to the
department within ten (10) days of the requesting date.
(2) Representatives of the department may, at any time, attend an approved continuing education course to
ensure that the course meets the stated objectives and that applicable requirements are being met.
Section 8. Disciplinary Action. The department may deny, suspend, or revoke approval of any course provider
or may issue a fine to any course provider who:
(1) Obtains or attempts to obtain registration or course approval through fraud, false statements, or
misrepresentation;
(2) Does not provide complete and accurate information in either the initial registration or in any notification of
changes to the information;
(3) Advertises a course as being approved by the department before the approval is received; or
(4) Fails to comply with the requirements of this administrative regulation.
Section 9. Incorporation by Reference. (1) The following material is incorporated by reference:
(a) Form PLB-3, "Application for Approval as a Plumbing Continuing Education Course Provider", November 2010;
and
(b) Form PLB-4, "Application for a Plumbing Continuing Education Course Approval", November 2010.
(2) This material may be inspected, copied, or obtained, subject to applicable copyright law, at the Department of
Housing, Buildings and Construction, Division of Plumbing, 101 Sea Hero Road, Suite 100, Frankfort, Kentucky
40601-5405, Monday through Friday, 8 a.m. to 4:30 p.m. (34 Ky.R. 1331; 1749; eff. 2-1-2008; 37 Ky.R. 1568;
2017; eff. 3-4-2011; 39 Ky.R. 325; eff. 11-2-12; 39 Ky.R. 2208; 40 Ky.R. 297; eff. 9-6-2013.)
48
815 KAR 20:040. Vehicle identification.
RELATES TO: KRS 318.170
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.170 authorizes agents of the department to
enforce the provisions of the state plumbing laws and code. This administrative regulation establishes the
identification requirements for all vehicles used in the operation of a plumbing business.
Section 1. Vehicle Identification. (1) All vehicles used in the operation of a plumbing business shall be properly
identified as established in this administrative regulation.
(2) Each vehicle shall bear the name of the company and the master plumber's Kentucky license number.
(3) All identification required by this administrative regulation shall be in letters not smaller than three (3) inches
high and shall be kept legible at all times. (Recodified from 401 KAR 1:017, 7-5-78; Am. 5 Ky.R. 253; eff. 11-1-
1978; 17 Ky.R. 2879; eff. 5-3-1991; TAm eff. 8-9-2007; 41 Ky.R. 166; 463; eff. 9-24-2014.)
49
815 KAR 20:050. Installation permits.
RELATES TO: KRS 318.030, 318.134, 318.160
STATUTORY AUTHORITY: KRS 318.130, 318.134(3)
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.134(3) requires the department to establish a
reasonable schedule of fees and charges to be paid for plumbing installation permits and the necessary
inspections incident thereto. KRS 318.130 authorizes the department to promulgate a reasonable rule or
administrative regulation to administer the provisions of KRS Chapter 318. This administrative regulation
establishes the requirements, fees, and charges for plumbing installation permits and inspections in Kentucky.
Section 1. Issuance of Permits. (1) A permit to construct, install, or alter plumbing, sewerage, or drainage shall
be issued only to a licensed master plumber except as established in subsection (3) of this section.
(2) A journeyman plumber shall not construct, install, or alter plumbing, sewerage, or drainage unless the work is
performed under the supervision of a licensed master plumber.
(3) A permit to construct, install, or alter plumbing, sewerage, or drainage shall be issued to a homeowner desiring
to install plumbing in a home occupied by the homeowner or constructed by the homeowner for the homeowner’s
own personal residential use, if:
(a) Application is made for the permit prior to the beginning of the work;
(b) The homeowner files with the application an affidavit stating that the homeowner shall abide by the terms of
this section;
(c) All work shall be performed in compliance with the state plumbing code, 815 KAR Chapter 20;
(d) All the work shall be personally performed by the homeowner; and
(e) The homeowner shall not have obtained another homeowner permit for construction of a new home issued
within the last five (5) years.
(4) A permit shall not be required for:
(a) The repairing of:
1. Leaks;
2. Cocks; or
3. Valves; or
(b) Cleaning out waste or sewer pipes.
Section 2. Conditions Under which a Permit Shall be Required. A plumbing installation permit shall be required
for:
(1) A new plumbing installation;
(2) An existing plumbing installation if a fixture, soil, or waste opening or conductor is to be moved or relocated;
(3) Each individual unit of a multistory building if there is more than one (1) unit;
(4) A building that is considered separate if:
(a) The connection between the building and another building is not a necessary part of the structure of either
building; or
(b) The building’s roof is not part of the roof of another building;
(5) A new house sewer or a house sewer that is to be replaced;
(6) A new water service or a water service that is to be replaced;
(7) The addition of a backflow prevention device to an existing water service;
(8) A new water heater installation or a water heater installation that is to be replaced; or
(9) Taking over a plumbing installation originally permitted to another master plumber or assuming responsibility
to correct and test an installation made by someone else.
Section 3. Plumbing Installation Permit Fees. (1) The base fee for each plumbing installation permit for
residential, one (1) and two (2) family units, shall be forty-five (45) dollars plus seven (7) dollars for each:
(a) Plumbing fixture or appliance or plumbing fixture opening or appliance opening left in the soil or waste pipe
system including openings left for future fixtures or appliances;
(b) Domestic water heater; and
(c) Separately metered water and sewer service if more than one (1) water or sewer service is to be installed.
(2) The base fee for each plumbing installation permit for other than residential, one (1) and two (2) family units,
shall be forty-five (45) dollars plus fifteen (15) dollars for each:
(a) Plumbing fixture or appliance or plumbing fixture opening or appliance opening left in the soil or waste pipe
system including openings left for future fixtures or appliances;
(b) Domestic water heater;
(c) Conductor opening; and
(d) Separately metered water and sewer service if more than one (1) water or sewer service is to be installed.
50
(3)(a) If only one (1) new domestic water heater is installed or replaced within a single building, the only fee for
the plumbing installation permit shall be forty-five (45) dollars.
(b) If more than one (1) water heater is replaced within a building, a permit shall be required pursuant to Sections
1 or 2 of this administrative regulation.
(4) If the application for permit does not include any new installation but is to make corrections to or to provide
testing for an installation made by someone else, the permit fee shall be limited to the base fee of forty-five (45)
dollars only.
Section 4. Inspection Fees. (1) A person with a plumbing permit shall be entitled to five (5) plumbing inspections
at no additional cost.
(2) Each plumbing inspection in excess of five (5) shall be charged at the rate of fifty (50) dollars per inspection
and shall be paid prior to the final inspection.
(3) Inspection fees shall not apply if the cost of the permit exceeds $200.
Section 5. Expiration of Permits. (1) Except as established in subsection (2) of this section, all plumbing
installations permits issued pursuant to this administrative regulation shall expire one (1) year after the date of
issuance.
(2)(a) Except as established in paragraph (b) of this subsection, if construction is begun within one (1) year after
the date the permit is issued, the permit shall remain effective until completion of the planned plumbing inspection.
(b) The permit shall expire and become void if the plumbing work ceases on the project for a period exceeding
twelve (12) months.
Section 6. Plumbing Inspection Fees for Public Buildings. The schedule of fees for inspection of the
construction, installation, or alteration of plumbing in public buildings shall be the same as established in Section
4 of this administrative regulation. (Recodified from 401 KAR 1:030, 7-5-1978; Am. 5 Ky.R. 160; eff. 10-4-78; 6
Ky.R. 696; 7 Ky.R. 220; eff. 10-1-80; 845; eff. 10-7-81; 9 Ky.R. 832; 1200; eff. 4-6-83; 13 Ky.R. 958; eff. 12-2-86;
17 Ky.R. 2880; eff. 5-3-91; 18 Ky.R. 1231; 1887; eff. 12-8-91; 19 Ky.R. 2335; eff. 6-7-93; 21 Ky.R. 1389; eff. 1-9-
95; 27 Ky.R. 3376; eff. 8-15-2001; 32 Ky.R. 2362; 33 Ky.R. 404; eff. 9-1-2006; 36 Ky.R. 1134; 2067-M; eff. 6-4-
2010; 41 Ky.R. 167; eff. 9-24-2014; 1202; eff. 3-6-2015.)
815 KAR 20:055. Water heater devices.
RELATES TO: KRS 318.200, EO 2009-535
STATUTORY AUTHORITY: KRS 318.200
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.200 requires that all retailers, wholesalers, and
installers of water heating devices forward the name and address of each purchaser along with the serial number
of the device purchased to the office or to the appropriate agency of county or city government having jurisdiction
within thirty (30) days of the purchase. EO 2009-535, effective June 12, 2009, reorganized the Office of Housing,
Buildings and Construction as the Department of Housing, Buildings and Construction, and established the
commissioner, rather than executive director, as the head of the department. This administrative regulation
establishes the requirements for submitting the information to the department.
Section 1. Reporting Requirements. (1) If required by KRS 318.200 to submit information to the department,
rather than to a local jurisdiction, a wholesaler, retailer, or installing contra tractor selling a water heating device
shall submit to the Department of Housing, Buildings and Construction, Division of Plumbing, the name and
address of each purchaser, including the serial number of the water heater, on Form PLB-94, Water Heater Report
Form.
(2) An installing contractor shall be exempt from the reporting requirements of subsection (1) of this section the
contractor has if purchased an installation permit for the water heater. The permit shall serve as the reporting
requirement for the Division of Plumbing as required by KRS 318.200.
Section 2. Incorporation by Reference. (1) Form PLB-94, "Water Heater Report Form", December 2009, is
incorporated by reference.
(2) This material may be inspected, copied, or obtained, subject to applicable copyright law, at the Department of
Housing, Buildings and Construction, Division of Plumbing, 101 Sea Hero Road, Suite 100, Frankfort, Kentucky
40601-5405, Monday through Friday, 8 a.m. to 430 p.m. (11 Ky.R. 911; Am. 1258; eff. 2-12-1985; 17 Ky.R. 2881;
eff. 5-3-1991; 24 Ky.R. 2463; eff. 7-13-1998; 32 Ky.R. 2364; 33 Ky.R. 406; eff. 9-1-2006; 36 Ky.R. 1533; 2068-M;
eff. 4-2-2010.)
51
815 KAR 20:060. Quality and weight of materials.
RELATES TO: KRS 318.130, 318.150, 42 U.S.C. 300g-6(d)(2)
STATUTORY AUTHORITY: KRS 198B.040(10), 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department to promulgate an
administrative regulation establishing the Kentucky State Plumbing Code to regulate plumbing, including the
quality and weight of material. This administrative regulation establishes the manufacturer's specification number
for the quality and weight of material that shall be used in the installation of plumbing systems and establishes
minimum specifications for the intended use.
Section 1. Definitions.
(1) "ASME" means the American Society of Mechanical Engineers.
(2) "CISPI" means the Cast Iron Soil Pipe Institute.
(3) "Lead" means solders and flux containing more than two-tenths (0.2) percent lead and the wetted surfaces of
pipes, pipe fittings, plumbing fittings, and fixtures containing more than a weighted average of 0.25 percent lead
as calculated according to the formula established in 42 U.S.C. 300g-6(d)(2).
Section 2. Quality of Materials. The material used in a drainage or plumbing system or part of a system shall be
free of defects.
Section 3. Label, Cast, or Stamped. Each length of pipe, fitting, trap, fixture, or device used in a plumbing or
drainage system shall be stamped or indelibly marked with the:
(1) Weight or quality; and
(2) Maker's mark or name (manufacturer's specification number).
Section 4. Vitrified clay pipe, concrete pipe, truss pipe, and extra heavy SDR 35 sewer piping shall be
produced, labeled, and used only as established in subsections (1) through (4) of this subsection. (1) Vitrified clay
pipe shall be as established in ASTM C-700.
(2) Concrete pipe shall be as established in ASTM C-14.
(3)(a) Except as established in paragraph (b) of this subsection, truss pipe shall be as established in ASTM D-
2680.
(b) Solid wall truss pipe shall be as established in ASTM D2751.
(4) Extra heavy SDR 35 sewer piping shall be as established in ASTM D-3033-74 and D-3034-74.
Section 5. Cast-iron Pipe. (Hub and Spigot and No-hub). (1) Extra heavy. Extra heavy cast-iron pipe and fittings
shall be produced and labeled as ASTM A74.
(2) Service-weight. Service-weight cast-iron pipe and fittings shall be produced and labeled as ASTM A74 and
C1563.
(3) No-hub cast-iron and fittings shall be produced and labeled ASTM 888 or CISPI 301.
(4) No-hub couplings shall be produced and labeled as ASTM C1277, C564, C1563, or CISPI 310.
(5) Coating. Cast-iron pipe and fittings for underground use shall be coated with:
(a) Asphaltum;
(b) Coal tar pitch; or
(c) A coating produced and labeled as ASTM A743.
Section 6. Wrought-iron Pipe. All wrought-iron pipe shall be produced and labeled with the latest ASTM
"specifications for welded wrought iron pipe".
Section 7. Mild-steel Pipe. Steel pipe shall be produced and labeled with the latest ASTM "specifications for
welded and seamless steel pipe".
Section 8. Brass Pipe; Copper Pipe; and Brass Tubing. Brass pipe, copper pipe, and brass tubing shall be
produced and labeled with the latest specifications of ASTM for "brass pipe, copper pipe, and brass tubing,
standard sizes".
52
Section 9. Borosilicate Pipe, Plastic Pipe, Stainless Steel Tubing, Polyethylene Pipe, and Polypropylene
Pipe. (1) Borosilicate pipe. Borosilicate pipe shall be produced and labeled with the latest ASTM specifications.
(2) Plastic pipe. All plastic piping used in a drainage, waste, and vent system shall be:
(a) Schedule 40 or 80, Type 1, Grade 1, polyvinyl chloride produced and labeled as ASTM D1784;
(b) Cellular core PVC produced and labeled ASTM F-891;
(c) Schedule 40 or 80 acrylonitrile-butadiene-styrene produced and labeled as ASTM D2661; or
(d) Cellular core ABS produced and labeled as ASTM F-628.
(3) Pipe and fittings shall be produced and labeled in accordance with the provisions of ASTM-D-2665, as
amended, for PVC and ASTM-D-2661 for ABS, and both shall bear the National Sanitation Foundation seal of
approval.
(4) Copies of National Sanitation Foundation specifications for the manufacture of products identified in this
administrative regulation may be obtained by writing the National Sanitation Foundation (NSF), 3475 Plymouth
Road, P.O. Box 1468, Ann Arbor, MI 48106.
(5) All pipe and fittings shall bear the ASTM designation together with the NSF seal, the manufacturer's
identification, and the size.
(6)(a) Except as established in paragraph (b) of this subsection, the use of plastic pipe and fittings (PVC or ABS)
shall be limited to buildings in which the plumbing system does not exceed forty-five (45) feet in height, measured
from the grade plane, and continuing through the vertical distance of the building to a maximum height of forty-
five (45) feet.
(b) Plastic pipe and fittings may be installed in a building in which the plumbing system exceeds forty-five (45) feet
in height if the installation complies with all of the requirements established in subparagraphs 1. through 3. of this
paragraph.
1. The use of PVC and ABS piping shall be limited to schedule 40 or 80 produced and labeled as ASTM D2665
and D1784 for PVC piping and ASTM D2661 for ABS piping.
2. The installation of the plastic pipe and fittings (PVC or ABS) shall be made in compliance with the manufacturer’s
recommendations, which shall be made available to the inspector.
3. Firestop systems shall be inspected in accordance with ASTM E2174 by an approved inspection agency.
(7) Stainless steel tubing.
(a) Stainless steel tubing for hot and cold water piping shall be produced and labeled either as ASTM A269 or
ASTM A312.
(b) Stainless steel tubing for the soil, waste, and vent system shall be 316L produced and labeled as ASME
A112.3.1.
(8) Polyethylene pipe used in acid waste systems shall be produced and labeled as ASTM D-1204.
(9) Polypropylene pipe used in acid waste systems shall be produced and labeled as ASTM D-4101 or ASTM F-
1412.
Section 10. Lead Pipe, Diameter, Weights. (1) Lead soil, waste, and vent pipe shall be produced and labeled
as Federal Specifications WW-P-325 and shall not be lighter than the weights established in the following table:
Size Inside
Diameter Inches
Commercial Designation
"D" or "XL"
Wall Thickness
Inches
Weight Pounds Per Foot
Ounces
1 ½ D XL 0.138 3 8
2 D XL 0.142 4 12
3 D XL 0.125 6 0
4 D XL 0.125 8 0
(2) Lead bends and lead traps. All lead bends and lead traps shall be of the weight known as extra heavy (XH)
and shall have at least one-eighth (1/8) inch wall thickness.
Section 11. Integral Flashing. If a roofing system requires integral flashing, a flashing material, which is part of
the manufactured roofing system and required by the roofing manufacturer to guarantee or warranty the roofing
system, shall be used.
Section 12. Sheet Lead. Sheet lead for a shower pan shall not weigh less than four (4) pounds per square foot
and shall not weigh less than two and one-half (2 1/2) pounds per square foot for vent pipe flashings.
53
Section 13. Sheet Copper or Brass. Sheet copper or brass shall not be lighter than No. 18 B. & S. gauge, except
local and interior ventilating pipe shall not be lighter than No. 26 B. & S. gauge.
Section 14. Threaded Fittings. (1) A plain screw fitting shall be either cast-iron, malleable iron, or brass of
standard weight and dimension.
(2) A drainage fitting shall be either cast-iron, malleable iron, or brass, with smooth interior waterway, with threads
tapped out of solid metal.
(3) A cast-iron fitting used in a water supply distribution shall be galvanized.
(4) A malleable iron fitting shall be galvanized.
Section 15. Caulking Ferrules. A caulking ferrule shall be of red brass and shall be in accordance with the
following table:
Pipe Sizes Inches Inside Diameter Inches Length Inches Minimum Weight Each
2 2 1/4 2 1/2 1 lb. 0 oz.
3 3 1/4 4 1/2 1 lb. 12 oz.
4 4 1/4 4 1/2 2 lb. 8 oz.
Section 16. Soldering Nipples. A soldering nipple shall be recessed red cast brass, iron pipe size. If cast, they
shall be full bore and of minimum weight.
Section 17. Floor Flanges for Water Closets and Service Sinks or Similar Fixtures. (1) A floor flange shall
either be:
(a) Hard lead;
(b) Brass;
(c) Cast iron;
(d) Galvanized malleable iron;
(e) ABS; or
(f) PVC.
(2) A hard lead or brass flange shall not be less than one-eighth (1/8) inch thick.
(3) Cast iron or galvanized malleable iron shall:
(a) Not be less than one-fourth (1/4) inch thick; and
(b) Have a two (2) inch caulking depth.
Section 18. Use of Lead. (1) Lead shall not be used in the installation or repair of a public or private water system
providing potable water for human consumption.
(2) This section shall not apply to:
(a) Pipes, pipe fittings, plumbing fittings, or fixtures, including backflow preventers, that are used exclusively for
non-potable services such as manufacturing, industrial processing, irrigation, outdoor watering, or any other uses
in which the water is not anticipated to be used for human consumption; or
(b) Toilets, bidets, urinals, fill valves, flushometer valves, tub fillers, shower valves, service saddles, or water
distribution main gate valves that are two (2) inches in diameter or larger.
Section 19. New Materials. (1) Materials other than those established in this administrative regulation shall be
prohibited unless the material is specifically approved by the State Plumbing Code Committee and the department
as being equal to or better than the material specified in the State Plumbing Code.
(2) It shall be the responsibility of any person or company seeking the approval of a material not included in this
code to prove that the material is equal to or better than the material that it is intended to replace.
(3) Procedural requirements for approval of new parts and materials are established in 815 KAR 20:020.
(Recodified from 401 KAR 1:030, 7-5-1978; Am. 5 Ky.R. 160; eff. 10-4-1978; 6 Ky.R. 133; 384; eff. 1-2-1980; 8
Ky.R. 359; eff. 1-6-1982; 14 Ky.R. 1123; eff. 1-4-1988; 15 Ky.R. 601; 970; eff. 9-28-1988; 17 Ky.R. 2882; eff. 5-3-
1991; 18 Ky.R. 2720; eff. 4-3-1992; 19 Ky.R. 999; 1385; eff. 12-8-1992; 27 Ky.R. 1902; 2794; eff. 3-22-2001; TAm
eff. 8-9-2007; 35 Ky.R. 2586; 36 Ky.R. 83; eff. 7-29-2009; 41 Ky.R. 169; eff. 9-24-2014; 42 Ky.R. 127; 1193; eff.
11-6-2015; 43 Ky.R. 621; eff. 1-6-2017.
54
815 KAR 20:070. Plumbing fixtures.
RELATES TO: KRS 318.010, 318.015, 318.150, 318.200
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department, after review by
the State Plumbing Code Committee, to promulgate an administrative regulation establishing the Kentucky State
Plumbing Code regulating plumbing, including the kind, type, and quality of plumbing fixtures to be used in the
construction of plumbing systems. This administrative regulation establishes the requirements for plumbing
fixtures allowed in Kentucky.
Section 1. Materials. Receptacles used as water closets, urinals, or for the disposal of human excreta, shall be
of vitrified earthenware, hard natural stone, or cast-iron with a light color porcelain enameled on the inside, except
as established in Section 4 of this administrative regulation.
Section 2. Installation. Plumbing fixtures shall be installed to allow access for cleaning.
(1) All pipes from fixtures shall be run to the wall.
(2) A trap or pipe shall not extend nearer to the floor than twelve (12) inches except laundry trays or similar fixtures.
Section 3. Water Closet Bowls. (1) A water closet bowl shall be of one (1) piece construction and hold a sufficient
quantity of water when filled to the trap overflow to prevent fouling of its interior surfaces.
(2) A water closet bowl shall be provided with an integral flushing rim to flush the entire interior of the bowl.
Section 4. Plastic Water Closet Bowl and Tank. (1) A plastic water closet bowl and tank shall be constructed
with a polypropylene lining inside the one (1) piece bowl and tank.
(2) The outer surface of the bowl shall be constructed of PVC material.
(3) The filler material between the lining and outer surface shall be made of polyurethane foam.
(4) The bowl shall have:
(a) A three (3) inch water seal; and
(b) A two and one-eighth (2 1/8) inch waste opening passage.
Section 5. Frost-proof Closet. (1) A frost-proof water closet may be installed only in a building that has at least
a twelve (12) inch air break between it and any building used for habitation or occupancy.
(2) The room shall be tightly enclosed and accessible from the outside only.
(3) The soil pipe between the trap and hopper shall be of extra heavy cast-iron, four (4) inches in diameter and
shall be light colored porcelain enamel on the inside.
(4) The building shall have a nonabsorbent floor.
(5) A frost-proof water closet shall have a four (4) inch vent.
Section 6. Floor and Shower Drains. (1) A floor drain or a shower drain shall be considered a plumbing fixture
and shall be provided with a strainer.
(2) Shower drain pan construction.
(a) A shower pan shall be constructed without a seam and shall extend to a minimum height of six (6) inches on
all vertical walls.
(b) A shower pan shall not be required on a concrete floor before the outside grade level.
(c) A shower drain pan shall be constructed of:
1. Sheet lead weighing not less than four (4) pounds per square foot;
2. Non-plasticized chlorinated polyethylene produced and labeled as ASTM D-412 and D-1204, which shall be
not less than 0.040 inches thick;
3. Non-plasticized polyvinyl chloride (PVC) sheet material produced and labeled as ASTM D-1004, D 412, 06A,
and D-1790, which shall be not less than 0.040 inches thick; or
1. Other approved material as established in 815 KAR 20:020, Section 5. Copies of ASTM specifications identified
in this administrative regulation may be obtained by writing the American Society for Testing Materials, 1916 Race
Street, Philadelphia, Pennsylvania 19103.
(3) Fiberglass bathtubs, showers, tub enclosures, and shower stalls.
(a) Fiberglass bathtubs and tub enclosures shall be produced and labeled as ANSI Z 124.1.
(b) Acrylic-faced bathtubs shall be produced and labeled as ASTM E8408A or E 162.
(c) Fiberglass shower stalls and shower receptors shall be produced and labeled as ANSI Z 124.2.
55
(4) Metamorphosed carbonate aggregate polyester resinous martrix-marbleoid bathtubs, lavatories, and shower
stalls.
(a)1. Metamorphosed carbonate aggregate polyester resinous martrix-marbleoid bathtubs shall be produced and
labeled as ANSI Z 124-1.
2. Lavatories shall be produced and labeled as ANSI Z 124-3.3. Shower stalls shall be produced and labeled as
ANSI Z 124-2.
(b) Copies of ANSI specifications identified in this administrative regulation may be obtained by writing the
American National Standards Institute, 1430 Broadway, New York, New York 10018.
Section 7. Fixture Strainers. (1) A fixture, other than a water closet or a pedestal urinal, shall be provided with
a strainer.
(2) The outlet area of the strainer shall not be less than the interior area of the trap.
Section 8. Fixture Overflow. The overflow from a fixture shall be optional, but if used, the overflow shall be
connected to the inlet side of a trap and accessible for cleaning.
Section 9. Fixture Additions. A fixture added to a plumbing system shall be installed to comply with all applicable
sections of the State Plumbing Code.
Section 10. Defective Fixtures. If a newly installed fixture is found to be defective or if an old fixture is found to
be in an unusable condition, it shall be repaired, replaced, or removed within thirty (30) days upon written notice
from the office.
Section 11. Water Heaters. (1) A water heater shall be properly connected to the hot and cold water supply.
(2) A water heater designed for use as an appliance for supplying potable hot water for domestic or commercial
purposes may be used for space heating if the water temperature does not exceed 140 degrees Fahrenheit.
(3) Every water heater shall be accessible for inspection, repair, and replacement.
(4)(a) If a water heater is installed in a crawl space after September 1, 2006, it shall have adequate access with
a travel path no less than five (5) feet of vertical distance and be installed on at least a two (2) inch thick
noncorrosive material adequate to support the heater.
(b) The replacement of a water heater that was originally installed in a crawl space prior to September 1, 2006
shall not require compliance with the vertical distance requirement of this subsection.
(5) If a water heater is located in an attic of a residence, a water tight pan of corrosion resistant material shall be
installed beneath the water heater and shall be equipped with at least a three-quarter (3/4) inch drain to be piped
similarly to a pressure and temperature relief valve discharge line.
(6) A fuel-fired water heater shall be connected to a flue or chimney of a size that shall be at least as large as the
size required by the water heater manufacturer's instructions.
(7) A fuel-fired water heater vent shall not be connected to a flue serving a coal-burning apparatus.
(8) The flue or chimney shall extend two (2) feet above the roof and shall be properly flashed and shall not
terminate within six (6) feet of a door or window.
(9) A fuel-fired water heater, with the exception of those having direct-vent or through the wall vent systems, shall
not be placed in any bathroom, toilet room, or a room used for sleeping.
(10) If a fuel-fired water heater is placed in a closed room or closet, the door shall be a louver door or shall be
properly ventilated to provide combustion air and circulation in accordance with the Fuel Gas Code incorporated
by reference in Chapter 35 of the Kentucky Building Code filed in 815 KAR 7:120.
(11) Direct venting system location.
(a) A residential gas-fired direct vent and through the wall type water heater shall be vented in accordance with
the manufacturer's recommendations and shall be installed in accordance with the Fuel Gas Code incorporated
by reference in the Kentucky Building Code filed in 815 KAR 7:120.
(b)1. The vent terminal of a direct vent appliance with an input of 50,000 BTU per hour or less shall be located at
least nine (9) inches from any opening through which flue gases could enter a building.
2. An appliance with an input over 50,000 BTU per hour shall require a twelve (12) inch vent termination clearance.
(c) The bottom of the vent terminal and the air intake shall be located at least twelve (12) inches above grade.
(12) An instantaneous water heater not listed in 815 KAR 20:020 shall:
(a) 1. Be certified to ANSI Z21.10.1 for units including but not exceeding 75,000 BTUs; or
2. Be certified to ANSI Z21.10.3 for units exceeding 75,000 BTUs;
(b) Have a minimum of 3/4 inch inlet and outlet;
(c) Be installed with a properly sized pressure relief valve not exceeding 150 pounds per square inch; and
(d) If required by the manufacturer to be periodically flushed, be installed to flush without altering the installation.
(13) Temperature and pressure relief valves shall be installed in accordance to manufacturer’s requirements.
56
Section 12. Conservation of Water. (1) Conservation of hot water.
(a) Showers. A shower used for other than safety reasons shall be equipped with an approved flow control device,
which shall limit the total flow to a maximum of two and one-half (2.5) gallons per minute per shower head.
(b) Lavatories.
1. Lavatories in restrooms of public facilities shall be equipped with an outlet device, which shall limit the flow of
domestic hot water to a maximum of 0.75 gallons per minute.
2. Lavatory faucets (other than those in restrooms of public facilities) shall be equipped with a flow control device,
which shall limit the flow of domestic hot water to a maximum of two (2.0) gallons per minute.
3. Sink faucets shall be equipped with a flow control device, which shall limit the flow of domestic hot water to a
maximum of two and one-half (2.5) gallons per minute.
(2) Conservation of cold water.
(a) Showers. A shower used for other than safety reasons shall be equipped with an approved control device to
limit the total flow to a maximum of two and one-half (2.5) gallons per minute per shower head.
(b) Lavatory and sink faucets.
1. Lavatory faucets. Lavatory faucets shall be equipped with a flow control device, which shall limit the flow of the
domestic cold water to a maximum of two (2.0) gallons per minute.
2. Sink faucets. Sink faucets shall be equipped with a flow control device, which shall limit the flow of domestic
cold water to a maximum of two and one-half (2.5) gallons per minute.
(c) Water closets. A water closet shall not be installed in a facility or building unless it is of a type designed and
manufactured to limit the gallons per flush as required by this subsection.
1. Residential (private use) installations. A water closet for private use in a single family dwelling, duplex, or
townhouse, condominium or apartment unit shall not exceed one and six-tenths (1.6) gallons per flush.
2. Commercial (public use) installations. A water closet for public use, including a commercial building, shall not
exceed three and one-half (3.5) gallons per flush.
(d) Urinals. A urinal shall not exceed one (1.0) gallon per flush.
(3)(a) The provisions of this section shall apply to new construction, renovation, or replacement in an existing
structure.
(b) Upon compliance with the requirements of this section, the Division of Plumbing shall permit the installation of
a tank type water closet equipped with devices found by the inspector to meet applicable specifications in water
closets having a tank capacity in excess of three and one-half (3 1/2) gallons (thirteen and three-tenths (13.3)
liters).
(c) The Division of Plumbing shall allow the use of a standard flush water closet and a urinal that does not meet
the specific specifications if the configuration of the building drainage system requires a greater quantity of water
to adequately flush the system, or if the owner requests the use of antique fixtures that would not be equipped for
reduced flow.
(Recodified from 401 KAR 1:040, 7-5-1978; Am. 8 Ky.R. 361; 769; eff. 1-6-1982; 9 Ky.R. 46; eff. 8-11-1982; 833;
eff. 2-2-1983; 1237; eff. 6-1-1983; 10 Ky.R. 453; eff. 11-2-83; 11 Ky.R. 73; eff. 8-7-1984; 13 Ky.R. 785; eff. 11-11-
1986; 1940; eff. 6-9-1987; 16 Ky.R. 1270; eff. 1-25-1990; 19 Ky.R. 1002; 1387; eff. 12-8-1992; 20 Ky.R. 3117; eff.
7-7-1994; 21 Ky.R. 1391; eff. 1-9-1995; 2533; eff. 6-1-1995; 23 Ky.R. 3975; eff. 6-25-1997; 32 Ky.R. 2365; 33
Ky.R. 406; eff. 9-1-2006; 35 Ky.R. 2588; 36 Ky.R. 85; eff. 7-29-2009; 37 Ky.R. 2759; eff. 8-5-2011; 41 Ky.R. 169;
eff. 9-24-2014.)
57
815 KAR 20:071. Storage and installation of Schedule 40, ABS and PVC plastic pipe and fittings.
RELATES TO: KRS Chapter 318
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: The office is directed by KRS 318.130 through the
Kentucky Housing, Buildings and Construction Advisory Committee, to adopt and put into effect a State Plumbing
Code. This administrative regulation relates to the method needed for storage, handling and installation of schedule
40, ABS and PVC plastic pipe and fittings. This administrative regulation is being amended because new fittings are
now available which allows for expansion when connecting plastic pipe to metal as well as a new means of
connecting different kinds of plastic pipe.
Section 1. Storage. (1) Pipe. Pipe shall remain in lifts until ready for use. Lifts shall not be stacked more than three
(3) high and shall always be stacked wood-on-wood. Loose pipe shall be stored in racks with a minimum support
space of three (3) feet. Pipe shall be shaded but not directly covered when stored outside in high ambient
temperatures to provide for free circulation of air and reduce the heat buildup due to direct sunlight exposure.
(2) Fittings. Fittings shall be stored in their original cartons to be kept free of dirt and to reduce the possibility of
damage. If possible, fittings shall be stored indoors.
(3) Solvent cement and primers. Solvent cement and primers shall not be exposed to ignition, sparks, open flames
or heat during storage and shall not be used beyond their marked shelf life.
Section 2. Handling. Care shall be exercised to avoid rough handling of pipe and fittings. They shall not be dragged
over sharp projections, dropped or have heavy objects dropped on them. Pipe ends shall be inspected for cracks in
the event of abuse prior to installation. (If transported by truck or trailer, piping shall be reasonably supported.)
Section 3. Installation. (1) Underneath concrete floors. Pipe and fittings shall be laid on stable earth conditions and
have four (4) inches of grillage on its bottom, top and sides. If ground is unstable, it shall be removed and the
excavation filled with grillage to the underneath side of the piping. Soil or waste pipe shall not be placed in a concrete
slab except those pipes that pass vertically through it.
(2) Above concrete floors. Horizontal piping shall be properly aligned and installed without strain. Piping shall not be
bent or pulled in position either before or after solvent welds have been made. It shall be supported at intervals not
to exceed four (4) feet and at the end of the branches and at the change of direction and shall be so installed as to
permit freedom of movement. Vertical piping shall be supported at their bases and all upward movement shall not
be restricted. Closet flanges shall be securely fastened to the floor through which it passes.
Section 4. Hangers. Hangers and straps shall be at least one (1) inch wide and shall not compress, distort, cut or
abrade the piping to allow free movement at all times.
Section 5. Making Solvent Cement Joints. (1)(a) Cement shall not be thinned. Cement that has thickened shall
be discarded. Cement shall not be used beyond its shelf life and shall not be subject to temperatures below thirty
(30) degrees Fahrenheit.
(b) Installers shall avoid prolonged breathing of vapors. Prolonged contact with skin is harmful. Install only with
adequate ventilation. Avoid contact with eyes and skin. Solvents are also flammable.
(2) Socket fit. ABS and PVC fittings are manufactured to a close tolerance. Joints shall be an interference fit between
pipe and fittings. Additional cement shall not be permitted for the correction of loosely fitted joints.
(3) Joining techniques. Piping shall be cut square with a saw or pipe cutter designed especially for plastic pipe. Pipe
and fittings shall be protected from serrated holding devices or abrasions.
(a) Burrs shall be removed from both inside and outside of the pipe. Dust, dirt and moisture shall be removed from
the surfaces that shall be cemented.
(b) Solvent chemical cleaner recommended by the company whose product is being installed shall be applied inside
the fitting and on the outside of the piping shall be joined.
(c) A paint brush shall be used to apply the solvent cement in a moderate, even coating in the fitting socket as well
as covering the pipe on the joining surfaces.
(d) Joints shall be assembled as quickly as possible before the cement dries. Insert the piping into the fitting socket
turning the pipe slightly to ensure even distribution to the cement. Hold the piping in a firm position so it does not
"back out" of the joint.
(e) Remove excess solvent cement from the exterior of the joint with a clean dry cloth. The joint shall not be handled
for a two (2) minute period. A fifteen (15) minute period shall be allowed for the joint to develop hanging strength.
(f) A Cemented pipe joint shall not be made in conditions of excessive moisture (ninety (90) percent humidity level)
or when the temperature is below forty (40) degrees or above ninety (90) degrees Fahrenheit.
58
Section 6. Commingling of Plastic Pipe. Plastic pipe shall not be commingled except through the use of male and
female adapters or other transition fittings approved by administrative regulation of the office.
Section 7. Mixing of Plastic and Metal Piping. Plastic and metal piping shall discharge into one another by the
use of proper fittings and adapters.
Section 8. Thermal Expansion. Each plumbing installation shall be engineered and designed giving due
consideration to the expansion characteristics of the material. Expansion tables for both PVC and ABS schedule 40
plastic piping are as follows:
PVC-DWV TYPE 1 THERMAL EXPANSION TABLE
Chart Shows Length Change in Inches vs. Degrees Temperature Change
Lg. Ft. 40°F 50°F 60°F 70°F 80°F 90°F 100°F
20 278 .348 .418 .487 .557 .626 .696
40 .557 .696 .835 .974 1.114 1.235 1.392
60 .835 1.044 1.253 1.462 1.670 1.879 2.088
80 1.134 1.392 1.670 1.949 2.227 2.506 2.784
100 .392 1.740 2.088 2.436 2.784 3.132 3.480
ABS-DWV TYPE 1 THERMAL EXPANSION TABLE
Chart Shows Length Change in Inches vs. Degrees Temperature Change
Lg. Ft. 40°F 5F 60°F 7F 80°F 90°F 100°F
20 0.536 0.670 0.80 0.938 1.072 1.206 1.340
40 1.070 1.340 1.610 1.880 2.050 2.420 2.690
60 1.609 2.010 2.410 2.820 3.220 3.620 4.020
80 2.143 2.680 3.220 3.760 4.290 4.830 5.360
100 2.680 3.350 4.020 4.700 5.360 6.030 6.700
(7 Ky.R. 525; 767; eff. 3-4-81; Am. 16 Ky.R. 2764; 17 Ky.R. 1098; eff. 8-22-90; 19 Ky.R. 1190; 1555; eff. 1-4-93;
TAm eff. 8-9-2007; 35 Ky.R. 2591; 36 Ky.R. 87; eff. 7-29-2009.)
59
815 KAR 20:072. Installation standards for cast iron soil pipe and fittings.
RELATES TO: KRS Chapter 318
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: The office is directed by KRS 318.130 through the
Kentucky Housing, Buildings and Construction Advisory Committee, to adopt and put into effect a State Plumbing
Code. This administrative regulation relates to the proper installation of cast iron soil pipe and fittings. This
amendment is necessary to bring the administrative regulation into technical compliance with KRS Chapter 13A. No
other substantive changes were made.
Section 1. The installation of cast iron soil pipe and fittings shall be made according to recommended
procedures, since care taken in installing will assure the satisfactory performance of the plumbing drainage system.
Section 2. Instructions for Cutting Cast Iron Soil Pipe. (1) During installation assembly, pipe and fittings shall be
inserted into the hub or into the gasket and firmly seated against the bottom of the hub or against the center rib or
shoulder of the gasket. To provide a sound joint with field cut lengths of pipe, it is necessary to have the ends cut
square and as smooth as possible with metal cutting saw or snap type cutters.
(2) Cast iron soil pipe, which may vary somewhat in toughness and resiliency, shall be cut with a twin-lever snap
cutter or a ratchet type cutter equipped with a chain which contains equally spaced beveled cutting wheels. The
following cutting procedure has been found to produce consistently good cuts:
(a) Position chain around pipe so that a maximum number of wheels are in contact with the pipe. Excessive space
between the first and last wheel in contact with the pipe is almost certain to produce a poor quality cut.
(b) Score the pipe before final pressure is applied to complete the cut. Apply only enough pressure to the lever or
ratchet handle to make the cutter wheels indent the pipe.
(c) Release the pressure and rotate tool a few degrees; then apply a quick final pressure to complete the cut. If a
piece of pipe is unusually tough, score the pipe several times and a good cut can be made. If the cutter wheels
become flattened or dull, it will be very difficult (if not impossible) to obtain a satisfactory cut. The life of the chain can
be extended by reversing the chain to obtain equal use of all the wheels. The mechanical features of a cutter shall
be kept in good working order.
Section 3. General Installation Instructions. (1) Vertical piping.
(a) Secure vertical piping at sufficiently close intervals to keep the pipe in alignment and to support the weight of the
pipe and its contents. Support stacks at their bases and at sufficient floor intervals to meet the requirements of local
codes. Approved metal clamps or hangers shall be used for this purpose.
(b) If vertical piping is to stand free of any support or if no structural element is available for support and stability
during construction, secure the piping in its proper position by means of adequate stakes or braces fastened to the
pipe.
(2) Horizontal piping, suspended.
(a) Support ordinary horizontal piping and fittings at sufficiently close intervals to maintain alignment and prevent
sagging or grade reversal. Support each length of pipe by an approved hanger located not more than eighteen (18)
inches from the joint.
(b) Support terminal ends of all horizontal runs or branches and each change of direction or alignment by an
approved hanger.
(c) Closet bends installed above ground shall be firmly secured.
(3) Horizontal piping, underground.
(a) When trenches are dug too deep, support the piping with approved grillage laid on firm ground as denoted in 815
KAR 20:130. To maintain proper alignment during backfilling, stabilize the pipe in proper position by partial backfilling
and cradling.
(b) Piping laid on grade shall be adequately secured to prevent misalignment when the slab is poured.
(c) Closet bends installed under slabs shall be adequately secured.
60
Section 4. Lead and Oakum Joint Installation. (1) Insert the spigot into the hub which has been properly cleaned.
(2) An oakum strand shall be inserted into the joint which is of a diameter that can be pressed into the joint by hand
and sufficiently long to make three (3) turns around the pipe. Drive the strand of oakum to the bottom of the joint
using a yarning iron. Pack the oakum solidly and evenly using a packing iron and hammer.
(3) Place additional strands of oakum into the joint until it fills the hub to within one-half (1/2) inch of the top, and
using a packing iron and hammer, pack this oakum until it forms a uniform surface one (1) inch from the top of the
hub.
(4) Pour molten lead into the joint at one (1) spot between the hub and spigot until it arches up slightly above the top
of the hub.
(5) When the lead has cooled, drive it down at four (4) points around the hub using a caulking iron to insure uniform
caulking.
(6) Caulk the joint on the inside and outside edges using a sixteen (16) ounce ball peen hammer and appropriate
caulking irons.
Section 5. Compression Joint Installation. (1) Fold and insert the one (1) piece rubber gasket into the hub which
has been properly cleaned.
(2) Apply special gasket lubricant to the spigot and inside of the neoprene gasket.
(3) Push, draw or drive the spigot into the gasketed hub with a pulling tool or suitable device.
Section 6. No-hub Joint Installation. (1) Clamp and gasket installation. The following procedures shall be taken to
insure a proper joint:
(a) Place the gasket on the end of one (1) pipe and the stainless steel or cast iron clamp assembly on the end of the
other pipe.
(b) Firmly seat the pipe ends against the integrally molded shoulder inside the neoprene gasket.
(c) Slide the clamp assembly into position over the gasket and tighten the bands or clamps as described below.
(2) Torqueing bands. A properly calibrated torque wrench, set at sixty (60) inch pounds shall be used. The following
procedure for applying torque to the band assembly shall be used: The stainless steel bands shall be tightened
alternately and firmly to sixty (60) inch pounds of torque.
(a) Step 1. The inner bands shall be tightened alternately and firmly to sixty (60) inch pounds of torque.
(b) Step 2. The outer bands shall be tightened alternately and firmly to sixty (60) inch pounds of torque.
(3) Torqueing clamps. A properly calibrated torque wrench, set at 175 inch pounds shall be used. The following
procedure for applying torque to the clamp assembly shall be used: The stainless steel bolts shall be tightened
alternately, gradually and firmly to 175 inch pounds torque. (9 Ky.R. 657; eff. 12-1-82; Am. 10 Ky.R. 1010; eff. 3-31-
84; 17 Ky.R. 2885; eff. 5-3-91; TAm eff. 8-9-2007.)
61
815 KAR 20:073. Installation standards for water and waste piping material of types K, L, M and DWV
copper; types R-K, R-L, R-DWV brass tubing and seamless stainless steel tubing, G or H.
RELATES TO: KRS 318.010, 318.130, 318.150
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the office, through the Kentucky
Housing, Buildings and Construction Advisory Committee, to promulgate an administrative regulation establishing
a State Plumbing Code. This administrative regulation establishes the standards for the proper installation of copper
pipe and fittings for water and waste piping.
Section 1. The installation of copper, brass and seamless stainless steel tubing water and waste piping shall
be made according to the procedures established in this administrative regulation to assure the satisfactory
performance of the plumbing water distribution and drainage system.
Section 2. Cutting, Reaming and Sizing. (1) The tube shall be cut to exact length with a square cut using:
(a) A tube cutter;
(b) A hacksaw blade; or
(c) An abrasive saw.
(2) The tube shall have burrs and slivers removed by using a reamer or other appropriate tool.
(3) The tube shall be brought to true dimensions and roundness by using a sizing tool consisting of a plug and ring.
Section 3. Cleaning. The surface to be joined shall be clean and free from oil, grease and heavy oxides. The end
of the tube shall be cleaned with a fine sand cloth or a special wire brush a distance slightly more than is required to
enter the socket of the fitting.
Section 4. Jointing Techniques. (1) Soldered joints. In accordance with 815 KAR 20:060, the following
procedures shall be used to solder a joint:
(a) After cleaning, the surfaces shall be covered with a thin film of mildly corrosive liquid or petroleum based
pastes that contain chlorides of zinc and ammonium. Self-cleaning flux shall not be used in place of the cleaning
pipe.
(b) Excess flux shall be wiped off within the fitting socket.
(c) The tube end shall be inserted into the socket, with the tube firmly seated against the end of the socket.
(d) Excess flux shall be removed with a rag.
(e) Heat shall be applied to the fitting and then moved in order to heat as large an area as possible. The fitting
and joint shall:
1. Not be overheated; and
2. Be heated until the solder melts on contact with the pipe and flows by capillary attraction into the joint.
(f) The heat shall be removed.
(g) The fitting and joint shall be cooled before moving.
(2) Brazed joints. The following procedures shall be used for a brazed joint:
(a)1. Except as provided in subparagraph 2 of this paragraph, after cleaning, the surface of the tube end and the
fitting socket shall be covered with a thin film of flux in accordance with the recommendations of the manufacturer
of the brazing filler metal being used. Effort shall be made to avoid getting flux inside the tube.
2. Flux may be omitted if joining copper tube to wrought copper fittings with copper-phosphorus alloys (B-cup
Series) which are self-fluxing on copper.
(b) The tube end shall be inserted into the socket hard against the stop and turn if possible.
(c) Heat shall be applied to the parts to be joined, with:
1. The tube heated first; and
2. The fitting at the base of the cup heated next.
(d) Brazing wire, rod or strip shall be applied at the point where the tube enters the socket of the fitting.
(e) The heat shall be removed.
(f) The fitting and joint shall be cooled.
(3) Flared joints; impact tools. The following procedures shall be used for a flared joint:
(a) The joints shall be cut, reamed, sized, and cleaned pursuant to Sections 2 and 3 of this administrative
regulation.
(b) The coupling nut shall be slipped over the end of the tube.
(c) The flaring tool shall:
1. Be inserted into the tube end; and
2. Be driven by hammer strokes to expand the end of the tube to the desired flare.
(d) The fitting shall be placed squarely against the flare.
(e) The coupling nut shall be engaged with the fitting threads.
62
(f) The joint shall be tightened with two (2) wrenches, one (1) on the nut and one (1) on the fitting.
(4) Screw type flaring block.
(a) The procedures established in subsection (3)(a) and (b) of this section shall be followed for impact flaring.
(b) The tube shall be clamped in the flaring block so that the tube is slightly above the block.
(c) The yoke of the flaring tool shall be placed on the block so that the beveled end of the compression cone is
over the tube end.
(d) The compressor screw shall be turned down firmly, forming the flare between the chamber in the flaring block
and the beveled compressor cone.
(e) The flaring tool shall be removed and assembled pursuant to subsection (3)(d), (e), and (f) of this section.
(5) Mechanically formed tee connection.
(a) A mechanically-formed tee connection shall be approved for use in a domestic hot and cold water distribution
system above ground only.
(b) A mechanically extracted collar shall be formed in a continuous operation consisting of drilling a pilot hole and
drawing out the tube surface to form a collar having a height of not less than three (3) times the thickness of the
tube wall. The collaring device shall be fully adjustable so to insure proper tolerance and complete uniformity of
the joint.
(c) All joints shall be brazed in accordance with subsection (2) of this section and the manufacturer's instructions.
A soldered joint shall not be permitted.
(6) Mechanical couplings. Types K and L copper tubing systems from two (2) inch through six (6) inch
and used for water distribution may be installed using mechanical pipe couplings of a bolted type with a flush seal
gasket along with grooved end copper fittings. Couplings shall be of the angle pad design to obtain rigidity.
Section 5. Hangers and Supports. Hangers, anchors and supports shall be of material of sufficient strength to
support the piping and its contents. Hangers, anchors and supports shall be securely attached to the building
construction at sufficiently close intervals to support the piping and its contents. Provisions shall be made to allow
for expansion, contraction, structural settlement and vibrations.
(1) Vertical piping.
(a) Copper tubing shall be supported:
1. At each story for piping one and one-half (1 1/2) inches and larger in diameter; and
2. At each story and not more than ten (10) foot intervals for piping one and one-quarter (1 1/4) inches and smaller
in diameter.
(b) Supports shall be of copper material of sufficient strength which will not adversely react with the piping material.
(2) Horizontal piping.
(a) Copper tubing shall be supported at:
1. Six (6) foot intervals for one (1) inch and smaller in diameter; and
2. Ten (10) foot intervals for one and one-quarter (1 1/4) inch and larger.
(b) Supports shall be of copper material of sufficient strength which will not adversely react with the piping material.
(9 Ky.R. 658; eff. 12-1-82; Am. 14 Ky.R. 1126; eff. 1-4-88; 17 Ky.R. 2886; 3107; eff. 3-91; 20 Ky.R. 1391; eff. 1-
10-94; 26 Ky.R. 215; 615; eff. 9-16-99; TAm eff. 8-9-2007.
63
815 KAR 20:074. Installation standards for steel and wrought iron pipe.
RELATES TO: KRS Chapter 318
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: The office is directed by KRS 318.130 through the
Kentucky Housing, Buildings and Construction Advisory Committee, to adopt and put into effect a State
Plumbing Code. This administrative regulation relates to the proper installation of steel and wrought iron pipe
and fittings and identifies the manufacturer's specification number of the material accepted in those installations.
Section 1. Materials. (1) Steel pipe shall be produced and labeled with the current ASTM specification number
for welded wrought iron pipe or welded and seamless steel pipe.
(2) Schedule 40 shall be the minimum weight.
(3) For water distribution or soil, waste and vent, galvanized pipe shall be used.
(4) Copies of ASTM specifications identified in this administrative regulation may be obtained by writing the
American Society for Testing Materials, 1916 Race Street, Philadelphia, Pennsylvania 19103.
Section 2. Cutting and Reaming. (1) Pipe shall be cut to length with a square cut using pipe cutters, hacksaw
or abrasive saw.
(2) If the cut-to-length pipe is to be threaded or prepared for a mechanical connection, it shall be reamed to the
full inner diameter of the pipe.
Section 3. Jointing Techniques. (1) Screw joints.
(a) Screw joints shall be made by the use of a properly cut thread inserted into the female part of the fitting after
applying the recommended pipe joint compound sparingly to the male threads.
(b) The screw joints shall be tightened hand-tight to check for alignment and then tightened enough to insure a
tight leak-proof joint but shall not be over-tightened.
(2) Mechanical joints.
(a) Mechanical joints for hot and cold water shall not be used above ground unless the couplings are galvanized
and the gaskets are ASTM D 2000, Grade N-R-615 BZ.
(b) The pipe ends shall be lubricated with an approved lubricant and the gasket shall be slipped over one (1)
pipe end.
(c) The pipe ends shall be connected and the gasket shall be inserted into central spanning position.
(d) The housing clamps shall be placed over the gasket and the bolts and nuts tightened with a socket wrench.
Section 4. Hangers and Supports. (1) Hangers, anchors and supports shall be:
(a) Of sufficient strength to support the piping and its contents; and
(b) Securely attached to the building construction at intervals to support the piping and its contents. Provisions
shall be made to allow for expansion, contraction, structural settlement and vibration.
(2) Vertical piping. (a) Screwed piping shall be supported at every other story height and supports shall be of
ferrous metal.
(b) Mechanical joint piping shall be supported at every story height and supports shall be of ferrous metal.
(3) Horizontal piping.
(a) Horizontal piping shall be supported at intervals which keep the piping in alignment and prevent sagging.
(b) Screwed and mechanical joint pipe one and one-half (1 1/2) inches and over shall be supported at twelve
(12) foot intervals; one and one-quarter (1 1/4) inch and smaller shall be supported at eight (8) foot intervals.
(c) Supports shall be of ferrous metal.
(9 Ky.R. 659; eff. 12-1-82; Am. 17 Ky.R. 2888; eff. 5-3-91; 19 Ky.R. 1003; 1389; eff. 12-8-92; TAm eff. 8-9-2007;
35 Ky.R. 2593; 36 Ky.R. 88; eff. 7-29-2009.)
64
815 KAR 20:078. Storage and installation of SDR 11, CPVC plastic pipe and fittings.
RELATES TO: KRS 318.010, 318.015, 318.130, 318.150
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the office, after review by the
Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate an administrative regulation
establishing the Kentucky State Plumbing Code regulating plumbing, including the methods and materials that
may be used in Kentucky. This administrative regulation establishes the methods of storage, handling and
installation of standard dimension ratio (SDR) 11, chlorinated polyvinyl chloride (CPVC) plastic pipe and fittings.
Section 1. Storage and Handling. (1) Chlorinated polyvinyl chloride (CPVC) pipe, tubing, and fittings shall be
stored under cover to avoid unnecessary dirt accumulation and long-term exposure to sunlight. Pipe and tubing
shall be stored with continuous support in straight, uncrossed bundles. Care shall be used in handling to avoid
unnecessary abuse such as abrasion on concrete or crushing.
(2) Solvent cement and primers, because of flammability, shall be stored in an area where there shall be no
exposure to ignition, sparks, open flames, or heat. Solvent cement and primers shall not be used beyond their
marked shelf life.
Section 2. Installation. Correct assembly shall consist of the following steps:
(1) Cutting the pipe square;
(2) Removing burrs;
(3) Cleaning both pipe end and fitting socket with a recommended CPVC cleaner, unless using an approved one
(1) step cement;
(4) Applying a liberal coat of CPVC solvent cement to the pipe and apply a light coat of cement to the fitting socket;
removing all excess cement from the interior which may clog the waterway;
(5) Assembling immediately by bottoming the pipe in the socket and rotating one-quarter (1/4) turn as the joint is
assembled;
(6) Removing excess cement from the joint; and
(7) Determining if the joint has been properly assembled by looking for a small bead of cement to appear at the
junction between the pipe or tubing and the fitting.
Section 3. Installation Temperature. Extra care shall be taken if installing in temperatures below forty (40)
degrees Fahrenheit or above 110 degrees Fahrenheit. The manufacturer's installation instructions shall be
followed carefully.
Section 4. Hangers and Supports. Support shall be provided at each floor level for piping installed in vertical
runs. For horizontal runs, support shall be provided at three (3) foot intervals for pipe one (1) inch or less in
diameter and at four (4) foot intervals for larger pipe sizes. Piping shall not be anchored tightly to a support but
secured with smooth straps or hangers allowing for movement caused by expansion and contraction. Hangers
shall not have rough or sharp edges that come in contact with the piping.
Section 5. CPVC-to-metal Transitions. CPVC threaded adapters shall not be used to transition from CPVC to
metal. Union type fittings that use gaskets or O-rings to seal dissimilar connections shall not be used. Compression
type transition fittings, over-molded transition fittings and push-type fittings that meet the ASSE 1061 standard
may be used.
Section 6. Thermal Expansion. The linear thermal expansion rate for CPVC is approximately one-half (1/2) inch
for each ten (10) degrees Fahrenheit temperature change for each 100 feet of pipe or tubing. If installing long runs
of pipe, one-sixteenth (1/16) to three thirty-seconds (3/32) inch longitudinal clearance shall be allowed per foot of
run to accommodate thermal expansion. Offsets of twelve (12) inches or more every ten (10) feet shall be included
on vertical risers if they are restrained by horizontal branches at each floor. (18 Ky.R. 3561; eff. 8-1-92; Am. 22
Ky.R. 799; eff. 12-7-95; 33 Ky.R. 406; 34 Ky.R. 34; eff. 7-13-2007.)
65
815 KAR 20:080. Waste pipe size.
RELATES TO: KRS Chapter 318
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department, after review by
the Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate an administrative
regulation establishing the Kentucky State Plumbing Code to regulate plumbing, including the sizes of waste
piping. This administrative regulation establishes the minimum size of waste piping required for certain fixtures.
Section 1. The minimum size (nominal inside diameter) of traps, soil, or waste branches for a given fixture
shall not be less than that established in the following table:
Fixture Minimum Size (in inches)
Trap Branch Fixture Unit
Automatic clothes washer 2 2 2
Basement floor drain 3 3 3
Bath: sitz 1 1/2 1 1/2 2
Bathtub 1 1/2 1 1/2 1 1/2
Combination fixture 2 2 2
Dental cuspidor 2 2 2
Dishwashers 1 1/2 1 1/2 1 1/2
Disposal Unit 1 1/2 1 1/2 1 1/2
Drinking Fountain 1 1/4 1 1/4 1
Floor drain in toilet room 3 3 3
Floor drain in utility room 3 3 3
Industrial floor drain 4 4 4
Kitchen sink unit 1 1/2 1 1/2 1 1/2
Laundry tray 1 1/2 1 1/2 1 1/2
Lavatories 1 1/4 1 1/4 1
Sanistand 3 4 6
Shower Stall 1 1/2 1 1/2 1 1/2
Sinks: bar or soda fountain 1 1/2 1 1/2 1 1/2
Sinks: Barium 2 2 2
Sinks: Chemical 1 1/2 1 1/2 1 1/2
Sink: Clinic 3 4 6
Sinks: Kitchen, residence 1 1/2 1 1/2 1 1/2
Sink: Plaster 2 2 2
Sink: Service 3 3 3
Sink: Service wall type 2 2 2
Sink: three compartment 2 2 2
Urinal: lip 1 1/2 1 1/2 1 1/2
Urinal: pedestal 3 3 3
Urinal: stall 2 2 2
Urinal: trough 1 1/2 1 1/2 1 1/2
Water closet:
3.5 gallon per flush
1.6 gallon per flush or less
3
3
3 or 4
3 or 4
6
4
(Recodified from 401 KAR 1:050, 7-5-78; Am. 9 Ky.R. 47; eff. 8-11-1982; TAm eff. 8-9-2007; 43 Ky.R. 460; eff.
11-16-2016.)
66
815 KAR 20:084. Storage and installation of cross-linked polyethylene piping.
RELATES TO: KRS 198B.050, 318.010, 318.015, 318.130, 318.150
STATUTORY AUTHORITY: KRS 198B.040 (10), 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department, after review by
the Kentucky Housing, Buildings and Construction Advisory Committee,, to promulgate an administrative
regulation establishing the Kentucky State Plumbing Code regulating plumbing, including the methods and
materials that may be used in Kentucky. This administrative regulation establishes the requirements for the
storage, handling, and installation of standard dimension ratio (SDR) 9 cross-linked polyethylene pipe and fittings.
Section 1. Definitions.
(1) "ASSE" means American Society of Sanitary Engineers.
(2) "ASTM" means American Society for Testing Materials.
(3) "PEX" means cross-linked polyethylene pipe.
(4) "PEX-AL-PEX" means polyethylene/aluminum/cross-linked polyethylene composite pressure pipe.
Section 2. Material. (1) PEX that is to be used for cold water only shall be produced and labeled as established
by ASTM F-876.
(2) Cross-linked polyethylene (PEX) that is to be used for either cold water or hot water shall be produced and
labeled as established by ASTM F-877.
(3) PEX-Al-PEX shall be produced and labeled as established by ASTM F-1281.
(4) Cold expansion fittings with PEX reinforcing rings for use with PEX tubing shall be produced and labeled as
established by ASTM F-1960.
(5) Metal insert fittings utilizing a copper crimp ring shall be produced and labeled as established by ASTM F-
1807.
(6) Stainless steel clamps substituted for the copper crimp ring shall be produced as established by ASTM F-
2098.
(7) Plastic insert fittings for PEX shall be produced as established by ASTM F-2159.
(8) Push fit fittings for PEX shall be produced as established by ASSE 1061.
(9) Metal insert fittings for cross-linked polyethylene/aluminum/cross-linked polyethylene composite pressure pipe
shall be produced as established by ASTM F-1974.
(10) Metal insert fittings utilizing a copper crimp ring for PEX-AL-PEX shall be produced as established by ASTM
F-2434.
Section 3. Storage and Handling. (1) PEX shall not be stored where it will be exposed to direct or indirect
ultraviolet light (sunlight).
(2)(a) PEX shall not be exposed to materials that affect the basic properties of cross-linked polyethylene, brass,
or copper.
(b) Chemicals, pipe thread compounds, putty, and mineral or linseed oil compounds shall not contact the pipe.
Section 4. Installation. (1) Water Service Installation.
(a) Tubing shall be snaked in the ditch to allow for linear expansion and contraction.
(b) 1. Tubing shall not be installed in contaminated soils.
2. PEX shall not be installed in areas of known soil contamination or where there is a high risk of chemical spills
such as organic solvents or petroleum distillates.
(c) Metallic fittings other than those consisting of red brass shall be protected from the soil to prevent corrosion.
(d) The number of fittings shall be kept to a minimum.
(e) The bottom of the trench shall be flat and free of rocks, hollows, or other sharp objects.
(f) If placed in soil consisting of rock, piping shall be covered with six (6) inches of coarse sand or pea gravel.
(g) If passing through a foundation wall, a rigid sleeve that spans the distance from within the wall out to the
undisturbed soil shall be used to prevent shearing of the tubing.
(2) Distribution System.
(a) If PEX is to be buried under a building, fittings shall not be used.
(b) PEX passing through a concrete slab or wall shall be protected by use of sleeves.
(c)PEX passing through metal studs or plates shall be protected by plastic grommets designed for this purpose.
(d) PEX shall not be used in operating conditions inconsistent with pressure ratings that appear on the tubing and
the applicable ASTM standard.
67
(e) PEX shall not be installed:
1. Where it may be exposed to direct or indirect ultraviolet light (sunlight);
2. Where it may be exposed to open flame;
3. With or exposed to petroleum based caulking or sealants;
4. Where it may be subjected to prolonged exposure to free chlorine concentrations greater than four (4) ppm;
5. Within twelve (12) inches of any recessed light fixture; or
6. Within six (6) inches of any gas appliance metallic vent.
(f) PEX shall be tested under a pressure not to exceed 100 pounds per square inch nor less than forty (40) pounds
per square inch.
Section 5. Hangers and Supports. (1) Cross-linked polyethylene (PEX) sizes one (1) inch and smaller installed
horizontally shall be supported at intervals not to exceed thirty-two (32) inches.
(2) PEX sizes 1-1/4" and larger installed horizontally shall be supported at intervals not to exceed forty-eight (48)
inches.
(3) PEX installed vertically shall be supported at the base of each story with a mid-story guide.
(4) PEX shall not be rigidly anchored but shall be installed to allow room for proper expansion and contraction of
the tubing.
(5) Hangers or strapping shall be constructed of plastic material or be coated to prevent damage to the tubing.
(6) PEX-AL-PEX installed horizontally shall be supported at intervals not to exceed ninety-eight (98) inches.
(7) Cross-linked polyethylene/aluminum/cross-linked polyethylene installed vertically shall be supported at the
base of each story with a mid-story guide. (42 Ky.R. 2688, 2898; eff. 6-22-2016.)
68
815 KAR 20:090. Soil, waste, and vent systems.
RELATES TO: KRS 318.010, 318.015, 318.130, 318.150, 318.200
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department, after review by
the Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate an administrative
regulation establishing the Kentucky State Plumbing Code regulating plumbing, including the methods and
materials that may be used in Kentucky for soil, waste, and vent systems. This administrative regulation
establishes the manufacturer's specification number of the material accepted in the installation and design of soil,
waste, and vent systems in each type of plumbing system.
Section 1. Grades and Supports of Horizontal Piping. (1) (a) Horizontal piping shall run in practical alignment
and at a uniform grade of not less than one-eighth (1/8) inch per foot and shall be supported or anchored in
accordance with the manufacturer's recommendations.
(b) The supports or anchors shall not be placed at intervals that exceed ten (10) feet in length.
(2) A stack shall be supported at its base, and each pipe shall be rigidly secured.
(3) No-hub pipe and fittings shall be supported at each joint of pipe and fittings.
(4) Polyvinyl chloride and acrylonitrile butadiene-styrene schedule forty (40) horizontal piping shall be supported
at:
(a) Intervals not to exceed four (4) feet;
(b) The base of each vertical stack; and
(c) Each trap branch as close to the trap as possible.
(5) Polyethylene pipe and fittings shall be continuously supported with a V channel.
(6) A stack shall be rigidly supported at its base and at the floor level.
Section 2. Change in Direction. (1) Except as provided in subsections (2), (3), or (4) of this section, a change in
direction shall be made by the appropriate use of a forty-five (45) degree wye, half-wye (1/2), quarter (1/4), sixth
(1/6), eighth (1/8) or sixteenth (1/16) bend.
(2) A single sanitary tee may be used in a vertical stack.
(3) A sanitary tee may be turned on its back or side. If turned on its back or side, a sanitary tee shall not be placed
at an angle of more than forty-five (45) degrees.
(4) A double sanitary tee may be used on a vertical soil, waste, and vent line.
Section 3. Prohibited Fittings. The following shall be prohibited:
(1) A double hub bend and double hub tee or inverted hub on a sewer, soil, or waste line;
(2) The drilling and tapping of a house sewer or house drain, soil, waste, or vent pipe;
(3) The use of a saddle hub; and
(4) Pipe installed with a hub or restriction that reduces the area or capacity of the pipe.
Section 4. Dead Ends. In the installation of a drainage system, a dead end shall not be used.
Section 5. Protection of Material. (1) A pipe passing under or through a wall shall be protected from breakage.
(2) A pipe passing through or under cinder, concrete, or other corrosive material shall be protected against external
corrosion.
Section 6. Materials. (1) Main or branch soil, waste, and vent pipes and fittings within or underneath a building
shall be:
(a) Hub and spigot extra heavy or service weight cast iron;
(b) No-hub service weight cast iron;
(c) Galvanized steel;
(d) Galvanized wrought iron;
(e) Lead;
(f) Brass;
(g) Types K, L, M, and DWV copper;
(h) Standard high-frequency welded tubing produced and labeled with the latest ASTM specifications;
(i) Types R-K, R-L, R-DWV brass tubing;
(j) DWV brass tubing produced and labeled as ASTM B587;
(k) Seamless stainless steel tubing;
(l) Grade G or H produced and labeled as ASTM A-312;
(m) Polyvinyl chloride schedule 40 or 80 produced and labeled as ASTM D2665, D1784, and F-891;
(n) Coextruded composite PVC pipe produced and labeled ASTM F-1488;
69
(o) Acrylonitrile-butadiene-styrene schedule 40 or 80 produced and labeled as ASTM D2661, F-1488, or F-628;
or
(p) Silicon iron or borosilicate.
(2) A main or branch soil waste and vent pipe and fittings underground shall either be:
(a) Hub and spigot extra heavy or service weight cast iron;
(b) No-hub service weight cast iron;
(c) Type K or L copper pipe;
(d) Type R-K, R-L brass tubing;
(e) Lead; or
(f) Silicon iron or borosilicate pipe and fittings or plastics DWV established in this section.
(3) Underground waste pipe installed beneath a concrete slab shall not be less than two (2) inches in diameter
and shall extend no less than twelve (12) inches above the concrete slab.
Section 7. Size of Soil and Waste Pipe per Fixture Unit on One Stack. (1) The following table, based on the
rate of discharge from a lavatory as a unit, shall be employed to determine fixture equivalents:
Pipe Size (In Inches) Maximum Developed Length Fixture Units
1 1/4 25 ft. 1
1 1/2 60 ft. 2
2 80 ft. 6
2 1/2 100 ft. 12
3 225 ft. 36
4 unlimited 172
5 unlimited 342
6 unlimited 576
8 unlimited 1600
10 unlimited 2900
12 unlimited 4600
(2) A water closet shall be on a minimum of a three (3) inch soil and waste pipe with a maximum of three (3) water
closets or soil discharging fixtures per three (3) inch soil and waste pipe. Four (4) water closets with a maximum
flushing rate of one and six-tenths (1.6) gallons per flush per water closet shall be allowed to discharge into a
three (3) inch soil and waste pipe.
Section 8. Soil and Vent Stacks. (1) A building in which a plumbing fixture is installed shall have a soil or waste
and vent stack, or stacks, extending full size through the roof.
(2) A soil or waste and vent stack shall be as direct as possible and free from sharp bends or turns.
(3) The required size of the soil or waste and vent stack shall be determined from the total fixture units connected
to the stack in accordance with Section 7 of this administrative regulation except that more than:
(a) Three (3) water closets with a flush rate of three and five-tenths (3.5) gallons per flush shall not discharge into
a three (3) inch stack; and
(b) Four (4) water closets with a flush rate of one and six-tenths (1.6) gallons per flush or less shall not discharge
into a three (3) inch stack.
Section 9. Future Openings. An existing opening or an opening installed in a plumbing system for future use
shall be complete with its soil, waste, and vent piping and shall comply with this administrative regulation.
Section 10. House Drain. (1) The size of the house drain shall be determined by the total number of fixture units
connecting to the house drain. The total area of vents through the roof shall be equal to that of the house drain
with a minimum of one (1) three (3) inch stack.
(2) If a three (3) inch house drain enters a building, it shall be attached to a three (3) inch stack. One (1) floor drain
may be added to the house drain with a three (3) inch trap if it conforms with the requirements of Section 24 of
this administrative regulation, without counting toward the fixture units of the system.
Section 11. Soil and Waste Stacks, Fixture Connections. (1) A soil and waste stack or branch shall have
correctly faced inlets for fixture connections.
(2) Each fixture shall be independently connected to the soil or waste system.
(3) A fixture connection to a water closet, floor-outlet pedestal sink, pedestal urinal, or other similar plumbing
fixture shall be:
70
(a) Cast iron;
(b) Lead;
(c) Brass;
(d) Copper; or
(e) Plastic closet bend.
(4) A three (3) inch closet bend shall have a four (4) inch by three (3) inch flange.
Section 12. Changing Soil and Vent Pipes in an Existing Building. If the soil, waste, and vent piping in an
existing building is not extended undiminished through the roof, or if there is sheet metal soil or waste piping and
the fixtures are to be changed or replaced, the piping shall be replaced with appropriate sizes and materials as
prescribed for new work.
Section 13. Prohibited Connections. (1) A fixture connection shall not be made to a lead bend or a branch of a
water closet or a similar fixture.
(2) A vent pipe above the highest installed fixture on a branch or main shall not be used as a soil or waste pipe.
Section 14. Soil, Waste, and Vent Pipe Protected. (1) Soil, waste, or vent pipe shall not be installed or permitted
outside a building unless adequate provision shall be made to protect it from frost.
(2) The piping shall be wrapped with one (1) layer of heavy hair felt and at least two (2) layers of two (2) ply tar
paper, properly bound with copper wire, or the vent shall be increased to full size, the size of the increaser required
as if it were passing through the roof.
Section 15. Roof Extensions. (1) A roof extension of soil and waste stacks shall run full size at least one (1) foot
above the roof.
(2) If the roof is used for purposes other than weather protection, the extension shall not be less than five (5) feet
above the roof.
(3) A stack of less than three (3) inches in diameter shall be increased to a minimum of three (3) inches in diameter
before passing through a roof.
(4) If a change in diameter is made, the fitting shall be placed at least one (1) foot below the roof.
Section 16. Terminals. If a roof terminus of a stack or vent is within ten (10) feet of the top, bottom, face, or side
edge of a door, window, scuttle, or air shaft, and not screened from the opening by a projecting roof or building
wall, it shall extend at least two (2) feet above the top edge of the window or opening.
Section 17. Terminals Adjoining High Buildings. (1) Soil, waste, or vent pipe extension of a new or existing
building shall not run or shall not be placed on an outside wall, but shall be installed inside the building unless the
piping is protected from freezing.
(2) If the new building is built higher than the existing building, the owner of the new building shall not locate a
window within ten (10) feet of an existing vent stack on the lower building.
Section 18. Protected Traps and Vents. (1) A fixture trap shall be protected against siphonage and
backpressure.
(2) Air circulation shall be assured by means of an individual vent.
(3) A crown vent shall not be permitted.
Section 19. Distance of Trap from Vent. (1)(a) The distance between the vent and the fixture trap shall be
measured along the center line of the waste or soil pipe from the vertical inlet of the trap to the vent opening.
(b) The fixture trap vent, except for a water closet or a similar fixture, shall not be below the dip of the trap, and
each ninety (90) degree turn in the waste line of the main waste, soil, or vent pipe shall be washed.
(c) A fixture trap shall have a vent located with a developed length not greater than that in the following table:
Size of Fixture Drain (In Inches) Distance Trap to Vent
1 1/4 2 ft. 6 in.
1 1/2 3 ft. 6 in.
2 5 ft.
3 6 ft.
4 10 ft.
(2) A fixture branch on a water closet shall not be more than four (4) feet six (6) inches.
71
Section 20. Main Vents to Connect at Base. (1) All main vents or vent stacks shall:
(a) Connect full size at the base of the main soil or waste pipe at or below the lowest fixture branch; and
(b) Extend undiminished in size through the roof or be reconnected with the main soil or vent stack at least six (6)
inches above the rim of the highest fixture.
(2)(a) Except as established in paragraph (b) of this subsection, if it becomes necessary to increase the size of
a vertical vent stack, the entire stack shall be increased from its base.
(b) If the height of a stack which does not serve as the main vent is less than forty-five (45) feet, it shall not be
required to be increased from its base.
Section 21. Vents; Required Sizes. (1) The required size of a vent or vent stack shall be determined by the total
number of fixture units it serves and the developed length of the vent, interpolating, if necessary, between
permissible length of vent given in the following table:
MAXIMUM PERMISSIBLE LENGTHS OF VENTS
Pipe Size (In Inches) Maximum Length (In Feet) Fixture Units
1 1/4 30 2
1 1/2 150 10
2 200 24
2 1/2 250 36
3 300 72
4 400 240
5 800 720
(2) Except for a residential installation, if a fixture opening is installed more than twenty-five (25) feet of developed
length from the point where it is connected to the main soil or waste system, or, if more than ten (10) feet of vertical
piping is used, the vent shall be continued full size through the roof or returned full size to the main vent.
Section 22. Branch and Individual Vents. A branch or individual vent shall not be less than one and one-fourth
(1 1/4) inches in diameter and shall not exceed the maximum length permitted for a main vent.
Section 23. Vent Pipes Grades and Connections. (1) A vent or branch vent pipe shall be free from drops or
sags and be so graded and connected as to drip back to the soil or waste pipe by gravity.
(2) If a vent pipe connects to a horizontal soil or waste pipe, the vent branch shall be taken off above the center
line of the pipe, and the vent pipe shall rise vertically at an angle of forty-five (45) degrees to the vertical, to a point
six (6) inches above the fixture it is venting before offsetting horizontally or connecting to the branch, main, waste,
soil or vent.
Section 24. Vents Not Required; Backwater Traps, Subsoil Catch Basin, and Basement Floor Drains. (1) A
vent shall not be required on a backwater trap, subsoil catch basin trap, or a basement floor drain if the basement
floor drain branches into the house drain so that measuring along the flow line from the center of the stack, the
floor drain shall not be closer than five (5) feet of the stack, nor farther than twenty (20) feet.
(2) A basement floor drain shall not require an individual vent if it branches into the house drain so that measuring
along the flow line from the center of the house drain the basement floor drain shall not be farther than ten (10)
feet from the house drain.
Section 25. Conditions Under Which Common Vent Permissible. If two (2) water closets, two (2) lavatories,
or two (2) fixtures of identical purpose are located on opposite sides of a wall or partition, or directly adjacent to
each other within the distance established in Section 19 of this administrative regulation measured along the
center line of the flow of water, the fixtures may have a common soil or waste pipe and a common vent. It shall
be vented in accordance with this administrative regulation.
Section 26. Floor Drain Individual Vent Not Required. (1) A manufacturer's floor drain shall not require an
individual vent if placed on a waste line for a floor drain within the distance of ten (10) feet from the main waste
line, or stack, if the base of the stack is washed and the stack or stacks are undiminished through the roof, or
connected to a main vent stack.
(2) An open receptacle may be connected to a floor drain line without being vented if the waste line discharges
into a four (4) inch master trap before entering the sanitary sewer system.
72
Section 27. Floor Drain. A floor drain or service sink installed on the operational floor level of a sewage and
water treatment plant facility that discharges into an open sump and is not connected directly to the sanitary
sewage system shall not be required to be trapped or vented.
Section 28. House Drain Material. A house drain shall be:
(1) Extra heavy cast iron;
(2) Service weight cast iron;
(3) Brass;
(4) Type (K) or (L) copper;
(5) Lead;
(6) ABS or PVC plastic; or
(7) Duriron.
Section 29. Indirect Waste Connections. (1) Waste pipe from a refrigerator drain or other receptacle where food
is stored or waste water from a water cooled compressor shall connect indirectly with the house drain, soil or
waste pipe.
(2) The drain shall be vented to the outside air.
(3) The waste pipe shall discharge into an open sink or another approved open receptacle that is properly supplied
with water in accordance with this administrative regulation.
(4) The connection shall not be located in an inaccessible or unventilated area.
Section 30. Bar and Soda Fountain Wastes. (1)(a) A bar and soda fountain waste, sink, or receptacle shall have
a one and one-half (1 1/2) inch P trap and branches.
(b) The main shall not be less than two (2) inches.
(c) The fresh air pipe shall not be less than one and one-half (1 1/2) inches.
(d) The main waste line shall discharge into a properly vented and trapped open receptacle inside or outside a
building.
(2) A floor receptor or floor sink may be installed flush with the finished floor if it has a full grate with an attached
funnel to receive indirect waste.
(3) A floor receptor or floor sink installed specifically for the indirect wastes from a tilting braising pan, tilting kettle,
or other similar equipment may be installed level with or slightly recessed in the floor if the receptor is equipped
with a proper strainer and receives no other indirect waste.
Section 31. Open Receptacles. Soil or waste piping receiving the discharge from an open receptacle shall be at
least six (6) inches above the surface of the ground if it discharges into a septic system.
Section 32. Refrigerator and Condensate Wastes. (1) A refrigerator or condensate discharge waste pipe shall
not be less than:
(a) One and one-half (1 1/2) inches for one (1) to three (3) openings; and
(b) Two (2) inches for four (4) to eight (8) openings.
(2) Each opening shall be trapped.
(3) The waste piping shall be equipped with sufficient cleanouts to allow for thorough cleaning.
Section 33. Overflow Pipes. (1) Waste from a water supply tank or exhaust from a water lift shall not be directly
connected to a house drain, soil, or waste pipe.
(2) The waste pipe shall discharge upon a roof or into a trapped open receptacle.
Section 34. Acid and Chemical Wastes. (1) A corrosive liquid shall not be permitted to discharge into the soil,
waste, or sewer system unless otherwise permitted by this administrative regulation.
(2) The waste shall be thoroughly diluted or neutralized by passing through a properly constructed and acceptable
dilution or neutralizing pit before entering the house sewer.
Section 35. Laboratory Waste Piping. (1) Laboratory waste piping shall be sized in accordance with this
administrative regulation and each fixture shall be individually trapped.
(2) A continuous waste and vent pipe system may be used if the waste discharges into a vented dilution pit outside
the building with a vent equal to the size of the drain. The vent may be eliminated if the pit has a ventilated cover.
(3) If a dilution pit is not required and is not used, the fixtures shall be individually vented.
(4) If construction conditions permit, the base of the stack of the continuous waste and vent system shall be
washed by the last fixture opening, and continue full size independently through the roof.
73
(5) A fixture branch exceeding more than the distance established in the table in Section 19 of this administrative
regulation from the main shall be revented, and the distance shall be measured from the center of the main to the
center of the vertical riser.
(6)(a) A fixture connection shall rise vertically to a height so that the trap shall not be lower than twelve (12) inches
from the bottom of the sink.
(b) Two (2) or more sinks may be connected into a common waste before entering the riser of the continuous
waste and vent system, if the fixtures are not more than five (5) feet from the center of one (1) fixture to the center
of the other.
Section 36. Acid Waste Piping. (1) Underground piping for acid wastes shall be:
(a) Extra heavy salt glazed vitrified pipe;
(b) Silicon iron;
(c) Lead;
(d) Polyethylene pipe and fittings produced and labeled as ASTM D204;
(e) Polypropylene pipe produced and labeled as ASTM D4101;
(f) Polypropylene pipe and fittings produced and labeled as ASTM F-1412; or
(g) Chlorinated Poly Vinyl Chloride (CPVC) Chemical Waste Drainage Systems meeting ASTM F 2618; or
(h) Other materials approved in 815 KAR 20:020, Section 5.
(2) Piping for acid wastes and vents above ground shall be:
(a) Silicon iron;
(b) Lead;
(c) Borosilicate;
(d) Polyethylene pipe produced and labeled as ASTM D-1204-62T;
(e) Polypropylene pipe produced and labeled as ASTM D-4101-85; or
(f) Filament-wound reinforced thermosetting resin pipe produced and labeled as ASTM D-2996 (green or poly
thread); or
(g) Chlorinated Poly Vinyl Chloride (CPVC) Chemical Waste Drainage Systems meeting ASTM F 2618.
Section 37. Special Vents. A flat vent may be allowed if the design of the building prohibits the type of venting
required by this administrative regulation.
Section 38. Basement Floor Drains and Sanitary Sewage Systems. (1) Except for a basement floor drain
exempted pursuant to subsection (2) of this section, a basement floor drain shall be connected to the house sewer
and properly trapped and vented as established in this administrative regulation.
(2)(a) A basement floor drain in a single family dwelling shall not be connected to the house sewer and shall be
exempt from this section if, prior to the installation, the local health department or sanitary sewage system board,
plant, district, or treatment plant owner notifies the Division of Plumbing, in writing, that connection is detrimental
to the functioning of the sanitary sewer system or subsurface system.
(b) If the drain is not to be connected to the house sewer, the installation shall also be exempt from the waste,
trap, and venting provisions of the State Plumbing Code. (Recodified from 401 KAR 1:060, 7-5-1978; Am. 6 Ky.R.
134; eff. 1-2-1980; 7 Ky.R. 509; eff. 1-7-1981; 846; eff. 6-3-1981; 9 Ky.R. 834; eff. 2-2-1983; 1238; eff. 6-1-1983;
14 Ky.R. 1129; eff. 1-4-1988; 16 Ky.R. 72; eff. 8-22-1989; 1272; 1590; eff. 8-22-1989; 18 Ky.R. 2722; eff. 4-3-
1992; 3537; 19 Ky.R. 411; eff. 8-1-1992; 1192; 1556; eff. 1-4-1993; 22 Ky.R. 1386; eff. 3-7-1996; 23 Ky.R. 2691;
2990; eff. 2-10-1997; 3978; eff. 6-25-1997; 27 Ky.R. 1905; 2796; eff. 3-22-2001; 30 Ky.R. 2393; 31 Ky.R. 88, eff.
8-6-2004; 32 Ky.R. 2367; 33 Ky.R. 408; eff. 9-120-2006; 34 Ky.R. 1239; 1750; eff. 2-1-2008; 35 Ky.R. 2594; 36
Ky.R. 88; eff. 7-29-2009; 35 Ky.R. 2594; 36 Ky.R. 88; 1352; eff. 3-5-2010; 41 Ky.R. 175; eff. 9-24-2014; 43 Ky.R.
461; eff. 11-16-2016.)
74
815 KAR 20:100. Joints and connections.
RELATES TO: KRS 198B.040 (7), (10), 198B.050(2), 318.130, 318.150
STATUTORY AUTHORITY: KRS 198B.040(10), 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department, after review by
the Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate a State Plumbing Code.
This administrative regulation establishes the methods that shall be used in joining certain types of piping materials
together and denotes the methods that shall be used in securing plumbing fixtures to waste piping outlets. This
administrative regulation also establishes the manufacturer's specification number of the material accepted in
those installations.
Section 1. Definitions.
(1) "ANSI" means the American National Standards Institute and a copy of the ANSI specifications identified in
this administrative regulation may be obtained by writing the American National Standards Institute, 1430
Broadway, New York, NY 10018.
(2) "ASTM" means the American Society for Testing Materials and a copy of the ASTM specifications identified
in this administrative regulation may be obtained by writing the American Society for Testing Materials, 1916 Race
Street, Philadelphia, Pennsylvania 19103.
Section 2. Water and Airtight Joints. Joints and connections shall be made gas and water tight.
Section 3. Vitrified Pipe Joints, Concrete Pipe Joints, House Sewers - Combined Sewers. (1) Joints in
vitrified clay pipe shall be ASTM specification C-425.
(2) Joints in concrete pipe shall be ASTM specifications C-443.
(3) If it is necessary to use piping in other than standard lengths, hot poured joints may be used.
(4) Joints between cast iron pipe and vitrified clay pipe or concrete pipe shall be made either of hot poured
bitumastic compound or by a preformed elastomeric ring. The ring shall completely fill the annular space between
the cast iron spigot and the vitrified clay or concrete pipe hub.
(5) Joints in pipe and fittings with no more than two (2) pipe sizes between vitrified clay, acrylonitrile-butadiene-
styrene, or polyvinyl chloride to cast iron pipe and fittings or the joining of either material may be made with proper
fittings by using a dispersion grade polyvinyl chloride ring produced and labeled as either ASTM C-443, C-425, or
C-564, or a elastomeric polyvinyl chloride coupling.
Section 4. Caulked Joints. Caulk joints shall be firmly packed with oakum or hemp and shall have at least one
(1) inch of pure lead properly caulked. Paint, varnish, or putty shall not be permitted until tests have been
performed.
Section 5. (1) Screw joints. Screw joints shall be American Standard screw joints, and all burrs or cuttings shall
be removed as required by 815 KAR 20:150.
(2) Mechanical joint couplings for hot and cold water. Mechanical joint couplings for hot and cold water shall not
be used above ground unless the couplings are galvanized and the gaskets produced and labeled as ASTM
D2000, grade N-R-615 BZ, or other material listed in approved parts or materials list, 815 KAR 20:020.
(3) Mechanical joint couplings for storm water piping. Mechanical joint couplings for storm water piping shall not
be used above ground unless the couplings are either black iron or galvanized and the gaskets produced and
labeled as ASTM D2000, grade N-R-615 BZ.
(4) Joints in PVC and ABS Schedule 40 or 80 pipe and fittings.
(a) Joints in polyvinyl chloride Schedule 40 or 80 pipe and fittings shall be solvent welded joints and shall be in
compliance with ASTM D2665.
(b) Joints in acrylonitrile-butadiene-styrene pipe and fittings shall be solvent welded joints and shall be in
compliance with ASTM D2661.
(c) Acrylonitrile-butadiene-styrene and polyvinyl chloride sewer piping produced and labeled as ASTM 3034 shall
be joined by solvent cement produced and labeled as ASTM D-2661-90 for acrylonitrile-butadiene-styrene and
ASTM D2665 for polyvinyl chloride or with an elastomeric joint in compliance with ASTM D3212.
(5) Copper pipe, brass, and stainless steel tubing joints.
(a) Joints of copper pipe, brass, and stainless steel tubing shall be soldered.
(b) Mechanical couplings.
(1) Types K and L copper tubing systems from two (2) inch through six (6) inch and used for water distribution
shall be installed using mechanical pipe couplings of a bolted type with a flush seal gasket along with grooved
end copper fittings.
2. Couplings shall be of the angle pad design to obtain rigidity.
75
(6) Expansion. An expansion joint shall be of an approved type and the material shall comply with the type of
piping in which it is installed.
(7) Brazed joints. Brazed joints shall be made by cleaning the surfaces to be joined down to the base metal,
applying flux approved for the joints and for the filler metal to be used, and making the joint by heating to a
temperature sufficient to melt the approved brazing filler metal on contact.
(8) Elastomeric polyvinyl chloride coupling. Elastomeric polyvinyl chloride couplings shall be used for connecting
cast iron, vitrified clay, concrete, or plastic pipe, or the combination of these pipe materials for use on house
sewers and combination sewers only. This coupling shall be provided with #305 stainless steel clamps.
Section 6. Cast Iron Soil Pipe Joints. (1) Joints in cast iron shall either be caulked, screwed, or made with the
use of neoprene gaskets. Neoprene gaskets shall be produced and labeled as ASTM C-564-70.
(2) Cast iron coupling for joining hub less cast iron pipe shall consist of neoprene gasket produced and labeled
as ASTM C-564, cast iron clamps produced and labeled as ASTM A-48, and stainless steel bolts and nuts
produced and labeled as ANSI B-18.2.1 and ANSI B-18.2.2.
Section 7. Borosilicate Joints. Joints and gaskets used for borosilicate pipe shall be made in a manner approved
by the department as established in 815 KAR 20:060.
Section 8. (1) Steel, brass, and copper connections to cast iron pipe. Steel, brass, and copper joints
connected to cast iron pipe shall be either screwed or caulked joints. Caulked joints shall be made by the use of
a caulking spigot.
(2) PVC and ABS pipe and fitting connections to steel, brass, copper, and cast iron pipe.
(a) Polyvinyl chloride and acrylonitrile-butadiene-styrene pipe and fitting connections to steel, brass, copper, or
cast iron pipe shall be either a screwed or caulked joint.
(b) Joints between Schedule 40 PVC or ABS pipe and cast iron pipe may be made by the use of a neoprene
gasket produced and labeled as ASTM C-564-70.
(c) Caulk joints shall be made with the use of either a polyvinyl chloride or acrylonitrile-butadiene-styrene or cast
iron caulking spigot.
(3) Stainless steel tubing to cast iron pipe or galvanized steel pipe or to copper tubing.
(a) Stainless steel tubing to cast iron pipe shall be made by caulking spigot.
(b) Stainless steel tubing to galvanized steel pipe or copper pipe shall be made by the use of an adaptor.
(4) Joints in acid waste piping.
(a) Joints in vitreous glazed piping shall be made in compliance with manufacturer's recommendations.
(b) Joints in polyethylene and polypropylene piping shall be made by the heat fusion process.
(c) Joints in polypropylene shall be made with a union joint.
(d) Joints in borosilicate pipe shall be a stainless steel mechanical joint.
(e) Joints between silicon iron pipe shall be either caulk joint or stainless steel mechanical joint.
Section 9. Lead Pipe. (1) Joints in lead pipe or between lead pipe and brass or copper pipes, ferrules, soldering
nipples, or trap, shall be full-wiped joints with an exposed surface of the solder at each side of the joint of not less
than three-quarters (3/4) of an inch.
(2) The minimum thickness of the thickest part of the joint shall be at least as thick as the material being used.
(3) If lead pipe is used for acid waste lines, the pipe may be joined by burning.
Section 10. Lead Pipe to Cast Iron, Steel, or Wrought Iron Pipe. The joints between lead to cast iron, steel, or
wrought iron shall be made by means of a caulking ferrule or a soldering nipple.
Section 11. Wall or Floor Flange Joints. Wall or floor flange joints shall be made by using a lead ring or brass
flange and shall be properly soldered.
Section 12. Soil Pipe, Iron Pipe, Copper Pipe, Tubular Trap Joints. Joints between soil pipe, iron pipe, copper
pipe, and tubular traps shall be made by the use of a heavy red cast brass adaptor. Tubular traps shall be soldered
to the adaptor in compliance with manufacturer's recommendations.
Section 13. Slip Joints. (1) Slip joints shall be permitted on the inlet side of the trap.
(2) A single one and one-half (1 1/2) inch slip joint connection with an elastomeric gasket shall be permitted on
the outlet side of a one and one-half (1 1/2) inch trap.
Section 14. Unions. Unions shall be ground faced and shall not be concealed or enclosed.
76
Section 15. Roof Joints. (1) The joint at the roof shall be made watertight by use of copper, lead, or other
approved flashing or flashing material.
(2)(a) Except as established in paragraph (b) of this subsection, the approved flashing shall:
1. Not extend less than six (6) inches from the pipe in all directions; and
2. Extend upward twelve (12) or more inches and turn down into the pipe.
(b) Lead flashings for three (3) inch and four (4) inch vent stacks shall have a minimum twelve (12) inch base.
(3) A hub flashing may be used if it is constructed in a manner allowing the flashing to be caulked into a hub above
the roof.
Section 16. Increasers and Reducers. If different size pipes or fittings are to be concealed, the proper size
increaser or reducer pitched at an angle of forty-five (45) degrees between the two (2) sizes shall be used. This
section shall not apply to nonmetallic installations.
Section 17. Prohibited Joints and Connections. A fitting or connection that has an enlargement chamber, or
recess with a ledge shoulder, or reduction of the pipe area in the direction of the flow shall be prohibited.
Section 18. Hangers and Supports. Piping and fixtures shall be adequately supported by hangers or anchors
securely attached to the building construction. (Recodified from 401 KAR 1:070, 7-5-78; Am. 5 Ky.R. 161; eff. 10-
4-78; 349; eff. 1-3-79; 9 Ky.R. 48; eff. 8-11-82; 10 Ky.R. 1012; eff. 3-31-84; 14 Ky.R. 1133; eff. 1-4-88; 15 Ky.R. 603;
972; eff. 9-28-88; 17 Ky.R. 2893; eff. 5-3-91; 19 Ky.R. 1010; 1394; eff. 12-8-92; 20 Ky.R. 1392; eff. 1-10-94; 27 Ky.R.
2242; 2799; eff. 3-22-2001; TAm eff. 8-9-2007; 35 Ky.R. 2598; 36 Ky.R. 92; eff. 7-29-2009; 38 Ky.R. 2099; eff. 8-31-
2012; 42 Ky.R. 130; eff. 11-6-2015.)
77
815 KAR 20:110. Traps and clean-outs.
RELATES TO: KRS 318.010, 318.130, 318.150
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the office after review by, the
Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate an administrative regulation
establishing the Kentucky State Plumbing Code. This administrative regulation establishes requirements for traps
and clean-outs to prevent harmful gases and odors from entering a building or home that is served by a plumbing
system and identifies the manufacturer's specification number of acceptable material.
Section 1. Traps, Kind and Minimum Size. (1) A Trap shall be self-cleaning.
(2) A trap for a bathtub, lavatory, sink or other similar fixture shall be made of the following:
(a) Tubular brass;
(b) Tubular ABS (acrylonitrile butadiene styrene) or PVC (polyvinyl chloride) produced and labeled as ASTM F-
409;
(c) Cast brass;
(d) Cast iron;
(e) Lead;
(f) Schedule 40 PVC; or
(g) Schedule 40 ABS.
(3) A tubular or schedule 40 PVC, or tubular or schedule 40 ABS p-trap shall be either the union-joint or solvent
welded type.
(4) A tubular brass trap shall be seventeen (17) gauge
(5) A tubular brass, tubular PVC, or tubular ABS trap shall not be installed below the finished floor serving a fixture.
(6) A trap shall have a full-bore, smooth interior waterway.
(7) The threads in a cast brass or cast iron trap shall be tapped out of solid metal.
(8) A lead trap shall be extra heavy.
Section 2. Prohibited Traps. A trap which depends upon the action of a movable part or concealed interior
partition for its seal shall not be used.
Section 3. Required Traps. (1) A fixture shall be separately trapped by a water-seal trap placed as near as
possible to the fixture but not to exceed ten (10) inches from the bottom of the fixture to the dip of the seal.
(2) Waste from a bathtub or other fixture shall not discharge into a water closet bend.
(3) A fixture shall not be double trapped.
Section 4. Water Seal. A fixture trap shall have a water seal not less than two (2) inches nor more than four (4)
inches.
Section 5. Trap Clean-outs. A trap clean-out shall be optional.
Section 6. Trap Levels and Protection. A trap shall be set true with respect to its water seal and shall be
protected from frost and evaporation. Trap primers shall be required on all floor drains and open receptacles in
commercial mechanical/boiler rooms and on open receptacles that receive the discharge from a temperature and
pressure relief device discharge only.
Section 7. Pipe Clean-outs. (1) The bodies of clean-out ferrules shall be made in a standard pipe size,
conforming in thickness to that of the pipe and fittings and shall not extend less than one-quarter (1/4) inch above
the hubs in which they are placed.
(2) The clean-out cap or plug shall be yellow-brass, PVC, or ABS not less than one-eighth (1/8) inch thick and
shall have a raised nut or recessed pocket for removal.
Section 8. Required Pipe Clean-outs. (1) In a building served by a stack over forty-five (45) feet in height, a
clean-out shall be provided at the base of each vertical waste or soil stack.
(2) There shall be at least one (1) clean-out in the building drain with a full-size branch inside the wall or outside
the building at a point not to exceed two (2) feet from the foundation wall. This clean-out shall be a two (2)
directional fitting or a combination of sanitary tees or tee wyes to allow cleaning in both directions.
(3) If located outside the building, the clean-out shall be extended to the finished grade for accessibility.
(4) A clean-out shall be of the same nominal size as the pipe it serves up to four (4) inches and shall not be less
than four (4) inches for larger pipe.
78
(5) A clean-out installed on a four (4) inch sewer shall be a two (2) directional fitting or a combination of sanitary
tees or tee wyes to allow cleaning in both directions.
Section 9. Manholes. An underground clean-out in a building shall be:
(1) Flush with the floor or wall; or
(2) Accessible by a manhole.
Section 10. Clean-outs (Equivalents). A floor or wall connection of a fixture shall be regarded as a clean-out,
except such fixtures shall not be regarded as a clean-out where the house drain enters a building.
Section 11. Grease Traps. (1) If a grease trap is installed, it shall be:
(a) Placed as near to the fixture it serves as practical; and
(b) Approved by the office.
(2) A grease trap used inside a building shall:
(a) Have a sealed cover; and
(b) Be properly vented.
(3) A grease trap shall be installed for a restaurant, food service establishment or other business establishment
as required by municipal ordinance.
(4) If a food establishment uses a private sewage system, a grease trap shall be installed as required by 902 KAR
10:085.
Section 12. Sand Traps. A sand trap shall be: (1) readily accessible; and
(2) Shall serve the purpose intended.
Section 13. Basement Floor Drains. (1) A basement floor drain shall:
(a) Connect to a trap;
(b) Be readily accessible for cleaning; and
(c) Be of sufficient size to serve the purpose intended.
(2) If a drain is subject to back flow or back pressure, the drain shall be equipped with a backwater valve that
complies with Section 14 of this administrative regulation
Section 14. Back Water Valves. A back water valve shall be:
(1) Made of noncorrosive material; and
(2) Constructed to insure a positive mechanical seal except if discharging waste.
Section 15. Residential Utility Room Floor Drains. A two (2) inch floor drain with an individual waste and vent
may be installed in a residential utility room.
Section 16. Directional Flow Fittings and Continuous-waste. A kitchen sink unit or fixture with more than one
(1) unit may be connected with a continuous-waste, if a directional flow fitting is used. Continuous-waste shall be
either seventeen (17) gauge tubular brass or schedule 40 ABS or PVC or tubular ABS or PVC material. (Recodified
from 401 KAR 1:080, 7-5-78; Am. 6 Ky.R. 138; eff. 11-7-79; 12 Ky.R. 47; eff. 8-13-85; 16 Ky.R. 1277; eff. 1-25-
90; 19 Ky.R. 1195; 1559; eff. 1-4-93; 22 Ky.R. 116; eff. 9-7-95; 26 Ky.R. 217; 616; eff. 9-16-99; 30 Ky.R. 1605;
eff. 2-16-2004; 30 Ky.R. 2397; 31 Ky.R. 91; eff. 8-6-04; 33 Ky.R. 3264; 4173; eff. 7-6-07.)
79
815 KAR 20:120. Water supply and distribution.
RELATES TO: KRS 318.010, 318.130, 318.150, 318.165, 318.200
STATUTORY AUTHORITY: KRS 198B.040(10), 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department, after review by
the Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate an administrative
regulation establishing the Kentucky State Plumbing Code regulating plumbing, including the methods and
materials that may be used in Kentucky. This administrative regulation establishes the types of piping and pipe
sizes required for a potable water supply system and the methods to be used to protect and control the water
supply system and requires the manufacturer's specification number of the material accepted in those installations
to be identified and published.
Section 1. Definitions.
(1) "ASSE" means the American Society of Sanitary Engineers.
(2) "ASTM" means the American Society for Testing Materials.
(3) "Critical level" or "CL" means the level to which the vacuum breaker may be submerged before backflow will
occur, and if the CL marking is not shown on the vacuum breaker, the bottom of the device shall be taken as the
CL.
(4) "DWV" means drain, waste and vent piping.
(5) "NSF" means the National Sanitation Foundation.
(6) "SDR" means standard dimensional ratio.
Section 2. Quality. (1) The bacteriological and chemical quality of the water supply shall comply with the
administrative regulations of the office and the Division of Water. Toxic material shall be kept out of a potable
water system.
(a) The pipe conveying, and each surface in contact with, potable water shall be constructed of nontoxic material.
(b) A chemical or other substance that could produce either a toxic condition, taste, odor, or discoloration in a
potable water system shall not be introduced into, or used in, the system.
(c) The interior surface of a potable water tank shall not be lined, painted, or repaired with a material that will affect
the taste, odor, color, or portability of the water supply if the tank is placed in, or returned to, service.
(2) Potable water shall be accessible to a plumbing fixture that supplies water for drinking, bathing, culinary use
or the processing of a medicinal, pharmaceutical, or food product.
(3) The potable water supply system shall be designed, installed, and maintained to prevent contamination from
a non-potable liquid, solid, or gas being introduced into the potable water supply through a cross connection or
other piping connection to the system.
(4) A cross connection shall meet the requirements of this administrative regulation.
(5) A cross connection between a private water supply and a public water supply shall not be made.
(6) Closed water systems, protection from excess pressure.
(a) If a single check valve is installed in a water system, a thermal expansion tank sized in accordance with
manufacturer’s instructions shall be installed in the cold water supply located near the water heater.
(b) If a backflow preventer is installed in a water system, a properly sized thermal expansion tank or other pressure
relief device listed in 815 KAR 20:020 shall be installed in the water distribution system.
(c) If a pressure reducing valve not equipped with a bypass is installed in the cold water supply line to a water
heater, a thermal expansion tank shall be installed in the cold water line near the water heater.
(7) Backflow and back siphonage protection. Protection against backflow shall be provided as required in
paragraphs (a) through (l) of this subsection in order of degree of protection provided. Backflow shall include both
back pressure and back siphonage.
(a) An air gap shall provide the best level of protection in all backflow situations. The minimum required air gap
shall be determined as follows:
1. How measured. The minimum required air gap shall be measured vertically from the lowest end of a potable
water outlet to the flood rim or line of the fixture or receptacle into which it discharges.
2. Size. The minimum required air gap shall be:
a. Twice the effective opening of a potable water outlet; or
b. If the outlet is a distance less than three (3) times the effective opening away from a wall or similar vertical
surface, three (3) times the effective opening of the outlet.
1. The minimum required air gap shall not be less than shown in the following table - Minimum Air Gaps for
Plumbing Fixtures.
80
MINIMUM AIR GAPS FOR PLUMBING FIXTURES
Fixture Minimum Air Gap
When not affected by
near wall (inches)
When affected by near wall
(inches)
Lavatories and other fixtures with effective
opening not greater than 1/2 inch diameter
1 1 1/2
Sink, laundry trays, gooseneck bath faucets
and other fixtures with effective openings not
greater than 3/4 inch diameter
1 1/2 2 1/4
Over rim bath fillers and other fixtures with
effective openings not greater than 1 inch
diameter
2 3
Drinking water fountains - single orifice not
greater than 7/16 (0.437) inch diameter or
multiple orifices having total area of 0.150
square inches (area of circle 7/16 inch
diameter)
1 1 1/2
Effective openings greater than 1 inch 2 x diameter of effective
opening
3 x diameter of effective
opening
NOTE 1. Side walls, ribs, or similar obstructions do not affect air gaps if spaced from the inside edge of the spout
opening a distance greater than three (3) times the diameter of the effective opening for a single wall, or a distance
greater than four (4) times the diameter of the effective opening for two (2) intersecting walls.
NOTE 2. Vertical walls, ribs, or similar obstructions extending from the water surface to or above the horizontal
plane of the spout opening require a greater air gap if spaced closer to the nearest inside edge of spout opening
than specified in NOTE 1 above. The effect of three (3) or more vertical walls or ribs has not been determined. In
this case, the air gap shall be measured from the top of the wall.
(b) A reduced pressure principle back pressure backflow preventer. A reduced pressure principle back pressure
backflow preventer shall provide the best mechanical protection against backflow available and shall be
considered equivalent to an air gap.
(c) Double check valve assembly: applicable to low level of hazard back pressure backflow conditions. This device
shall be a manufactured assembly consisting of two (2) independently acting check valves and including a shutoff
valve at each end, and petcock and test gauge for testing the water tightness of each check valve.
(d) Pressure type vacuum breaker: applicable to back siphonage conditions.
(e) Atmospheric type vacuum breaker: applicable to back siphonage conditions. If applicable, an atmospheric type
vacuum breaker shall be installed after the last cutoff valve on the water line. This device may operate under
normal atmospheric pressure if the critical level (CL) is installed at the required height in accordance with the table
in this paragraph:
CRITICAL LEVEL (CL) SETTINGS FOR ATMOSPHERIC TYPE VACUUM BREAKERS
Fixture or Equipment Method of Installation
Aspirators, ejectors, and
showers
CL at least 6 in. above flood level of receptacle
Bidets CL at least 6 in. above flood level of receptacle
Cup beverage vending machines
CL at least 12 in. above flood level of machine
On models without built-in vacuum breakers:
Dental units CL at least 6 in. above flood level rim of bowl.
Dishwashing machines CL at least 6 in. above flood level of machine
Flushometers (closet & urinal) CL at least 6 in. above top of fixture supplied
Garbage can cleaning machines CL at least 6 in. above flood level of machine
Hose bibs (sinks or receptacles) CL at least 6 in. above flood level of receptacle served
Hose outlets CL at least 6 in. above highest point on hose line
Laundry machines CL at least 6 in. above flood level of machine
Lawn sprinklers CL at least 12 in. above highest sprinkler or discharge outlet
Steam tables CL at least 12 in. above flood level
Tanks & vats CL at least 6 in. above flood level rim or line
81
(f) Barometric loop: applicable to back siphonage conditions. The use of a barometric loop shall not be acceptable
as the primary back siphonage preventer.
(g) Location of backflow and back siphonage preventers.
1. A backflow and back siphonage preventer shall be in an accessible location, and accessible from within the
same room as the fixture or connection it protects.
2. A backflow device may be installed in a utility or service space.
3. A device or air gap shall not be installed in a location subject to flooding or freezing.
(h) Inspection of devices.
1. A periodic inspection shall be made of each backflow and back siphonage preventer to determine if it is in
proper working condition.
2. A reduced pressure principle back pressure backflow preventer shall be tested on at least an annual basis.
3. Records shall be kept on each inspection.
(i) Approval of devices.
1. Before a device for the prevention of backflow or back siphonage is installed, it shall be identified as meeting
the applicable specifications as listed in the application chart included in paragraph (k) of this subsection.
2. A device installed in a building potable water supply distribution system for protection against backflow shall be
maintained in good working condition by the person responsible for the maintenance of the system.
(j) Degree of hazard. The protection required at an outlet or connection shall be determined based on the degree
of hazard posed by that outlet or connection as follows:
1. Severe hazard, if there is potential for contamination by a toxic substance or disease-causing organism;
2. Moderate hazard, if there is potential for contamination by a nontoxic but objectionable substance; or
3. Minor hazard, if there is potential for contamination by a generally nontoxic, non-objectionable substance, but
which may cause the consumer to question the quality of water.
(k) Minimum acceptable protection. An opening or outlet shall be protected by an air gap between the opening
and flood level rim if possible. The acceptable protection for various types of outlets or connections shall be as
shown in the tables in this paragraph:
82
APPLICATION TABLE
TYPE AND
PRESSURE
DESCRIPTION INSTALLED AT EXAMPLES OF
INSTALLATIONS
APPLICABLE
SPECIFICATIONS
Reduced pressure
principle backflow
preventer for high
hazard cross
connections
Two independent
check valves with
intermediate relief
valve. Supplied with
shut-off valves and
ball-type test cocks.
All cross connections
subject to backpressure or
back siphonage if there is a
high potential health hazard
from contamination.
Continuous pressure.
Main supply lines,
commercial boilers, cooling
towers, hospital
equipment, processing
tanks, laboratory
equipment, waste
digesters, car wash,
sewage treatment, lawn
sprinklers
ASSE No. 1013
AWWA C506
FCCCHR of U.S.C.
CSA B.64.4
Sizes 3/4" - 10"
(A) Double check
valve assembly for
low hazard cross
connections
Two independent
check valves.
Supplied with
shutoff valves and
ball type test cocks.
All cross connections
subject to back pressure if
there is a low potential
health hazard or nuisance.
Continuous pressure.
Main supply lines, food
cookers, tanks and vats,
commercial pools
NON
TOXIC
ASSE No.
1015
AWWA C506
FCCCHR of
U.S.C.
CSA B.64.5
Sizes 3/4" - 10"
(B) Dual check valve
backflow preventer
for low hazard
applications
Two independent
check valves.
Checks are re-
movable for testing
Cross connections if there
is a low potential health
hazard and moderate flow
requirements.
Post ground hydrants ASSE No.
1024
Sizes 3/4" & 1"
(A) Backflow
preventer with
intermediate
atmospheric vent for
moderate hazard
cross connections in
small pipe sizes
Two independent
check valves with
intermediate
vacuum breaker and
relief valve.
Cross connections subject
to back pressure or back
siphonage if there is a
moderate health hazard.
Continuous pressure.
Boilers (small), cooling
towers (small), dairy
equipment residential
ASSE No. 1012
CSA B.64.3
Sizes 1/2" & 3/4"
(B) Backflow
preventer for
carbonated
beverage machine
Two independent
check valves with a
vent to atmosphere
On potable water
distribution lines serving
beverage-dispensing
equipment to prevent
backflow of carbon dioxide
gas and carbonated water
into the water supply
system.
Postmix carbonated
beverage machine
ASSE 1022
(C) Laboratory
faucet and double
check valve with
intermediate
vacuum breaker in
small pipe sizes for
moderate to low
hazard
Two independent
check valves with
intermediate
vacuum breaker and
relief vent.
Cross connection subject to
back pressure or back
siphonage if there is a
moderate to low health
hazard.
Laboratory faucets and
pipe lines, barber shop and
beauty parlor sinks
ASSE No. 1035
(N-LF9)
(A) Atmospheric
vacuum breakers for
moderate to high
hazard cross
connections
Single float and disc
with large
atmospheric port.
Cross connections not
subject to backpressure or
continuous pressure. Install
at least 6" above fixture rim.
Protection against back
siphonage only.
Process tanks,
dishwashers, soap
dispensers, washing
machines
ASSE No. 1001
ANSI.A112.1.1
CSA B.64.1.1
FCCCHR of U.S.C.
Sizes 1/4" - 3"
(B) Antisiphon
pressure breakers
for moderate to high
hazard cross
connections
Spring loaded single
float and disc with
independent 1st
check. Supplied with
shutoff valves and
ball type test cocks.
This valve is designed for
installation in a continuous
pressure potable water
supply system 12" above
the overflow level of the
system being supplied.
Protection against back
siphonage only.
Laboratory equipment,
cooling towers, commercial
laundry machines,
swimming pools,
commercial plating tanks,
large toilet total & urinal
facilities, degreasers,
photo tanks, livestock
water systems, lawn
sprinklers
ASSE No. 1020
CSA B.64.1.2
FCCCHR of U.S.C.
Sizes 1/2" - 2"
(C) Hose connection
vacuum breakers for
residential and
industrial hose
supply outlets
Single check with
atmospheric
vacuum breaker
vent.
Install directly on hose bibs,
service sinks and wall
hydrants. Not for
continuous pressure.
Hose bibs, service sinks,
hydrants
ASSE No. 1011
CSA B.64.2
Size 3/4" Hose
83
CROSS CONNECTIONS, DEGREE OF HAZARD AND ACCEPTABLE
PROTECTION FOR VARIOUS PLUMBING OUTLETS AND CONNECTIONS
Degree of
Hazard
Acceptable Protection
Type of Connection
Backflow Backsiphonage
Severe
Moderat
e
Minor
Air Gap
Reduced
Pressure
Device
Double Check
Valve
Assembly
Pressure
Type
Vacuum
Breaker
Atmospheri
c Type
Vacuum
Breaker
I. Connections subject to back
pressure from:
A. Pumps, tanks, and lines
handling:
1. Toxic substance X
X X
2. Nontoxic substance
X
X X X
B. Boilers
1. With chemical additives X
X X
2. Without chemical additives
X
X X X
C. Gravity due to obvious site
conditions subject to:
1. Contamination by toxic
substances
X
X X
2. Contamination by nontoxic
substances
X
X X X
II. Water outlets and connections not subject to back pressure:
A. Connection to sewer or
sewage pump
X
X
B. Outlet to receptacles
containing toxic substances
X
X X
X X
C. Outlet to receptacles
containing nontoxic substances
X
X X X X X
D. Outlet into domestic water
tanks
X EACH CASE TREATED SEPARATELY
E. Flush valve toilets X
X X
X X
F. Flush valve urinals
X
X X
X X
G. Outlets with hose attachments
subject to contamination from:
1. Toxic substance X
X X
X X
2. Nontoxic substance
X
X X X X
H. Outlets to recirculating cooling tower
1. With chemical additives X
X X
2. Without chemical additives
X
X X X
(l) Protection of potable water system. A potable water opening, outlet, or connection, except one (1) that serves
a residential unit, shall be protected against backflow in accordance with paragraphs (a) through (k) of this
subsection.
Section 3. Water Required. (1) A building equipped with a plumbing fixture and used for habitation or occupancy
shall be equipped with a supply of potable water.
(2) In a building used as a residence or a building in which people assemble or are employed, both hot and cold
water shall be supplied.
Section 4. Water Service. (1) The water service piping to a building shall:
(a) Not be less than three-fourths (3/4) inch nominal pipe size; and
(b) Be of sufficient size to permit a continuous and ample flow of water to each fixture in the building.
(2) Except as provided in this subsection, the underground water service pipe from the main or water supply
system to the water distribution system shall not be less than five (5) feet apart horizontally from the house sewer
and shall be separated by undisturbed or compacted earth. The pipe may be placed in the same trench if:
(a) The bottom of the water service pipe at all points is at least eighteen (18) inches above the top of the sewer at
its highest point;
84
(b) The water service pipe is placed on a solid shelf excavated at one (1) side of the common trench; and
(c) The number of joints in the water service pipe is kept to a minimum.
Section 5. Distribution. (1) The water supply shall be distributed through a piping system entirely independent
of another piping system.
(2) Piping which has been used for a purpose other than conveying potable water shall not be used for conveying
potable water.
(3) Non-potable water may be used for flushing a water closet or urinal, if the water is piped in an independent
system.
(a) If a dual water distribution system is used, the non-potable water supply shall be durably and adequately
identified.
(b)1. An outlet on the non-potable water distribution system used for a drinking or domestic purpose shall be
permanently posted: DANGER - UNSAFE WATER.
2. Each branch, fitting, or valve shall be identified by the phrase - "NONPOTABLE WATER" either by a sign or
brass tag that shall be permanently affixed to the pipe, fitting, or valve.
3. The identification marking shall not be concealed and shall be maintained by the owner.
(4) A backflow device or cross-connection control device shall be approved by the department.
(5) A combination stop and waste valve, cock, or hydrant shall not be installed in the underground water
distribution system without the installation of an approved backflow preventer.
(6) A private water supply shall not be interconnected with a public water supply.
(7) Water used for cooling of equipment or in another process shall not be returned to the potable water system.
The water shall be discharged into a drainage system through an air gap, or used for a nonpotable purpose as
referenced in this section.
(8) Hose connections other than those intended for clothes washing machines, frost proof burial hydrants, and
water heater drain valves shall be equipped with a vacuum breaker ASSE 1011 for areas not subject to freezing
and a vacuum breaker ASSE 1019 for areas subject to freezing.
Section 6. Water Supply to Fixtures. (1) A plumbing fixture shall be provided with a sufficient supply of water
for flushing to keep them in a sanitary condition.
(2) A water closet or pedestal urinal shall be flushed by means of an approved tank or flush valve.
(3) The tank or valves shall furnish at least a sufficient amount of water to thoroughly cleanse the surface area of
a water closet, urinal, or similar fixture.
(4) If a water closet, urinal, or similar fixture is supplied directly from the water supply system through a flushometer
or other valve, the valve shall be set above the fixture to prevent the possibility of polluting the potable water
supply by back siphonage.
(5) The fixture shall have a vacuum breaker.
(6) A plumbing fixture, device or appurtenance shall be installed in a manner that shall prevent a possibility of a
cross connection between the potable water supply system, drainage system, or other water system.
Section 7. Connections to Boilers. (1) A potable water connection to a boiler feed water system in which a boiler
water conditioning chemical is introduced shall be made through an air gap, or provided with a reduced pressure
principle backflow preventer located in the potable water line before the point where a chemical is introduced.
(2) A boiler shall be equipped with a check valve in the cold water supply to the boiler.
Section 8. Water Supply to Drinking Fountains. The orifice of a drinking fountain shall be provided with a
protective cowl to prevent contamination of the potable water supply system.
Section 9. Sizing of Water Supply Piping. (1)(a) The minimum size water service from the property line to the
water heater shall be three-fourths (3/4) inch.
(b)The hot and cold water piping shall extend three-fourths (3/4) inch in size to the first fixture branch.
(c) More than three (3), one-half (1/2) inch fixture branches shall not be supplied from a one-half (1/2) inch pipe.
(2)(a) The schedule in this subsection shall be used for sizing the water supply piping to a fixture.
(b) The branch pipe to a fixture shall terminate not more than thirty (30) inches from the point of connection to the
fixture and shall be brought to the floor or wall adjacent to the fixture.
(c) A concealed water branch pipe shall not be less than one-half (1/2) inch nominal pipe size.
85
Fixture Branches Nominal Pipe Size (Inches)
Bath tubs 1/2
Combination sink and tray 1/2
Cuspidor 1/2
Drinking fountain 1/2
Dishwasher (domestic) 1/2
Kitchen sink (res.) 1/2
Kitchen sink (com.) 1/2 or 3/4 as required
Lavatory 1/2
Laundry tray 1/2
Sinks (service, slop) 1/2
Sinks flushing rim 3/4
Urinal (flush tank) 1/2
Urinal (direct flush type) 1/2 or 3/4 as required
Water closet (tank type) 1/2
Water closet (flushometer type) 1
Hot water boilers 3/4
Hose bibs 1/2
Wall hydrant 1/2
Domestic clothes washer 1/2
Shower (single head) 3/4
(3) Water hammer. In a building supply system in which a device or appurtenance is installed utilizing a quick
acting valve that causes noise due to water hammer, a protective device, including an air chamber or approved
mechanical shock absorber, shall be installed as close as possible to the quick acting valve causing the water
hammer.
(a) If a mechanical shock absorber is installed, the absorber shall be in an accessible place.
(b) If a mechanical device is used, the manufacturer's specifications shall be followed as to location and method
of installation.
Section 10. Water Supply Pipes and Fittings, Materials. (1) Water supply piping for a potable water system
shall be as follows:
(a) Galvanized wrought iron;
(b) Galvanized steel;
(c) Brass;
(d)Types K, L, and M copper;
(e) Cast iron;
(f) Types R-K, R-L, and R-M brass tubing;
(g) Fusion welded copper tubing produced and labeled as ASTM B-447-2002 and ASTM B-251;
(h) DWV welded brass tubing produced and labeled as ASTM B587;
(i) Seamless stainless steel tubing, Grade H, produced and labeled as ASTM A268/268M;
(j) Filament-wound reinforced thermosetting resin pipe produced and labeled as ASTM D-2996 (red thread for
cold water use and silver and green thread for hot and cold);
(k) Polyethylene (PE) plastic pipe produced and labeled as ASTM D2239 or ASTM F-714;
(l) Cross-linked polyethylene (PEX) pipe produced and labeled as ASTM F-876 for cold water and ASTM F-877
for hot or cold water applications;
(m) Cross-linked Polyethylene/Aluminum/Cross-linked Polyethylene (Pex-Al-Pex) pipe produced and labeled as
ASTM F-1281;
(n) Polyethylene/Aluminum/Polyethylene (Pe-Al-Pe) pipe produced and labeled as ASTM F-1282;
(o) Copper tubing size PE produced and labeled as ASTM D-2737 for water service, if installed with compression
couplings;
(p) Polyvinyl chloride (PVC) plastic pipe produced and labeled as ASTM D1785;
(q) Chlorinated Polyvinyl chloride (CPVC) plastic pipe produced and labeled as ASTM D2846;
(r) Schedule 80 chlorinated polyvinyl chloride (CPVC) plastic pipe shall meet ASTM F441;
(s) Schedule 80 chlorinated polyvinyl chloride (CPVC) plastic solvent fittings shall meet ASTM F439;
(t) Schedule 80 chlorinated polyvinyl chloride (CPVC) plastic threaded fittings shall meet ASTM F437;
86
(u) Schedule 80 chlorinated polyvinyl chloride (CPVC) plastic pipe and fittings shall be installed using primer
meeting ASTM F656 and solvent cement meeting ASTM F493;
(v) Polyvinyl chloride (PVC) standard dimensional ratio (SDR) 21 and (SDR) 26 pipe produced and labeled as
ASTM D-2241-05;
(w) Fusion welded polypropylene pipe products measuring one-half (1/2) inch to eighteen (18) inches in diameter
which meet NSF Standards 61 and 14, and ASTM F2389, shall be approved. These pipe products shall be tested
for compliance with the manufacturer’s installation instructions;
(x) Fusion welded high density polyethylene pipe products which meet NSF Standards 61 and 14, and ASTM
F3035 and F714, shall be approved for underground use. These pipe products shall be tested for compliance with
the manufacturer’s installation instructions;
(y) Push-fit fitting systems which meet the ASSE Standard 1061. Except as established in 815 KAR 20:020, these
systems are approved for above-ground use only using pipe sizes up to two (2) inches; or
(z) PE-RT Piping (Polyethylene of Raised Temperature) meeting ASTM F2769.
(2) A plastic pipe or fitting shall bear the NSF seal of approval.
(3) Polybutylene pipe utilizing an insert fitting of brass or copper shall use a copper clamping ring.
(4) A polybutylene hot and cold water connector to a lavatory, sink, or water closet shall be produced and labeled
as ASTM D3309, and polybutylene plastic pipe shall be produced and labeled as ASTM 2662 for a cold water
application.
(5) A fitting shall be brass, copper, approved plastic, galvanized cast iron, or galvanized malleable iron. Piping or
a fitting that has been used for another purpose shall not be used for the water distribution system.
(6) Each joint in the water supply system shall be made of a screw, solder, or plastic joint. A cast iron water pipe
joint may be caulked, screwed, or machine drawn.
(7) If Type M copper pipe, Type R-M brass tubing, standard high frequency welded tubing or stainless steel tubing
is placed within a concrete floor or passes through a concrete floor, it shall be wrapped with an approved material
to permit expansion or contraction.
(8) Polyethylene or PVC shall not be used below ground under a house or building. If a chlorinated polyvinyl
chloride (CPVC) joint or connection is installed below ground under a house or building, the water distribution
system shall be tested to at least 100 pounds per square inch before backfilling. The applicable requirements of
815 KAR 20:060 and 815 KAR 20:073 shall be met.
(9) Joints between copper tubing and galvanized steel pipe. The joint between ferrous piping and copper or
copper-alloy piping shall be made with a dielectric fitting or other insulating fitting to prevent electrolysis.
Section 11. Temperature and Pressure Control Devices for Shower Installations. A temperature or pressure
balance device to prevent a sudden unanticipated change in water temperature shall be installed to serve each
shower compartment and shower-bath combination.
Section 12. Water Supply Control. (1) A main shutoff valve shall be provided near the curb, in or near the meter
box or property line on the water service pipe. In addition, a main supply control valve shall be placed inside a
foundation wall. The main supply control valve shall be a full port valve and be accessible from within the occupied
space and provided with a drip or drain valve. A pit or similar type installation shall not be used for a potable water
supply shutoff valve.
(2) A pressure or gravity tank shall have its supply line valved at or near its source.
(3) A family unit in a two (2) family or multifamily dwelling shall have the unit controlled by an arrangement of
shutoff valves which will permit the unit to be shutoff without interfering with the cold water supply to another family
unit or portion of the building.
(4) In a building other than a dwelling, a shutoff valve shall be installed to permit the water supply to the equipment
to be isolated without interference with the supply to other equipment.
(5) A fixture or group of bath fixtures shall be valved and a lawn sprinkler opening shall be valved. In residential
construction, each fixture, except a bathtub or shower, shall be valved individually or as a group of fixtures.
(6) A group of fixtures or a fixture group shall include two (2) or more fixtures adjacent to or near each other in the
same room or back-to-back on a common wall.
(7) The cold water branch to a hot water storage tank or water heater shall be provided with a shutoff valve located
near the equipment and serving this equipment. In residential dwellings, the shutoff valve shall be placed within
three (3) feet of the water heater and be accessible from the accessible side of the water heater.
Section 13. Water Supply Protection. A concealed water pipe, storage tank, cistern, or other exposed pipe or
tank subject to freezing temperatures shall be protected against freezing. A water service shall be installed at
least thirty (30) inches in depth.
87
Section 14. Temperature and Pressure Relief Devices for Water Heaters. (1) A temperature and pressure
relief device shall:
(a) Be installed on each water heater on the hot water side not more than three (3) inches from the top of the
heater;
(b) If a marked opening is provided on the water heater by the manufacturer for the temperature and pressure
relief device, be installed according to the manufacturer's recommendation; and
(c) Be of a type approved by the office in accordance with this administrative regulation and 815 KAR 20:020.
(2)(a) If a water heater is installed in a location that has a floor drain, the discharge from the relief device shall be
piped to within two (2) inches of the floor.
(b) If a water heater is installed in a location that does not have a floor drain, the discharge from the relief device
shall be piped to the outside of the building with an ell turned down and piped to within four (4) inches of the
surface of the ground.
(c) The relief device may discharge through an air gap to a sump basin, service sink, open receptacle or other
point of discharge in which equivalent safety shall be provided as approved by the Division of Plumbing.
(3) A relief device shall be installed on a pneumatic water system.
Section 15. Protection of a Private Water Supply or Source. A private water supply or source shall be protected
from pollution. Approval shall be obtained from the Division of Plumbing prior to using the private water supply or
source.
Section 16. Domestic Solar Water Heaters. A domestic solar water heater may have a "single wall heat
exchanger" if the following conditions are met:
(1) The solar panel and the water heater exchanger use a nontoxic liquid such as propylene glycol or an
equivalent;
(2) The heat exchanger is pretested by the manufacturer to 450 pounds per square inch;
(3) The water heater has a warning label advising that a nontoxic heat exchanger fluid shall be used at all times;
and
(4) A pressure relief valve is installed at the highest point in the solar panel.
Section 17. Domestic Water Heater Preheating Device. (1) A domestic water heater preheating device may be
used and connected with the high pressure line from the compressor of a domestic home air conditioner or heat
pump water heater.
(2) Double wall heat-exchangers with two (2) separate thicknesses separating the heat exchange fluid (other than
potable water) from the potable water supply shall be provided.
(3) The water inlet to the heat exchange vessel shall be provided with a check valve. There shall be provided
adjacent to, and at the outlet side of the check valve, an approved pressure relief valve set to relieve at five (5)
pounds per square inch above the maximum water pressure at the point of installation, if the heat exchange units
contain more than twenty (20) pounds of refrigerants. This device shall be equipped with a temperature limit
control that would actuate a pump that would circulate hot water from the water heater through the preheater
device.
(4) Condensate drain water shall be piped in accordance to the State Plumbing Code and it shall not be permitted
to drain into crawl space, or into a sewer or vent stack, or be installed in an area subject to freezing. If a drain is
not available or if a drain is located above the vent, a condensate pump shall be utilized.
Section 18. Tanks and Vats below Rim Supply. A tank or vat with potable water supply below the rim shall be
subject to the following requirements:
(1) If a potable water outlet terminates below the rim of a tank or vat and the tank or vat has an overflow of diameter
not less than given in the table in this subsection, the overflow pipe shall be provided with an air gap as close to
the tank as possible;
Sizes of Overflow Pipes
for Water Supply Tanks
Maximum capacity of
water supply line to tank
Diameter of Overflow
Pipe (inches ID)
Maximum capacity of
water supply line to tank
Diameter of overflow
Pipe (inches ID)
0- 50 gpm 2 400- 700 gpm 5
50-150 gpm 2 1/2 700-1000 gpm 6
150-200 gpm 3 Over 1000 gpm 8
88
(2) The potable water outlet to the tank or vat shall terminate at a distance not less than one and one-half (1 1/2)
times the height to which water can rise in the tank above the top of the overflow. This level shall be established
at the maximum flow rate of the supply to the tank or vat, and with all outlets, except the air gap overflow outlet,
closed; and
(3) The distance from the outlet to the high water level shall be measured from the critical point of the potable
water supply outlet.
Section 19. Water Distribution for Fan Coil Units. (1) If a domestic water heater is used for heating purposes
through a fan coil medium, its temperature shall not exceed 140 degrees Fahrenheit.
(2) It shall utilize not less than three-fourths (3/4) inch piping and its run shall not exceed 140 feet between the
water heater and the heating unit.
(3) The applicable requirements established in 815 KAR 20:070 shall be met.
Section 20. Fire Protection Systems. Except if installing an NFPA 13D fire protection system in a one (1) or two
(2) family dwelling, a fire protection system using water from the potable water distribution system shall be
equipped with two (2) check valves, one (1) of which may be an alarm check valve.
Section 21. Water Distribution and Connections to Mobile Homes. (1) An adequate and safe water supply
shall be provided to each mobile home.
(2) All materials, including the pipe or fitting used for a connection, shall conform to the State Plumbing Code.
(3) An individual water connection shall be provided at an appropriate location for each mobile home space.
(a) The connection shall consist of a riser terminating at least four (4) inches above the ground with two and three-
fourths (2 3/4) inch valve outlets with screw connection, one (1) for the mobile home water system and the other
for lawn watering and fire control.
(b) The ground surface around the riser pipe shall be graded to divert surface drainage.
(c) The riser pipe shall be encased in an eight (8) inch vitrified clay pipe or an equivalent with the intervening
space filled with an insulating material to protect it from freezing.
(d) An insulated cover shall be provided which shall encase both valve outlets but not prevent connection to the
mobile home during freezing weather.
(e) A shutoff valve may be placed below the frost depth on the water service line, but this valve shall not be a
stop-and-waste cock.
Section 22. Conservation of water shall comply with the standards established in 815 KAR 20:070. (1 Ky.R.
485; eff. 3-12-1975; Am. 2 Ky.R. 457; eff. 4-14-1976; 3 Ky.R. 450; eff. 1-5-1977; 4 Ky.R. 190; 425; eff. 5-3-1978;
Recodified from 401 KAR 1:090, 7-5-1978; 5 Ky.R. 163; eff. 10-4-1978; 7 Ky.R. 513; eff. 1-7-1981; 647; 849; eff.
6-3-1981; 9 Ky.R. 49; eff. 8-11-1982; 1242; eff. 6-1-1983; 10 Ky.R. 1013; eff. 3-31-1984; 11 Ky.R. 74; eff. 8-7-
1984; 802; 1259; eff. 2-12-1985; 12 Ky.R. 436; eff. 11-12-1985; 1667; eff. 5-6-1986; 13 Ky.R. 1656; eff. 4-14-
1987; 14 Ky.R. 636; eff. 11-6-1987; 1135; eff. 1-4-1988; 15 Ky.R. 605; 974; eff. 9-28-1988; 16 Ky.R. 904; eff. 1-
12-1990; 2767; 17 Ky.R. 1100; eff. 8-22-1990; 2269; eff. 3-13-1991; 18 Ky.R. 2894; eff. 5-1-1992; 19 Ky.R. 816;
eff. 11-9-1992; 2113; eff. 7-12-1993; 20 Ky.R. 3119; eff. 7-7-1994; 21 Ky.R. 1967; eff. 3-22-1993; 22 Ky.R. 800;
eff. 12-7-1995; 23 Ky.R. 1757; 2739; eff. 1-9-1997; 24 Ky.R. 2465; eff. 7-13-1998; 25 Ky.R. 1187; eff. 2-18-1999;
2961; 26 Ky.R. 388; eff. 8-16-1999; 27 Ky.R. 2244; 2801; eff. 3-22-2001; 29 Ky.R. 1392; 1812; eff. 1-16-2003; 32
Ky.R. 369; 660; eff. 11-4-2005; 2371; 33 Ky.R. 411; eff. 9-1-2006; 3266; 4174; eff. 7-6-2007; 35 Ky.R. 2601; 36
Ky.R. 93; eff. 7-29-2009; 39 Ky.R. 2210; eff. 8-2-2013; 43 Ky.R. 466, 689; eff. 11-16-2016.)
89
815 KAR 20:130. House sewers and storm water piping; methods of installation.
RELATES TO: KRS 318.010, 318.015, 318.130, 318.150, 310.200
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department to promulgate an
administrative regulation establishing the Kentucky State Plumbing Code to regulate plumbing, including the
methods and materials that may be used in Kentucky for the construction of house sewers and storm water piping.
This administrative regulation establishes the materials and methods of installation that may be used in the
construction of house sewers or storm water piping.
Section 1. Independent System. (1) The drainage and plumbing system of a new building and of a new work
installed in an existing building shall be separate and independent of other buildings except as otherwise
established in this administrative regulation.
(2) A building shall have an independent connection with either a public or private sewer or sewer system.
Section 2. Exceptions. (1)(a) If a building stands in the rear of other buildings or on an interior lot and a sewer
connection cannot be made available to the rear building through an adjoining alley, court, yard, or driveway, the
sewer from the front building may be extended to the rear building and it shall be considered as one (1) sewer.
(b) The exception established in this subsection shall not apply to corner lots if a sewer connection is available
from the street or alley or to a new or existing building that abuts a street or alley.
(2) A building sewer may serve additional buildings and still be considered as one (1) sewer if the additional
buildings are:
(a) Used in conjunction with the primary building;
(b) Contained within the same deed as the primary building; and
(c) Restricted within the deed from being sold separately from the primary building.
Section 3. Connection with Private Sewage Disposal System. If a sewer is not available, the house drain from
a building shall connect with an approved private sewage disposal system.
Section 4. Excavations. An excavation made for the installation of a house sewer shall be open trench work,
and the trenches shall be kept open until the piping has been inspected, tested, and approved.
Section 5. Depth of Sewer at the Property Line. (1) The sewer at the property line shall be at a sufficient depth
to properly serve a plumbing connection installed in the basement of a building.
(2)(a) A house sewer shall be laid on a grade of not less than one-eighth (1/8) inch nor more than one-fourth (1/4)
inch per foot.
(b) A sewer shall have at least an eighteen (18) inch cover.
(c) Sewer piping installed under property subject to vehicular traffic (such as a driveway, parking lot, or similar
location) shall have at least a twenty-four (24) inch cover unless constructed of cast iron piping. If less than a
twenty-four (24) inch cover is available, sewer piping shall be encased in a minimum of six (6) inches of concrete
on each side and the top.
(d) A sewer shall be backfilled by hand and tamped six (6) inches above the piping or filled with six (6) inches
grillage above the piping.
(e) Each joint in cast iron and vitrified clay pipe shall be constructed to comply with 815 KAR 20:060, Sections 4
and 5.
Section 6. New House Sewer Connections. A house sewer installed where a private sewerage system has
been discarded may connect to the house drain if the existing plumbing system meets the State Plumbing Code.
90
Section 7. Materials for House Sewers. A house sewer or combined sewer shall be made of:
(1) Extra heavy cast iron pipe;
(2) Service weight cast iron;
(3) Vitrified clay;
(4) Concrete;
(5) Coextruded composite PVC pipe produced and labeled ASTM F-1488;
(6) PVC or ABS plastic pipe Schedules 40 and 80;
(7) Cellular core PVC produced and labeled as ASTM F-891;
(8) Cellular core ABS produced and labeled as ASTM 628 or ASTM F-1488;
(9) Truss pipe;
(10) Extra heavy SDR 35 pipe;
(11) Type PS 46, PVC in sizes four (4) inches through fifteen (15) inches produced and labeled as ASTM F789;
(12) PVC ribbed pipe produced and labeled as ASTM F794; or
(13) Polyethylene pipe produced and labeled as ASTM F-714.
Section 8. Material for Storm Sewers Inside Buildings. (1) A storm sewer inside a building extending to a point
two (2) feet outside a building in sizes eight (8) inches and smaller shall be made of:
(a) Cast iron pipe;
(b) Aluminum; or
(c) Schedule 40 ABS or PVC DWV pipe or PVC pipe produced and labeled as ASTM F-1488.
(2) A storm sewer in a size of ten (10) inches or larger shall be made of:
(a) Cast iron;
(b) Aluminum;
(c) Schedule 40 ABS or PVC DWV pipe;
(d) SDR 35;
(e) Vitrified clay or concrete conforming to appropriate commercial specifications with approved joints; or
(f) Polyethylene pipe produced and labeled as ASTM F-714.
(3) Primary and secondary roof drains shall comply with the requirements established in this subsection.
(a)1. Roof drains shall have strainers extending not less than four (4) inches above the surface of the roof
immediately adjacent to the roof drain.
2. Strainers shall have an available area not less than one and one-half (1 1/2) times the area of the conductor or
leader to which the drain is connected.
(b) Roof drain strainers for use on sun decks, parking decks, and similar areas that are normally services and
maintained, may be of the flat surface type, installed level with the deck, with an available inlet area not less than
two (2) times the area of the conductor or leader to which the drain is connected.
(c) Secondary (emergency) roof drains or scuppers shall be provided where the roof perimeter construction allows
ponding if the primary roof drains become blocked.
(d) Separate systems required.
1. Secondary roof drain systems shall have piping and point of discharge separate from the primary system.
2. Discharge shall be above grade plane in a location that would normally be observed by the building occupants
or maintenance personnel.
(e) Primary and secondary drains shall be sized in accordance with Section 11 of this administrative regulation.
Section 9. Change of Direction. A change in direction of a sewer shall be made only with:
(1) Long curves;
(2) Forty-five (45) degree wyes;
(3) Half wyes;
(4) Quarter, sixth, eighth or sixteenth bends; or
(5) Sanitary tees installed on their back or on their sides. If installed, sanitary tees shall be at an angle of not more
than forty-five (45) degrees.
Section 10. Size of House Sewers and Horizontal Branches. (1) The minimum size of a house sewer shall not
be less than four (4) inches nor less than that of the house drain.
(2) A house sewer receiving a branch shall be sized in the same manner as a house drain.
(3) The house drains shall be installed in accordance with 815 KAR 20:090.
91
Section 11. Size of Storm Systems. (1) The required size of a storm sewer shall be determined on the basis of
the total drained area in horizontal projection in accordance with the table in subsection (4) of this section.
(2) A storm sewer shall not be laid parallel to or within two (2) feet of a bearing wall.
(3) The storm sewer shall be laid at a sufficient depth to protect it from freezing.
(4)
Diameter of
pipe –
inches
Maximum drained roof area square feet*
Slope 1/8 in. fall to 1 ft.
Slope 1/4 in. fall to 1 ft.
3 N/A 1,160
4 1,880 2,650
5 3,340 4,720
6 5,350 7,550
8 11,500 6,300
10 20,700 29,200
12 33,300 47,000
15 59,500 84,000
*The calculations in this table are based on a rate of rainfall of four (4) inches per hour
Section 12. Combined Storm and Sanitary Sewer System. (1) If a combined sewer system is used, the required
size of the house drain or house sewer shall be determined by multiplying the total number of fixture units carried
by the drain or sewer by the conversion factor corresponding to the drained area, and the total fixture units, adding
the product to the drained area and applying the sum from the table for storm water sewers in Section 11 of this
administrative regulation.
(2) A combined house drain or house sewer shall not be less than four (4) inches in diameter, and a combined
house drain or house sewer shall not be smaller in size than that required for the same number of fixture units or
for the same roof area in separate systems.
(3)
CONVERSION FACTORS FOR COMBINED STORM AND SANITARY SYSTEM
Number of Fixture Units on Sanitary System
Drained roof area in sq.
ft.
Up
to 6
7 to
18
19 to
36
37 to
60
61 to
96
97 to
144
145 to
216
217 to
324
Up to 120 180 105 60 45 30 22 18 15
121 to 240 160 98 57 43 29 21 17.6 14.7
241 to 480 120 75 50 39 27 20 16.9 14.3
481 to 720 75 62 42 35 24 18 15.4 13.2
721 to 1,080 54 42 33 29 20 15 13.6 12.1
1,081 to 1,620 30 18 16 15 12 11.5 11.1 10.4
1,621 to 2,430 15 12 11 10.5 9.1 8.8 8.6 8.3
2,431 to 3,645 7.5 7.2 7.0 6.9 6.6 6.5 6.4 6.3
3,646 to 5,460 2.0 2.4 3.0 3.3 4.1 4.2 4.3 4.4
5,461 to 8,190 0 2.0 2.1 2.2 2.3 2.4 2.5 2.6
8,191 to 12,285 0 0 2.0 2.1 2.1 2.2 2.3 2.3
12,286 to 18,420 0 0 0 2.1 2.1 2.1 2.2 2.2
18,421 to 27,630 0 0 0 0 2.0 2.1 2.2 2.2
27,631 to 40,945 0 0 0 0 0 2.0 2.1 2.2
40,946 to 61,520 0 0 0 0 0 0 2.0 2.1
Over 61,520 0 0 0 0 0 0 0 2.0
92
Number of Fixture Units on Sanitary System
Drained roof
area in square
feet
325
to
486
487 to
732
733 to
1098
1,099 to
1644
1,645 to
2466
2,467
to
3702
3,703 to
5556
Over
5556
Up to 120 12 10.2 9.2 8.4 8.2 8.0 7.9 7.8
121 to 240 11.8 9.9 9.1 8.3 8.1 8.0 7.9 7.8
241 to 480 11.5 9.7 8.8 8.2 8.0 7.9 7.8 7.7
481 to 720 10.8 9.2 8.6 8.1 7.9 7.9 7.8 7.7
721 -1,080 10.1 8.7 8.3 8.0 7.8 7.8 7.7 7.6
1,081 - 1,620 9.8 8.4 8.1 7.9 7.7 7.7 7.6 7.5
1,621 - 2,430 8.0 7.9 7.8 7.7 7.6 7.5 7.4 7.4
2,431-3,645 6.2 6.3 6.4 6.4 6.8 7.0 7.1 7.2
3,646-5,460 4.5 4.7 5.0 5.1 6.1 6.4 6.9 6.9
5,461-8,190 2.8 3.2 3.7 4.6 5.0 5.6 6.2 6.4
8,191-12,285 2.4 2.5 2.6 2.7 3.5 4.5 5.2 5.6
12,286-18,420 2.3 2.3 2.4 2.4 2.6 3.2 4.2 4.7
18,421-27,630 2.2 2.3 2.3 2.3 2.4 2.5 2.8 3.1
27,631-40,945 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.4
40,946-61,520 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
Over 61,520 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
(5) For a building constructed after August 1, 1996, each plumbing fixture or opening connecting to a combination
sanitary and storm sewer system shall either:
(a) Be installed above the elevation of the cover of the nearest manhole serving the main; or
(b) Discharge through a sewage ejector to the combined sewer system at an elevation high enough to prevent
flooding of the building.
Section 13. House Sewer in Undisturbed or Filled Ground. (1) A house sewer laid in undisturbed ground shall
be laid on at least four (4) inches of pea gravel, sand, or other approved grillage as defined in 815 KAR 20:010.
(2) A house sewer laid in filled ground shall be embedded to the lower quadrant with at least a four (4) inch
concrete pad below the invert, or other equivalent support that shall be approved by the department.
(3) A support in filled ground shall be on a ten (10) foot center to a solid footing, either undisturbed earth or rock.
(4) A house sewer constructed of flexible thermoplastic sewer piping shall be installed with at least six (6) inches
of gravel on the bottom, top, and sides of the piping.
Section 14. Storm Sewers in Undisturbed or Filled Ground. (1) A storm sewer laid in undisturbed ground shall
not require grillage.
(2) A storm sewer laid in filled ground shall be embedded to the lower quadrant with at least a four (4) inch concrete
pad below the invert or other support that shall be approved by the department.
(3) A support in filled ground shall be on a ten (10) foot center to a solid footing, either undisturbed earth or rock.
Section 15. Drainage Below Sewer Level (Public). In a public building in which the whole or part of the building
drain and plumbing system lies below the level of the main sewer, sewage and waste shall be lifted by a device
that complies with Sections 17 and 18 of this administrative regulation and discharged into the building sewer.
93
Section 16. Drainage Below Sewer Level (Residential). (1) In a home in which the house sewer level is above
the basement floor, waste water shall be lifted by means of an approved sump pump appropriate for that
installation.
(2) The sump pit shall:
(a) Be gas and air tight; and
(b) Be constructed of:
1. Poured or precast concrete;
2. Approved fiberglass; or
3. Polyethylene material.
(3) The sump pit shall be provided with a two (2) inch vent, which may also act as a waste and vent for a laundry
tray.
(4) The pump discharge piping shall discharge into a two (2) inch waste pipe extended inside the building to a
height at least twelve (12) inches above the outside grade plane.
(5) The sump pit shall be provided with a tight-fitting concrete cover.
(6)(a) On the outside of the building, this waste piping shall connect into a four (4) inch by two (2) inch sanitary
tee, which shall connect into a four (4) inch P trap and then into the sanitary sewer.
(b) The four (4) inch by two (2) inch sanitary tee shall be extended at least two (2) inches above the finished grade
plane and shall be provided with a ventilated cap.
Section 17. Sumps and Receiving Tanks. (1) A subsoil drain shall discharge into an air tight sump or receiving
tank located to receive the sewage by gravity.
(2) The sewage shall be lifted and discharged into the house sewer by a pump or ejector.
(3) Sewage sumps shall be a minimum twenty four (24) inches in diameter and no less than twenty four (24)
inches in depth.
(4) A system that relies solely on a pump shall be equipped with both an audible and visual alarm to be placed
within the occupied space.
(5) The sump shall automatically discharge.
Section 18. Ejectors, Vented. (1) A sewage ejector serving a residential installation shall be vented with a two
(2) inch vent.
(2)(a) Except as established in paragraph (b) of this subsection, an ejector serving a commercial or industrial
installation shall be vented with a three (3) inch vent.
(b)1. If a three (3) inch vent stack is serving a fixture that empties into the ejector pit and is located within twenty-
five (25) feet of the pit, the ejector may be revented with a two (2) inch vent back to the three (3) inch vent stack.
2. The ejector vent shall not be smaller than that recommended by the manufacturer of the pump.
(3) A portion of the building drainage system that is above the cover of the manhole serving the main that can flow
by gravity to a sewer shall be installed for gravity flow to the combined sanitary and storm sewer, except for a
system designed otherwise by a licensed professional engineer.
Section 19. Ejector Power: Motors, Compressors, and Air Tanks. (1) A motor, air compressor, or air tank shall
be located so that it shall be open for inspection and repair at all times.
(2) An air tank shall be proportioned to furnish sufficient air at suitable pressure to the ejector to completely empty
the sump or storage tank with the compressor not operating.
(3) The end pressure in the tank shall not be less than two (2) pounds for each foot of height through which
sewage is raised.
Section 20. Ejectors for Subsoil Drainage. (1) If a subsoil catch basin is installed below the sewer level, an
automatic ejector shall be used.
(2) The ejector or a device raising subsoil water shall discharge into a properly trapped fixture or into a storm-
water drain.
94
Section 21. Drainage of Yards, Areas, Roofs, and Traps. (1) A roof, paved area, court, or courtyard shall be
drained into:
(a) A storm water system;
(b) A combined sewerage system; or
(c) A surface drainage area unless prohibited by the local health department or sewer district.
(2) A yard, roof, paved area, court, or courtyard shall not be drained into a sewer intended for sewage only.
(3) Traps.
(a) If a drain is connected to a combined sewerage system, it shall be trapped.
(b) If a roof leader, conductor, or gutter opening is located more than ten (10) feet from a window, scuttle, or air
shaft, a trap shall not be required.
(c) A trap shall be set below the frost line or on the inside of the building.
(d) If a drain is not connected to a combined sewer, a trap shall not be required.
Section 22. Size of Rain Water Leader. An inside leader shall not be less size than as established in the following
table:
Section 23. Inside Conductors or Roof Leaders. (1) If a conductor or roof leader is placed within the walls of a
building, or in an interior court or ventilating pipe shaft, it shall be constructed of:
(a) Cast iron pipe;
(b) Galvanized wrought iron;
(c) Galvanized steel;
(d) Copper;
(e) Schedule 40 ABS/PVC DMV pipe; or
(f) Reinforced thermosetting resin pipe produced and labeled as ASTM F1113 (red and silver thread).
(2)(a) Except as established in paragraph (b) of this subsection, plastic pipe and fittings (PVC or ABS) shall be
limited to buildings in which the conductor does not exceed forty-five (45) feet in height, measured from the grade
plane as defined by the Kentucky Building Code, 815 KAR 7:120, or Kentucky Residential Code, 815 KAR 7:125,
and continuing through the vertical distance of the building to a maximum height of forty-five (45) feet.
(b) Plastic pipe and fittings may be installed in a building in which the conductor exceeds forty-five (45) feet in
height if the installation complies with all of the requirements established in this section.
(c) The use of PVC and ABS piping shall be limited to Schedule 40 or 80 produced and labeled as ASTM D2665
and D1784 for PVC piping and ASTM D2661 for ABS piping.
(d) The installation of the plastic pipe and fittings (PVC or ABS) shall be made in compliance with the
manufacturer’s recommendations, which shall be made available to the inspector.
(e) Firestop systems shall be inspected in accordance with ASTM E2174 by an inspection agency approved by
the department.
Section 24. Outside Conductors. (1) If an outside sheet metal conductor or downspout is connected to a house
drain, it shall be connected by means of a cast iron pipe extending vertically at least one (1) foot above the grade
plane.
(2) If the downspout runs along a public driveway without a sidewalk, it shall be placed in a niche in the walk,
protected by wheel guards, or enter the building through the wall at a forty-five (45) degree slope at least twelve
(12) inches above the grade plane.
Section 25. Defective Conductor Pipes. If an existing sheet metal conductor pipe within the walls of a building
becomes defective, the conductor shall be replaced by one that conforms to this administrative regulation.
Area of Roof (In Square
Feet)
Leader, Diameter
(Inches)
Up to 90 1 1/2
91 to 270 2
271 to 810 3
811 to 1,800 3 1/2
1,801 to 3,600 4
3,601 to 5,500 5
5,501 to 9,600 6
95
Section 26. Vent Connections with Conductors Prohibited. (1) A conductor pipe shall not be used as a soil,
waste, or vent pipe.
(2) A soil, waste, or vent pipe shall not be used as a conductor.
Section 27. Overflow Pipes. An overflow pipe from a cistern, supply tank, expansion tank, or drip pan shall
connect indirectly with a house sewer, house drain, soil pipe, or waste pipe.
Section 28. Subsoil Drains. A subsoil drain below sewer level shall discharge into a sump or receiving tank and
shall be automatically lifted and discharged into the storm drainage system or upon the ground outside the building
it serves.
Section 29. Approvals of New Sewer Connections to Existing Buildings. If the local health department or
sanitary sewage system board, plant, district, or treatment plant owner prohibits the discharge of a basement floor
drain or other apparatus into the sanitary sewer system, an existing basement floor drain or sump pump apparatus
shall comply with the construction requirements of this administrative regulation and be inspected prior to the
approval of a connection for a new sewer line. (Recodified from 401 KAR 1:100, 7-5-1978; Am. 5 Ky.R. 164; eff.
10-4-1978; 8 Ky.R. 362; eff. 1-6-1982; 10 Ky.R. 1016; eff. 3-31-1984; 12 Ky.R. 1675; eff. 5-6-1986; 13 Ky.R. 959;
eff. 12-2-1986; 14 Ky.R. 1142; eff. 1-4-1988; 16 Ky.R. 911; eff. 1-12-1990; 2779; 17 Ky.R. 1108; eff. 8-22-1990;
18 Ky.R. 2725; eff. 4-3-1992; 19 Ky.R. 822; eff. 11-9-1992; 1659; eff. 3-12-1993; 2742; 20 Ky.R. 309; eff. 8-6-
1993; 21 Ky.R. 1974; eff. 3-22-1995; 22 Ky.R. 2339; eff. 8-1-1996; 23 Ky.R. 2625; 2994; eff. 2-10-1997; 24 Ky.R.
962; eff. 12-15-1997; 27 Ky.R. 231; 773; eff. 9-11-2000; 33 Ky.R. 3273; 4180; eff. 7-6-2007; 35 Ky.R. 2608; 36
Ky.R. 99; eff. 7-29-2009; 41 Ky.R. 179; eff. 9-24-2014; 42 Ky.R. 133; eff. 11-6-2015; 43 Ky.R. 624; eff. 1-6-2017.)
96
815 KAR 20:150. Inspection and tests.
RELATES TO: KRS 318.090, 318.130, 318.134, 318.140, 318.160, 318.170
STATUTORY AUTHORITY: KRS 198B.040(1), 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the office, after review by the
Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate an administrative regulation
establishing the Kentucky State Plumbing Code. This administrative regulation establishes the requirements for
the tests and inspections that are necessary in order to ensure compliance with 815 KAR Chapter 20, the Kentucky
State Plumbing Code.
Section 1. Inspections and Tests. (1) The office shall inspect the following to ensure compliance with the State
Plumbing Code:
(a) The water distribution system;
(b) The soil, waste, and vent system;
(c) The fixtures and fixture traps;
(d) Appurtenances; All connections in a plumbing system. In buildings condemned by other authorities because
of unsanitary conditions of the plumbing system, the alterations shall be considered as a new plumbing system.
Section 2. Material and Labor for Tests. All equipment, material and labor necessary for inspections and tests
shall be furnished by the persons procuring the plumbing construction permits.
Section 3. Systems of Tests. (1) Test for the potable water supply system. The potable water supply system
shall be tested and found without leaks under the normal working pressure under which the system will function.
(2) Tests for the soil, waste, and vent system.
(a) The soil, waste, and vent system of the plumbing system shall be tested with water or air in accordance with
this administrative regulation before it is concealed or covered within the floors or walls of a building.
(b) After the plumbing fixtures have been set and their traps filled with water and before the building is occupied,
the entire system, other than the house sewer, shall be subjected to a final air pressure test.
(c) It shall be the responsibility of the person who secured the plumbing construction permit to notify the office
representative and request a final inspection and air test upon completion of the installation.
(d) If only a portion of the plumbing fixtures are set, an air test shall be requested and given prior to the time a
building is occupied. After the plumbing system is finally completed, another inspection and test shall be requested
and given.
(e) The office may require the removal of any clean-outs to ascertain whether or not the pressure has reached all
parts of the system.
(3) Tests of the house sewer. The house sewer shall be tested with a water, air, or smoke test.
Section 4. Methods of Testing. (1) The potable water supply system, as well as the water service, shall be:
(a) Tested under a pressure of not less than the maximum working pressure under which it is to be used; and
(b) Free from leaks.
(2)(a) Except as provided in subsection (3) of this section, a water test shall be performed:
1. On the entire soil, waste, and vent system; or
2. In sections.
(b) If it is applied to the entire system, all openings shall be closed, except the highest opening and the system
shall be filled with water to the point of overflow.
(c) If the system is tested in sections, each opening shall be tightly plugged, except the highest opening and it
shall be tested with not less than a ten (10) foot head of water. In testing successive sections, at least the upper
ten (10) feet of the preceding section shall be retested.
(3) In lieu of a water test, an air pressure test may be used by attaching an air compressor or test apparatus to
any suitable opening. All other inlets and outlets to the system shall be closed, forcing air into the system until
there is a uniform pressure of five (5) pounds per square inch (PSI). The pressure shall be maintained for fifteen
(15) minutes.
(4) The final air test shall test the entire soil, waste, and vent system including the fixture and appurtenances by
connecting an air machine to any suitable opening or outlet and applying air pressure equivalent to a one (1) inch
water column. It shall be maintained for at least a fifteen (15) minute period. If there are no leaks or forcing of trap
seals as may be indicated by the functioning of a drum, float, or water column, the system shall be deemed airtight.
(5) A garage drainage system shall be tested in the same manner as the soil, waste, and vent system.
(6) A house sewer shall be tested by a water, air, or smoke test. After the sewer trench has been filled with at
least two (2) feet of earth cover, it shall be retested. A four (4) inch test tee or Y connection shall be provided at
the property line for testing. The distance between cleanouts in sewers shall not exceed 150 feet.
97
(7) A building sewer not drained by gravity shall have a minimum of twenty-four (24) inches of cover and shall be
tested with five (5) pounds per square inch for a period of fifteen (15) minutes.
Section 5. Required Tests. Tests shall be made separately or as follows:
(1) The house sewer and its branches from the property line to the house drain;
(2) The house drain including its branches;
(3) The soil, waste, and vent system;
(4) Inside rain water conductors; and
(5) The final inspection and air test which shall include the complete plumbing system as required by Section 4(2)
of this administrative regulation, exclusive of the house sewer.
Section 6. Tests of Alterations, Extensions, or Repairs. Any alterations, repairs, or extensions that require
more than ten (10) feet of soil, waste, or vent piping shall be inspected and tested as required by Section 3(2) of
this administrative regulation.
Section 7. Covering of Work. The plumbing system shall not be covered until it has been inspected, tested, and
approved.
Section 8. Uncovering of Work. If any part of a plumbing system is covered or concealed before being inspected,
tested, and approved, it shall be uncovered, or unconcealed and tested as required.
Section 9. Defective Work. If an inspection or a test indicates defective work or material, it shall be replaced and
the inspection and the test repeated.
Section 10. Testing Defective Plumbing. An air test shall be used in testing the condition of a plumbing system
if there is reason to believe it has become defective.
Section 11. Inspections and Tests Not Required for Exhibition Purposes. Tests and inspections shall not be
required where a plumbing system shall be used for exhibition purposes and is not directly connected to a
sewerage system.
Section 12. Inspections and Tests for the Replacement of Old Plumbing Fixtures. Inspections and tests shall
not be required if:
(1) Old plumbing fixtures are replaced with new fixtures;
(2) Faucets or valves are replaced; or
(3) Leaks are repaired.
Section 13. Certificate of Approval. Upon the satisfactory completion and final test of the plumbing system, a
certificate of approval shall be issued by the office. (Recodified from 401 KAR 1:110, 7-5-78; Am. 11 Ky.R. 77; eff.
8-7-84; 20 Ky.R. 1394; eff. 1-10-94; 27 Ky.R. 234; 776; eff. 9-11-2000; 33 Ky.R. 3277; 4183; eff. 7-6-07.)
98
815 KAR 20:170. Mobile home park waste systems and connections.
RELATES TO: KRS 318.130, 318.150
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: The office is directed by KRS 318.130 through the Kentucky
Housing, Buildings and Construction Advisory Committee, to adopt and put into effect a State Plumbing Code.
This administrative regulation establishes the requirements for mobile home park waste systems and connections
and specifies the materials and the method that shall be used in installing the necessary plumbing to serve mobile
homes.
Section 1. Sewers. (1) The main and branch sewers for the connections of mobile homes shall be laid at a uniform
grade and alignment and all joints shall be water tight.
(2) Clean-outs shall be provided at intervals not to exceed 100 feet for main and branch sewers in sizes six (6)
inches and smaller.
(3) The cleanouts shall be extended to the grade with cast-iron soil pipe and shall be provided with a clean-out
plug.
(4) A four (4) inch concrete pad, eighteen (18) inches square, shall be provided around each clean-out.
(5) All main and branch sewers eight (8) inches and larger shall not require clean-outs but shall require standard
manholes at intervals not to exceed 400 feet as well as in all changes in direction.
(6) Each mobile home shall be provided with a four (4) inch sewer.
(7) A three (3) inch waste connection shall be provided and extended one (1) inch above the grade using a three
(3) inch standard female thread.
(8) A four (4) inch concrete pad twenty-four (24) inches square shall be provided around the waste opening.
(9) A three (3) inch screw plug shall be fastened by a chain to the concrete pad which shall be used if the mobile
home opening is not in use.
(10) The waste pipe connection between the mobile home and the sewer waste opening shall be a waterproof
connection constructed of either cast-iron, schedule 40 steel pipe, copper pipe or schedule 40 ABS or PVC piping.
Section 2. Individual Residential Mobile Home Waste System and Connection. (1) An individual residential
mobile home shall either be connected to a municipal sewer system or to an approved private sewage disposal
system in accordance with this section.
(2) Each mobile home shall be provided with at least a three (3) inch waste connection to the house sewer.
(3) All piping that does not have at least an eighteen (18) inch cover shall be cast-iron pipe.
(4) Waste connections between the permanent piping and the mobile home waste connection shall be a
waterproof connection constructed of either cast-iron, schedule 40 steel pipe, copper pipe or schedule 40 ABS or
PVC piping. (Recodified from 401 KAR 1:130, 7-5-78; Am. 17 Ky.R. 2895; eff. 5-3-91; TAm eff. 8-9-2007; 35 Ky.R.
2612; 36 Ky.R. 102; eff. 7-29-2009.)
99
815 KAR 20:180. Special connections.
RELATES TO: KRS 318.010, 318.130
STATUTORY AUTHORITY: KRS 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the office, after review by the
Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate an administrative regulation
establishing the Kentucky State Plumbing Code regulating plumbing, including the methods and materials that
may be used in Kentucky. This administrative regulation establishes requirements regarding waste, other than
sanitary wastes.
Section 1. Commercial Laundry Wastes. Waste from commercial and institutional washing machines and
extractors shall not discharge into an open trench, unless the trench is drained into at least a four (4) inch trap,
with a full-size vent. The trench shall be constructed of a material resistant to alkaline waste.
Section 2. Semi-commercial Laundries (Automatic). (1) Waste from semi-commercial laundries shall discharge
into a four (4) inch waste line for washing machines only.
(2) The waste line shall have a full-size vent and the base of the stack shall be washed by either a washing
machine or starch sink.
(3) A four (4) inch trap shall be provided in the waste line to serve not more than two (2) washing machines.
(4) Floor drains may be placed in the waste line.
(5) If they are the pump type, a stand pipe shall be provided to the height of the machine.
(6) Each four (4) inch trap shall constitute four (4) fixture units. A washing machine shall not discharge into a
trench.
Section 3. Washing Machines, Automatic, Residential (New Buildings). An automatic washing machine
installed in a new building, shall have a two (2) inch trap and shall be vented in accordance with 815 KAR 20:080.
The trap shall be installed twelve (12) inches above the floor with a two (2) inch stand pipe extended to the height
of the washer. If a washing machine discharges into a private disposal system, fifty (50) feet additional lateral shall
be added to the sewage system.
Section 4. Washing Machines, Automatic, Residential (Old Buildings). An automatic washing machine
installed in an old building, shall be connected to the house sewer by the use of a four (4) inch cast-iron P-trap,
placed on the outside of the building on the opposite side of the wall of the washing machine. The trap shall have
a vented cover extending three (3) inches above the grade line. A four (4) inch by two (2) inch tee shall be installed
in the inlet side of the trap with a two (2) inch waste pipe extending into the building through the floor to the height
of the washing machine. All waste piping shall conform with 815 KAR 20:080.
Section 5. Air Conditioning Equipment. (1) Air conditioning equipment installed with a water supply and waste
shall conform with 815 KAR 20:090, Sections 29 and 32. Evaporative cooler, air washer, air handling or similar
air conditioning equipment shall not have any drain pipe directly connected to any soil, waste or vent pipe. The
equipment shall be drained by means of indirect waste pipe. The indirect waste shall discharge through an air gap
or air break into an open floor sink, floor drain, or other approved type receptor which is properly connected to the
drainage system, except that an air gap shall be required if the indirect waste pipe may be under vacuum.
(2) The condensate or waste pipe from an air conditioning unit shall be classified as a plumbing fixture only if
directly connected to the plumbing system.
Section 6. Garage Sand Trap. A garage sand trap shall be constructed of concrete with a heavy cover or grate.
The minimum size shall be two (2) feet by four (4) feet and it shall have sufficient depth so that there is at least a
ten (10) inch vertical distance between the bottom of the outlet ell and the bottom of the trap. Sand traps shall be
provided with a four (4) inch vent.
Section 7. Inflammable Waste. Liquid waste from buildings using gasoline, benzine, naphtha or other
inflammable oils or compounds shall discharge into a separator before it enters a sanitary sewer. The waste line
receiving the waste shall be trapped and vented in accordance with 815 KAR 20:080 and 20:090. The separator
shall be provided with a three (3) inch vent.
Section 8. Hot Water, Steam Blow-offs or Exhaust. Hot water or steam or exhaust blow-offs shall discharge
into a tank or basin before entering the house drain or sewer. The tank or basin shall have an airtight cover and
be provided with a four (4) inch vent independent of any other venting system.
100
Section 9. Stable Manure Pits. All liquid waste from barns, stable manure pits and stable yard drains shall
discharge through a separator before entering the house sewer.
Section 10. Pedicure Chairs. (1) A two (2) inch open receptacle may receive the discharge from up to two (2)
pedicure chairs. Three (3) to six (6) chairs shall have a minimum of a three (3) inch open receptacle.(2) A branched
tail piece discharge for a pump-type pedicure chair may be used in an existing location only after approval of the
Division of Plumbing.
(3) If the water inlet for a pedicure chair is below the flood level rim or is equipped with a spray hose, it will be
treated as a high hazard and require a reduced pressure principle backflow preventer on both the hot and cold
supply. (Recodified from 401 KAR 1:140, 7-5-78; Am. 10 Ky.R. 457; eff. 11-2-83; 17 Ky.R. 2896; eff. 5-3-91; 32
Ky.R. 375; 666; 11-4-05.)
101
815 KAR 20:191. Minimum fixture requirements.
RELATES TO: KRS 58.200, 318.160
STATUTORY AUTHORITY: KRS 198B.040 (10), 318.130
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department, after approval by
the Kentucky Housing, Buildings and Construction Advisory Committee, to promulgate an administrative
regulation establishing the Kentucky State Plumbing Code regulating plumbing, including the methods and
materials that may be used in Kentucky. KRS 58.200(2) requires newly-constructed public buildings to be
equipped with twice the number of restroom facilities for use by women as is provided for use by men. This
administrative regulation establishes the minimum plumbing fixture requirements for buildings in Kentucky.
Section 1. Definitions. (1) "Developed travel distance" means the length of a pathway measured along the center
line of the path.
(2) "Mobile facility" means a vehicle licensed and registered with the Kentucky Department of Transportation
that contains plumbing fixtures and is intended for temporary use with regard to the structure it serves.
(3) "Modular" means a structure or component that is wholly or in substantial part fabricated in an off-site
manufacturing facility for installation at the building site.
(4) "Temporary" means a period of time not to exceed thirty (30) days of intermittent or continual use within a
twelve (12) month period on the same premises.
Section 2. General Requirements. (1) In a building accommodating males and females, it shall be presumed
that the occupants will be equally divided between males and females, unless otherwise denoted.
(2) The occupancy load factor used to determine the total number of plumbing fixtures required in a building shall
be the load denoted in the Kentucky Building Code, incorporated by reference in 815 KAR 7:120.
(3) All types of buildings shall be provided with toilet rooms on each level or floor, unless:
(a) Separate facilities on each level or floor are unnecessary; and
(b) Toilet rooms on every other level or floor shall be sufficient.
(4) Unisex Facilities in Historic Buildings. A building or structure that is listed in the National Register of Historic
Places or designated as historic under Kentucky statute may provide the required number of plumbing fixtures in
unisex facilities if the overall occupant load is 100 persons or less, except as required in Sections 7, 8, 9, 12, 13,
15, 16, and 17 of this administrative regulation.
(5) Unisex facilities in historic buildings permitted by this section shall not be required to provide the urinals.
(6) Toilet rooms for males, females, and unisex shall be clearly marked.
(7) Upon written request, the department shall permit the temporary use of a mobile facility in accordance with
this administrative regulation. The written request shall be submitted to the Division of Plumbing and shall include
the:
(a) Name of the owner;
(b) Address of the location of the building being served by the mobile facilities; and
(c) Dates for which the mobile facilities are to be used.
Section 3. Toilet Floor Construction Requirements. (1) Floors in toilet rooms shall be constructed of
nonabsorbent materials.
(2) If a wood floor is used, the wood floor shall be covered by other nonabsorbent materials.
(3) If two (2) or more fixtures that receive human waste are installed, the toilet room shall have at least:
(a) One (1) floor drain; and
(b) One (1) accessible hose bibb.
Section 4. Facilities for Stages.
(1) A separate water closet and lavatory shall be provided for males and females in the stage area.
(2) A drinking fountain shall be provided in the stage and auditorium area.
102
Section 5. Theaters, Assembly Halls, and Similar Occupancies. Separate toilet rooms for males and females
shall be provided as established in this section and in Sections 2 through 4 of this administrative regulation. (1)
Water closets and urinals for males.
(a) Water closets for males shall be installed with at least:
1. One (1) water closet for each 100 males;
2. Two (2) water closets for 101 to 200 males;
3. Three (3) water closets for 201 to 400 males; and
4. If over 400 males, three (3) water closets plus one (1) additional water closet for each additional 500 males or
fraction thereof.
(b) Urinals for males shall be installed with at least:
1. One (1) urinal for eleven (11) to 100 males;
2. Two (2) urinals for 101 to 300 males;
3. Three (3) urinals for 301 to 600 males; and
4. If over 600 males, three (3) urinals plus one (1) additional urinal for each additional 300 males or fraction thereof.
(2) Water closets for females. Water closets for females shall be installed with at least:
(a) One (1) water closet for each fifty (50) females;
(b) Two (2) water closets for fifty-one (51) to 100 females;
(c) Three (3) water closets for 101 to 150 females;
(d) Four (4) water closets for 151 to 200 females; and
(e) If over 200 females, four (4) water closets plus one (1) additional water closet for each additional 150 females
or fraction thereof.
(3) Lavatories for Males or Females. Lavatories shall be installed with at least:
(a) One (1) lavatory for up to 100 persons;
(b) Two (2) lavatories for 101 to 200 persons;
(c) Three (3) lavatories for 201 to 400 persons;
(d) Four (4) lavatories for 401 to 750 persons; and
(e) If over 750 persons, four (4) lavatories plus one (1) additional lavatory for each additional 500 persons or
fraction thereof.
(4) Sinks. There shall be at least one (1) service sink or slop sink on each floor.
(5) Number of fixtures. The number of fixtures shall be based upon the maximum seating capacity or fixed seats.
If fixed seats are not provided, the basis for determining the capacity shall be one (1) person per each fifteen (15)
square feet of area.
(6) Drinking fountain. At least one (1) drinking fountain shall be provided on each floor for each 50 persons or
fraction thereof.
(7) Water closets in public restrooms shall be of the elongated bowl type with a split open front seat.
Section 6. Libraries, Museums, and Art Galleries. Separate toilet facilities for males and females shall be
provided as established in this section and in Sections 2 through 4 of this administrative regulation:
(1) There shall be at least one (1) water closet and one (1) lavatory for each 100 females or fraction thereof.
(2) Except as established in subsection (7) of this section, there shall be at least one (1) water closet and one (1)
lavatory for each 200 males or fraction thereof.
(3) There shall be at least:
(a) One (1) urinal for eleven (11) to 200 males;
(b) Two (2) urinals for 201 to 400 males;
(c) Three (3) urinals for 401 to 600 males; and
(d) If over 600 males, three (3) urinals plus one (1) additional urinal for each additional 300 males or fraction
thereof.
(4) There shall be at least one (1) service sink or slop sink on each floor.
(5) At least one (1) drinking fountain shall be provided for each 500 persons or fraction thereof.
(6) Number of fixtures. The number of fixtures shall be based upon the maximum seating capacity of fixed seats.
If fixed seats are not provided, the basis for determining the capacity shall be one (1) person for each fifteen (15)
square feet of area.
(7) Urinals may be substituted for water closets for males if:
(a) The substituted urinals do not exceed one-third (1/3) of the required total number of water closets; and
(b) The minimum number of urinals is installed.
(8) Water closets in public restrooms shall be of the elongated bowl type with a split open front seat.
103
Section 7. School Buildings Not Including Higher-Education Facilities. A school building shall be in
compliance with the requirements established in 702 KAR 4:170 and this section. (1) Drinking fountains.
(a) At least one (1) drinking fountain shall be provided on each floor and wing of a building.
(b) At least one (1) additional drinking fountain shall be provided for each seventy-five (75) pupils or fraction
thereof.
(c) The drinking fountains shall be equipped with:
1. A protective cowl; and
2. The orifice, which shall be one (1) inch above the overflow rim of the fountain.
(2) Elementary through secondary level school buildings shall be provided with the following:
(a) Water closets for males shall be installed with at least:
1. One (1) water closet for up to twenty-five (25) pupils;
2. Two (2) water closets for twenty-six (26) to 100 pupils; and
3. If over 100 pupils, two (2) water closets plus one (1) additional water closet for each additional 100 pupils or
fraction thereof;
(b) Urinals for males shall be installed with at least:
1. One (1) urinal for up to twenty-five (25) pupils;
2. Two (2) urinals for twenty-six (26) to fifty (50) pupils;
3. Four (4) urinals for fifty-one (51) to 100 pupils;
4. Six (6) urinals for 101 to 200 pupils;
5. Eight (8) urinals for 201 to 300 pupils;
6. Ten (10) urinals for 301 to 400 pupils;
7. Twelve (12) urinals for 401 to 500 pupils; and
8. If over 500 pupils, twelve (12) urinals plus one (1) additional urinal for each additional fifty (50) pupils or fraction
thereof in excess of 500;
(c) Water closets for females shall be installed with at least:
1. Two (2) water closets for up to twenty-five (25) pupils;
2. Three (3) water closets for twenty-six (26) to fifty (50) pupils;
3. Six (6) water closets for fifty-one (51) to 100 pupils;
4. Eight (8) water closets for 101 to 200 pupils;
5. Ten (10) water closets for 201 to 300 pupils;
6. Twelve (12) water closets for 301 to 400 pupils;
7. Fourteen (14) water closets for 401 to 500 pupils; and
8. If over 500 pupils, fourteen (14) water closets plus one (1) additional water closet for each additional forty (40)
pupils or fraction thereof; and
(d)1. Lavatories for male and female pupils shall be installed with at least:
a. One (1) lavatory for each twenty-five (25) pupils or fraction thereof; and
b. If over fifty (50) pupils, two (2) lavatories plus one (1) additional lavatory for each additional fifty (50) pupils or
fraction thereof; and
2. Twenty-four (24) inches of sink or eighteen (18) inches of circular basin, if provided with water outlet for each
space, shall be considered equivalent to one (1) lavatory.
(3) At least one (1) service sink or slop sink shall be installed on each floor of a building.
(4) If detached modular classrooms are used, sanitary facilities shall not be required, if:
(a) The entrance of the modular classroom for elementary grades through the fifth grade is within a developed
travel distance not to exceed 100 feet from the accessible entrance to the main structure or an approved central
modular restroom;
(b) The entrance of the modular classroom for sixth grade and above is within a developed travel distance not to
exceed 200 feet, from the accessible entrance to the main structure or an approved central modular restroom;
(c) The travel path meets the accessibility requirements established in the Kentucky Building Code, 815 KAR
7:120; and
(d) There are sufficient fixtures in the main structure to serve the entire capacity of the school, including the
modular classrooms.
(5) Water closets in a school building shall be of the elongated bowl type with a split open front seat.
104
Section 8. Schools of Higher Education and Similar Educational Facilities. (1)(a) Except as established in
paragraph (b) of this subsection, in a school of higher education or a similar education facility, there shall be
installed at least:
1. One (1) water closet for each fifty (50) males and one (1) water closet for each twenty-five (25) females or
fraction thereof;
2. One (1) lavatory for each fifty (50) persons or fraction thereof;
3. One (1) drinking fountain for each seventy-five (75) persons or fraction thereof; and
4. One (1) urinal for each fifty (50) males or fraction thereof.
(b) One (1) water closet less than the number specified in paragraph (a) of this subsection may be provided for
each urinal installed except that the number of water closets in those cases shall not be reduced to less than two-
thirds (2/3) of the minimum specified.
(2) Water closets in a school of higher education or a similar education facility shall be of the elongated bowl type
with a split open front seat.
Section 9. Public Garages and Service Stations. (1) Separate toilet rooms for males and females shall be
provided with at least:
(a) A water closet and lavatory for females; and
(b) A water closet, lavatory, and urinal for males.
(2) Water closets shall be of the elongated bowl type with a split open front seat.
Section 10. Churches. (1) Sanitary facilities shall be provided in a church with at least:
(a) One (1) drinking fountain for each 400 persons or fraction thereof;
(b) One (1) water closet for each 150 females or fraction thereof;
(c) One (1) water closet for each 300 males or fraction thereof;
(d) One (1) urinal for fifty (50) to 150 males or fraction thereof;
(e) One (1) additional urinal for each additional 150 males or fraction thereof; and
(f) One (1) lavatory for each 150 persons or fraction thereof.
(g) Water closets in public restrooms shall be of the elongated b
Section 11. Transient Lodging Facilities. A transient lodging facility shall be in compliance with the requirements
established in 902 KAR 10:010 and this section. (1) A hotel or motel with private rooms shall have at least one (1)
water closet, one (1) lavatory, and one (1) bathtub or shower per room.
(2) In the public and service areas, there shall be at least:
(a) One (1) water closet for each twenty-five (25) males or fraction thereof;
(b) One (1) water closet for each fifteen (15) females or fraction thereof;
(c) One (1) lavatory for each twenty-five (25) persons or fraction thereof;
(d) One (1) urinal for eleven (11) to 100 males plus one (1) additional urinal for each additional fifty (50) males or
fraction thereof;
(e) One (1) drinking fountain for each seventy-five (75) persons or fraction thereof on each floor; and
(f) One (1) service sink or slop sink on each floor.
(3) In residential-type buildings, there shall be at least one (1) water closet, one (1) lavatory, and one (1) bathtub
or shower for each ten (10) males and each ten (10) females or fraction thereof.
(4) In rooming houses with private baths, there shall be at least one (1) water closet, one (1) lavatory, and one (1)
bathtub or shower per room.
(5) In rooming houses without private baths, there shall be at least:
(a) One (1) water closet for one (1) to ten (10) males and one (1) for each additional twenty-five (25) males or
fraction thereof;
(b) One (1) water closet for one (1) to eight (8) females and one (1) for each additional twenty (20) females or
fraction thereof;
(c) One (1) urinal for eleven (11) to 100 males and one (1) for each additional fifty (50) males or fraction thereof;
(d) One (1) lavatory for each ten (10) persons or fraction thereof; and
(e) One (1) bathtub or shower for each ten (10) persons or fraction thereof.
105
Section 12. Dormitories: School, Labor, or Institutional. (1) Water closets. There shall be at least:
(a) One (1) water closet for up to ten (10) males plus one (1) additional water closet for each additional twenty-
five (25) males or fraction thereof; and
(b) One (1) water closet for up to eight (8) females plus one (1) additional water closet for each additional twenty
(20) females or fraction thereof.
(2) Urinals.
(a) There shall be at least:
1. One (1) urinal for each twenty-five (25) males or fraction thereof up to 150 males; and
2. If there are over 150 males, one (1) additional urinal for each additional fifty (50) males or fraction thereof.
(b) If urinals are provided, a urinal may be substituted for a water closet, not to exceed one-third (1/3) of the
required total number of water closets.
(c) Trough urinals shall be figured on the basis of one (1) urinal for each twenty-four (24) inches of length.
(3) Lavatories. There shall be at least one (1) lavatory for one (1) to twelve (12) persons, with an additional one
(1) lavatory for each additional twenty (20) males and fifteen (15) females or fraction thereof.
(4) Additional fixtures. There shall be at least:
(a)1. One (1) bathtub or shower for each eight (8) persons or fraction thereof, up to 150 persons; and
2. If there are over 150 persons, one (1) additional bathtub or shower for each twenty (20) persons;
(b) One (1) drinking fountain for each seventy-five (75) persons or fraction thereof;
(c) One (1) laundry tray or clothes washer for each fifty (50) persons or fraction thereof; and
(d) One (1) service sink or slop sink for each 100 persons or fraction thereof.
(5) If the dormitory is located in a youth camp, the requirements of 902 KAR 10:040 shall apply in addition to the
requirements established in this section.
106
Section 13. Hospitals, Nursing Homes, and Institutions. A hospital, nursing home, or institution shall comply
with the requirements established in 902 KAR 20:031, 902 KAR 20:046, 902 KAR 20:056, and 902 KAR 9:010.
Sanitary facilities shall be provided on each floor level and shall conform to this section.
(1) Hospitals.
(a) Wards. There shall be at least:
1. One (1) water closet for each ten (10) patients or fraction thereof;
2. One (1) lavatory for each ten (10) patients or fraction thereof;
3. One (1) tub or shower for each fifteen (15) patients or fraction thereof; and
4. One (1) drinking fountain for each 100 patients or fraction thereof.
(b) Individual rooms. There shall be at least one (1) water closet, one (1) lavatory, and one (1) tub or shower.
(c) Waiting rooms. There shall be at least one (1) water closet and one (1) lavatory.
(2) Nursing homes and institutions (other than penal). There shall be at least:
(a) One (1) water closet for each twenty-five (25) males or fraction thereof;
(b) One (1) water closet for each twenty (20) females or fraction thereof;
(c) One (1) lavatory for each ten (10) persons or fraction thereof;
(d) One (1) urinal for each fifty (50) males or fraction thereof;
(e) One (1) tub or shower for each fifteen (15) persons or fraction thereof;
(f) One (1) drinking fountain on each floor; and
(g) One (1) service sink or slop sink on each floor.
(3) Institutions, penal.
(a) Cell. There shall be at least:
1. One (1) prison-type water closet; and
2. One (1) prison-type lavatory.
(b) Day rooms and dormitories.
1. There shall be at least:
a. One (1) water closet for each eight (8) female inmates or fraction thereof and one (1) water closet for each
twelve (12) male inmates or fraction thereof;
b. One (1) lavatory for each twelve (12) inmates or fraction thereof;
c. One (1) shower for each fifteen (15) inmates or fraction thereof;
d. One (1) drinking fountain per floor; and
e. One (1) service sink or slop sink per floor.
2. For males, one (1) urinal may be substituted for each water closet if the number of water closets is not reduced
to less than one-half (1/2) the number required.
(c) Toilet facilities for employees shall be located in separate rooms from those in which fixtures for the use of
inmates or patients are located.
(d) There shall be at least one (1) drinking fountain on each floor.
(e) There shall be at least one (1) service sink or slop sink per floor.
107
Section 14. Workshops, Factories, Mercantile, and Office Buildings. Separate toilet facilities shall be provided
for males and females on each floor unless otherwise denoted.
(1) Workshops and factories: Sanitary facilities shall conform to the following:
(a) There shall be at least:
1. One (1) water closet for each twenty-five (25) males or fraction thereof, up to 100;
2. One (1) lavatory for each twenty-five (25) males or fraction thereof, up to 100;
3. One (1) urinal for eleven (11) to fifty (50) employees;
4. Two (2) urinals for fifty-one (51) to 100 employees;
5. One (1) lavatory for each twenty-five (25) females or fraction thereof up to 100; and
6. One (1) water closet for each fifteen (15) females or fraction thereof up to 100;
(b) If in excess of 100 persons, there shall be at least:
1. One (1) additional water closet for each additional thirty (30) males and each additional thirty (30) females or
fraction thereof;
2. One (1) additional lavatory for each additional fifty (50) males and females or fraction thereof; and
3. One (1) additional urinal for each additional 100 males or fraction thereof;
(c) There shall be at least:
1. One (1) shower for each fifteen (15) persons or fraction thereof, exposed to skin contamination from irritating,
infectious, or poisonous materials;
2.a. One (1) drinking fountain on each floor for each fifty (50) employees or fraction thereof, up to 100 employees;
and
b. If there are more than 100 employees, there shall be an additional drinking fountain on each floor for each
additional seventy-five (75) employees or fraction thereof; and
3. One (1) service sink or slop sink per floor; and
(d)1. Individual sinks or wash troughs may be used in lieu of lavatories.
2. Twenty-four (24) inches of sink or trough, if provided with water, or eighteen (18) inches of circular basin shall
be deemed the equivalent of one (1) lavatory.
108
(2) Mercantile.
(a) Employees.
1. Except as provided in subparagraph 2 of this paragraph, sanitary facilities within each store shall be provided
for employees. If more than five (5) persons are employed, separate facilities for each se shall be provided.
2. For a store containing not more than 3,000 square feet of total gross floor area, employee facilities shall not be
required if adequate interior facilities are provided within a centralized toilet room area or accessible areas having
a travel distance of not more than 500 feet within the building in which the store is located.
(b) Customers.
1. Sanitary facilities shall be provided for customers if the building contains 5,000 square feet or more.
2. In a mall or shopping center, the required facilities, based on one (1) person per 100 square feet of total area,
shall be installed in individual stores or in a central toilet room area or areas, if:
a. The distance from the main entrance of a store does not exceed 500 feet; and
b. The toilet room area is accessible to physically disabled persons.
(c) Sanitary facilities shall be provided as stated in this section and there shall be at least:
1. One (1) water closet for one (1) to 150 males;
2. Two (2) water closets for 151 to 300 males;
3. Three (3) water closets for 301 to 450 males;
4. If over 500 males, three (3) water closets plus one (1) additional water closet for each additional 500 males or
fraction thereof;
5. One (1) urinal for fifty (50) to 200 males;
6. Two (2) urinals for 201 to 400 males;
7. Three (3) urinals for 401 to 600 males;
8. If over 300 males, three (3) urinals plus one (1) additional urinal for each additional 300 males or fraction thereof;
9. One (1) water closet for one (1) to 100 females;
10. Two (2) water closets for 101 to 200 females;
11. Three (3) water closets for 201 to 400 females;
12. If over 400 females, three (3) water closets plus one (1) additional water closet for each additional 300 females
or fraction thereof;
13. One (1) lavatory for one (1) to 200 persons;
14. Two (2) lavatories for 201 to 400 persons;
15. Three (3) lavatories for 401 to 700 persons;
16. If over 700 persons, three (3) lavatories plus one (1) additional lavatory for each additional 500 persons or
fraction thereof; Three (3) lavatories plus one (1) lavatory for each 500 persons, or fraction thereof, in excess of
700;
17. One (1) drinking fountain on each floor for each 500 persons or fraction thereof; and
18. One (1) service sink or slop sink per floor
109
(3) Office buildings.
(a) Employees.
1. Except as established in subparagraph 2 of this paragraph, sanitary facilities within office buildings shall be
provided for employees. If more than five (5) persons are employed, separate facilities for each sex shall be
provided.
2. For an office building or space containing not more than 3,000 square feet of total gross floor area, employee
facilities shall not be required if adequate interior facilities are provided within a centralized toilet room area or
areas having a travel distance of not more than 500 feet within the same building.
(b) Customers.
1. Sanitary facilities shall be provided for customers if the office building or space contains 5,000 square feet or
more.
2. In an office building, the required facilities, based on one (1) person per 100 square feet of total area, shall be
installed within the individual offices, or in a central toilet room area or areas if:
a. The distance from the main entrance of an office space does not exceed 500 feet; and
b. The toilet room area is accessible to physically disabled persons.
(c) Separate sanitary facilities for each gender shall be provided as stated in this section.
1. For males and females there shall be at least:
a. One (1) water closet for one (1) to fifteen (15) persons;
b. Two (2) water closets for sixteen (16) to thirty-five (35) persons;
c. Three (3) water closets for thirty-six (36) to fifty-five (55) persons;
d. Four (4) water closets for fifty-six (56) to eighty (80) persons;
e. Five (5) water closets for eighty-one (81) to 110 persons;
f. Six (6) water closets for 111 to 150 persons;
g. If over 150 persons, six (6) water closets plus one (1) additional water closet for each additional forty (40)
persons or fraction thereof;
h. One (1) lavatory for one (1) to fifteen (15) persons;
i. Two (2) lavatories for sixteen (16) to thirty-five (35) persons;
j. Three (3) lavatories for thirty-six (36) to sixty (60) persons;
k. Four (4) lavatories for sixty-one (61) to ninety (90) persons;
l. Five (5) lavatories for ninety-one (91) to 125 persons;
m. If over 125 persons, five (5) lavatories plus one (1) additional lavatory for each additional seventy-five (75)
persons or fraction thereof; and
n. One (1) drinking fountain for each seventy-five (75) persons or fraction thereof.
2. For males, if urinals are provided, one (1) water closet less than the number specified may be provided for each
urinal installed if the number of water closets is not reduced to less than seventy (70) percent of the minimum
specified.
110
Section 15. Swimming Pool Bathhouses. A swimming pool bathhouse shall comply with the requirements
established in 902 KAR 10:120 and this section. (1) Bathhouses for public swimming pools shall be divided into
two (2) parts separated by a tight partition, with one (1) part designated for "Males" or "Men" and the other part
designated for "Females" or "Women."
(2) Sanitary facilities shall be provided in each bathhouse to serve the anticipated bather load, as defined in 902
KAR 10:120, and shall conform to the following:
(a) For swimming pools in which the total bather capacity is 200 persons or less, there shall be at least:
1. One (1) water closet for each seventy-five (75) males or fraction thereof;
2. One (1) water closet for each fifty (50) females or fraction thereof;
3. One (1) urinal for each seventy-five (75) males or fraction thereof;
4. One (1) lavatory for each 100 persons or fraction thereof;
5. One (1) shower per each fifty (50) persons or fraction thereof; and
6. One (1) drinking fountain per each 200 persons or fraction thereof;
(b) For swimming pools in which the total bather capacity exceeds 200 persons, there shall be at least:
1. Five (5) water closets for 201 to 400 females, with one (1) additional water closet for each additional 250 females
or fraction thereof;
2. Three (3) water closets for 201 to 400 males, with one (1) additional water closet for each additional 500 males
or fraction thereof;
3. Three (3) urinals for 201 to 400 males, with one (1) additional urinal for each additional 500 males or fraction
thereof;
4. One (1) lavatory for up to 150 persons;
5. Two (2) lavatories for 151 to 400 persons;
6. Three (3) lavatories for 401 to 750 persons;
7. If over 750 persons, three (3) lavatories plus one (1) additional lavatory for each additional 750 persons or
fraction thereof;
8. One (1) shower per each fifty (50) persons or fraction thereof up to 150;
9. If over 150 persons, three (3) showers plus one (1) additional shower for each additional 500 persons or fraction
thereof; and
10. One (1) drinking fountain per each 500 persons or fraction thereof.
(3) Fixture schedules shall be increased for pools at schools or similar locations where bather loads may reach
peaks due to schedules of use. Pools used by groups or classes on regular time schedules of:
(a) One (1) hour or less shall have at least one (1) shower for each six (6) swimmers; and
(b) One (1) to two (2) hours shall have at least one (1) shower for each ten (10) swimmers.
(4) Shower facilities, including warm water and soap, shall be provided for each sex.
(a) Showers shall be supplied with water at a temperature of not less than ninety (90) degrees Fahrenheit and at
a flow rate of at least three (3) gallons per minute.
(b) Thermostatic, tempering, or mixing valves shall be installed to prevent scalding of the bathers.
(5) The requirement relating to bathhouse toilet room and shower facilities may be waived if the facilities are
available to pool patrons within 150 feet from the pool.
111
Section 16. Park Service Buildings or Bathhouses. A park service building or bathhouse shall comply with the
requirements established in 902 KAR 15:020, Section 8, and this section.
(1) Except for a self-contained recreational vehicle community, each park shall provide one (1) or more central
service buildings containing the necessary toilet and other plumbing fixtures established in this section.
(2) Except for a self-contained recreational vehicle community, sanitary facilities shall be provided as follows:
(a) If there are one (1) to fifteen (15) vehicle spaces, there shall be for:
1. Males: At least one (1) water closet, one (1) urinal, one (1) lavatory, and one (1) shower; and
2. Females: At least one (1) water closet, one (1) lavatory, and one (1) shower;
(b) If there are sixteen (16) to thirty (30) vehicle spaces, there shall be for:
1. Males: At least one (1) water closet, one (1) urinal, two (2) lavatories, and two (2) showers; and
2. Females: At least two (2) water closets, two (2) lavatories, and two (2) showers;
(c) If there are thirty-one (31) to forty-five (45) vehicle spaces, there shall be for:
1. Males: At least two (2) water closets, one (1) urinal, three (3) lavatories, and three (3) showers; and
2. Females: At least two (2) water closets, three (3) lavatories, and three (3) showers;
(d) If there are forty-six (46) to sixty (60) vehicle spaces, there shall be for:
1. Males: At least two (2) water closets, two (2) urinals, three (3) lavatories, and three (3) showers; and
2. Females: At least three (3) water closets, three (3) lavatories, and three (3) showers;
(e) If there are sixty-one (61) to eighty (80) vehicle spaces, there shall be for:
1. Males: At least three (3) water closets, two (2) urinals, four (4) lavatories, and four (4) showers; and
2. Females: At least four (4) water closets, four (4) lavatories, and four (4) showers;
(f) If there are eighty-one (81) to 100 vehicle spaces, there shall be for:
1. Males: At least four (4) water closets, two (2) urinals, five (5) lavatories, and five (5) showers; and
2. Females: At least five (5) water closets, five (5) lavatories, and five (5) showers; and
(g) If over 100 vehicle spaces are provided, there shall be provided at least:
1. One (1) additional water closet and one (1) additional lavatory for each sex per additional thirty (30) spaces or
fraction thereof;
2. One (1) additional shower for each sex per additional forty (40) vehicle spaces or fraction thereof; and
3. One (1) additional urinal for males per additional 100 vehicle spaces or fraction thereof.
112
Section 17. Residential and Day Camp Sites. A residential or day camp site shall comply with the requirements
established in 902 KAR 10:040 and this section. (1)(a) Each residential camp site shall be provided with sanitary
facilities for each sex as established in this section.
(b) A day camp shall:
1. Not be required to provide shower facilities; and
2. Provide all other sanitary facilities for each sex as established in this section.
(2) Sanitary facilities shall be provided as follows:
(a) If there are one (1) to eighteen (18) persons served, there shall be for:
1. Males: At least one (1) water closet, one (1) urinal, one (1) lavatory, and one (1) shower; and
2. Females: At least two (2) water closets, one (1) lavatory, and one (1) shower;
(b) If there are nineteen (19) to thirty-three (33) persons served, there shall be for:
1. Males: At least two (2) water closets, one (1) urinal, two (2) lavatories, and two (2) showers; and
2. Females: At least two (2) water closets, two lavatories, and two showers;
(c) If there are thirty-four (34) to forty-eight (48) persons served, there shall be for:
1. Males: At least two (2) water closets, two (2) urinals, two (2) lavatories, and three (3) showers; and
2. Females: At least three (3) water closets, two (2) lavatories, and three (3) showers;
(d) If there are forty-nine (49) to sixty-three (63) persons served, there shall be for:
1. Males: At least three (3) water closets, two (2) urinals, three (3) lavatories, and four (4) showers; and
2. Females: At least four (4) water closets, three (3) lavatories, and four (4) showers;
(e) If there are sixty-four (64) to seventy-nine (79) persons served, there shall be for:
1. Males: At least three (3) water closets, three (3) urinals, three (3) lavatories, and five (5) showers; and
2. Females: At least five (5) water closets, three (3) lavatories, and five (5) showers;
(f) If there are eighty (80) to ninety-five (95) persons served, there shall be for:
1. Males: At least four (4) water closets, three (3) urinals, four (4) lavatories, and six (6) showers; and
2. Females: At least six (6) water closets, four (4) lavatories, and six (6) showers; and
(g) If over ninety-five (95) persons are served, there shall be provided at least:
1. One (1) additional water closet and one (1) additional lavatory for each twenty-five (25) persons or fraction
thereof served;
2. One (1) additional shower for each twenty (20) persons or fraction thereof served; and
3. One (1) additional urinal per fifty (50) additional males or fraction thereof.
(3) Coed day camps with equal number of males and females shall meet the fixture requirements of Section 6(2)
of this administrative regulation, relating to elementary through secondary level school buildings.
(4) Water closets may be substituted for urinals if facilities are to be used by both sexes.
113
Section 18. Retail Food Stores and Restaurants. Sanitary facilities shall be provided for employees. A retail
food store or restaurant shall comply with the requirements established in 902 KAR 10:020, 902 KAR 45:005, and
this section.
(1) Food stores.
(a) If more than five (5) persons of different sex are employed, separate sanitary facilities shall be provided for the
employees.
(b)1. Separate sanitary facilities for each sex shall be provided for customers if the building contains 5,000 square
feet or more.
2. In a mall or shopping center, the required facilities shall be:
a. Based on one (1) person per fifty (50) square feet; and
b. Installed in individual stores or in a central toilet room area or areas, if the distance from the main entrance of
a store does not exceed 500 feet.
(c) There shall be at least:
1. One (1) water closet for one (1) to 100 persons;
2. Two (2) water closets for 101 to 200 persons;
3. Three (3) water closets for 201 to 400 persons;
4. If over 400 persons, three (3) water closets plus one (1) additional water closet for each additional 500 males
or 300 females or fraction thereof;
5. One (1) urinal for eleven (11) to 200 males;
6. Two (2) urinals for 201 to 400 males;
7. Three (3) urinals for 401 to 600 males;
8. If over 600 males, three (3) urinals plus one (1) additional urinal for each additional 300 males or fraction thereof;
9. One (1) lavatory for one (1) to 200 persons;
10. Two (2) lavatories for 201 to 400 persons;
11. Three (3) lavatories for 401 to 700 persons;
12. If over 700 persons, three (3) lavatories plus one (1) additional lavatory for each additional 500 persons or
fraction thereof;
13. One (1) drinking fountain on each floor for each 500 persons or fraction thereof; and
14. One (1) service sink, utility sink, or curbed mop basin per floor as required by the Cabinet for Health and
Family Services.
114
(2) Restaurants.
(a) If more than five (5) persons of different sex are employed, separate sanitary facilities for each sex shall be
provided for the employees.
(b)1. Except as provided in subparagraph 3 of this paragraph, in a new establishment or an establishment that is
extensively altered or changed from another type occupancy to a restaurant, toilet facilities for each sex shall be
provided and readily accessible for the use of both patrons and employees.
2. Carryout-type food service operations shall be exempt from providing toilet facilities for the use of their patrons.
3. A restaurant with a business occupancy of one (1) to fifteen (15) persons shall:
a. Comply with the requirements in paragraphs (c) and (e) of this subsection; or
b. Provide at least one (1) unisex facility consisting of one (1) water closet and one (1) lavatory.
(c) There shall be at least:
1. Two (2) water closets for one (1) to 100 persons;
2. Three (3) water closets for 101 to 200 persons;
3. Four (4) water closets for 201 to 300 persons; and
4. If over 300 persons, four (4) water closets plus one (1) additional water closet for each additional 200 persons
or fraction thereof.
(d) There shall be at least:
1. One (1) urinal for fifty (50) to 200 males; and
2. If over 200 males, one (1) urinal plus one (1) additional urinal for each additional 150 males or fraction thereof.
(e) There shall be at least:
1. One (1) lavatory for one (1) to 200 persons;
2. Two (2) lavatories for 201 to 400 persons;
3. Three (3) lavatories for 401 to 600 persons; and
4. If over 600 persons, three (3) lavatories plus one (1) additional lavatory for each additional 200 persons or
fraction thereof.
(f) There shall be at least:
1. One (1) drinking fountain for one (1) to 100 persons; and
2. If over 100 persons, two (2) drinking fountains plus one (1) additional water fountain for each additional 400
persons or fraction thereof.
(g) If food is consumed indoors on the premises, water stations may be substituted for drinking fountains.
(h) There shall be one (1) service sink, utility sink, or curbed mop basin on each floor as required by the Cabinet
for Health and Family Services.
(i) Lavatories for hand washing shall be provided in the kitchen area, readily accessible to the employees.
(3) Licensed food establishments. In all food establishments licensed by the Cabinet for Health and Family
Services, Department for Public Health, the requirements in this subsection shall be met.
(a) Hand-washing sinks.
1. All hand-washing sinks shall have a minimum hot water temperature of 100 degrees Fahrenheit and a maximum
of 120 degrees Fahrenheit.
2. Self-closing faucets shall provide a flow of water for no less than fifteen (15) seconds from activation.
3. Placement of hand-washing sinks shall be approved by the Cabinet for Health and Family Services, Department
for Public Health pursuant to 902 KAR 45:005.
(b) A three (3) compartment sink used for washing utensils shall be required and shall drain by a direct connection
with a minimum of a two (2) inch drain.
(c) Dishwashing or ware washing machines shall discharge indirectly through a three (3) inch open receptacle.
(d) Residential type dishwashing machines shall discharge:
1. Through an air gap device; or
2. Indirectly through a three (3) inch open receptacle.
(e) Sinks solely used for food preparation shall discharge by an indirect connection to a minimum three (3) inch
trap.
(f) All hub drains, open receptacles, floor sinks, or other waste receptacles shall extend one (1) inch above the
floor plane unless a full grate/strainer is installed flush with the floor.
(g) Occupied mobile food units not located within an existing permitted food establishment shall:
1. Meet the requirements of the Kentucky Plumbing Code, KRS Chapter 318 and 815 KAR Chapter 20;
2. Have a waste tank no less than fifty (50) percent larger than the freshwater tank;
3. Have a National Sanitary Foundation (NSF) approved freshwater tank for potable water; and
4. Have a minimum of a three (3) compartment sink and one (1) hand sink.
(7 Ky.R. 526; eff. 1-7-1981; Am. 8 Ky.R. 367; eff. 1-6-1982; 9 Ky.R. 837; eff. 2-2-1983; 10 Ky.R. 458; eff. 11-2-1983; 1018; eff. 3-31-1984; 12
Ky.R. 49; eff. 8-13-1985; 14 Ky.R. 1146; eff. 1-4-1988; 15 Ky.R. 613; 981; eff. 9-28-1988; 16 Ky.R. 2277; eff. 6-7-1990; 23 Ky.R. 1764; 2503; eff.
12-11-1996; 27 Ky.R. 236; 777; eff. 9-11-2000; 30 Ky.R. 2398; 31 Ky.R. 92; eff. 8-6-2004; TAm eff. 8-9-2007; 36 Ky.R. 218; 609; eff. 10-2-2009;
2135-M; 2327; 37 Ky.R. 375; eff. 6-23-2010; 39 Ky.R. 155; eff. 10-5-2012; 41 Ky.R. 183; 463; eff. 9-24-2014; 42 Ky.R. 2655, 2899; eff. 6-22-2016.)
115
815 KAR 20:195. Medical gas piping installations.
RELATES TO: KRS 198B.050, 318.010, 318.134
STATUTORY AUTHORITY: KRS 198B.050(2), (5), 318.130, 318.134(3)
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.134(3) requires the department to establish a
reasonable schedule of fees and charges to be paid for plumbing installation permits and the necessary
inspections incident thereto. KRS 318.130 authorizes the department to promulgate a reasonable rule or
administrative regulation to administer the provisions of KRS Chapter 318. This administrative regulation
establishes the requirements for medical gas piping installation.
Section 1. Definitions. (1) "Health care facility" means a hospital, nursing home, limited care facility, clinic,
ambulatory care center, or office practice medical or dental office as defined in NFPA 99C.
(2) "Medical gas piping" means a permanent fixed piping system in a health care facility that is used to convey
oxygen, nitrous oxide, nitrogen, carbon dioxide, helium, medical air, and mixtures of these gases from its source
to the point of use. Medical gas piping includes the fixed piping associated with a medical, surgical, or gas
scavenging vacuum system, as well as a bedside suction system.
(3) "NFPA" means the National Fire Protection Association.
Section 2. Standards and Procedures. (1) Installation standards. Except as established in paragraphs (a) and
(b) of this subsection, a new medical gas piping installation or an addition to an existing medical gas piping system
shall comply with the applicable provisions of NFPA 99C, Standard on Gas and Vacuum Systems, 2002 Edition.
(a) Section 5.1.10.6.6, Branch Takeoffs, shall not be adopted nor enforced within the commonwealth.
(b) Axially swaged, elastic strain preload fittings providing metal to metal seal having a temperature rating not less
than 538 degrees Celsius (1,000 degrees Fahrenheit) and a pressure rating not less than 2,070 kPa (300 psi),
and that, at completion, are permanent and non-separable, shall be permitted to be used to join copper or stainless
steel tube. The axially swaged, elastic strain preload fittings shall not be installed within six (6) inches of a brazed
joint, and a brazed joint shall not be installed within six (6) inches of an existing axially swaged, elastic strain
preload fitting.
(2) Permit required. A licensed master plumber shall make application for a permit to install medical gas piping
prior to the installation. To obtain the permit, the master plumber shall:
(a) Pay a fee of forty-five (45) dollars base permit for the medical gas system for each building;
(b) Pay a fee of fifteen (15) dollars per opening; and
(c) Identify the person who shall perform the installation. The person making the installation shall be a certified
medical gas installer as required by NFPA 99C as well as a licensed master or journeyman plumber.
(3) Supervision by the master. It shall be the responsibility of the licensed master plumber to ensure that the
person doing the installation:
(a) Is properly certified as required by NFPA 99C;
(b) Uses the proper products and stores them correctly; and
(c) Requests and receives all inspections at the initial pressure test for the complete system from a certified state
plumbing inspector.
(4) Final approval. Upon completion of the installation, the master plumber shall furnish the Division of Plumbing
with certification from the medical gas system verifier as required by NFPA 99C.
Section 3. Incorporation by Reference. (1) "NFPA 99C Standard on Gas and Vacuum Systems", 2002 Edition,
National Fire Protection Association, is incorporated by reference.
(2) This material may be inspected, copied, or obtained, subject to applicable copyright law, at the Department of
Housing, Buildings and Construction, 101 Sea Hero Road, Suite 100, Frankfort, Kentucky 40601-5412, Monday
through Friday, 8 a.m. to 4:30 p.m.
(3) A copy may also be obtained by contacting the National Fire Protection Association, 1 Batterymarch Park,
P.O. Box 9101, Quincy, Massachusetts 02269-9101. (23 Ky.R. 2372; Am. 2746; eff. 1-9-97; 30 Ky.R. 2404; 31
Ky.R. 97 eff. 8-6-04; TAm eff. 8-9-2007; 35 Ky.R. 2613; 36 Ky.R. 103; eff. 7-29-2009; 39 Ky.R. 1509; 1887; eff.
4-5-2013; 41 Ky.R. 1204; 1796; eff. 3-6-2015; 42 Ky.R. 2661, 2904; eff. 6-22-2016.)
116
Please note the following approved methods of kitchen equipment installation. Apply this to
the plans submitted to the State of Kentucky Division of Plumbing for approval.
Ice makers – Open Receptacle or Floor Drain with a funnel
Pre-rinse sink – Must have solid connection
Dishwasher – Open Receptacle with a minimum 3” trap
Dipper wells – Open Receptacle
Waiter sink – Must have solid connection
Drink dispensers – Open Receptacle
Beverage center – Open Receptacle
Three Compartment sink – Must have solid connection
2 compartment sink – Must have solid connection
Single compartment sink – Must have solid connection
Ice bin – Open Receptacle
Bar sink Must have solid connection
Sinks used for food preparation can only discharge into a floor sink. Arrange the floor sink so they
have a 1” lip above the finished floor.
When using a floor drain, floor sink, open receptacle or hub drain line only, the waste can be arranged
to use a combination hub and floor drain system. The main waste line will be 4” waste line with a full
size vent at the last opening. All floor drains must have 4” traps. The waste line must drain into an
approved master trap outside the building as specified by the Kentucky State Plumbing Code.
If each floor drains, floor sink, open receptacle and hub drain are vented individually, the master trap
is not required.
All restaurants and food service establishments are required to have a grease trap.
Sinks for food preparation shall be indirectly connected to the plumbing system via a Floor Sink. The
drain pipe from the prep sink to the floor sink is cut on a 45 degree angle to provide an air gap and
reduce splashing.
117
Useful Information
Angle of Bend Arc of Circle
60 – Degree 1/6
th
45 – Degree 1/8
th
30 – Degree 1/12
th
22½ – Degree 1/16
th
11¼ – Degree 1/32
nd
5 5/8 – Degree 1/64
th
To find the length of a forty-five degree offset: Multiply the distance between the two parallel lines by the
constant 1.414.
For offsets that are not greater than 3 feet: The following is a good rule for 45-degree offsets, but not close
enough for long offsets. Add to the distance between the two parallel lines pipe, 5 inches for each foot of such
distance, and at the same rate for fractional parts of a foot. This would mean the addition of 5/12
th
of an inch for
each inch. To be more exact, add 12/32
nd
of an inch to each inch distance between the two lines of pipe.
Table of Pipe Offset Constants
Fitting Angle Constants
1/64
th
Bend 5 5/8 – Degree 10.203
1/32
nd
Bend 11¼ – Degree 5.125
1/16
th
Bend 22½ – Degree 2.613
1/12
th
Bend 30 – Degree 2.000
1/8
th
Bend 45 – Degree 1.414
1/6
th
Bend 60 – Degree 1.155
118
The weight of one US gallon of water is 8 1/3 lbs.
One cubic foot contains 7.48 US gallons.
Pressure per square inch of a column of water is 0.434 X height in feet.
To find the pressure in pounds per square inches at the base of a column of water: Multiply the head or
height in feet by .434.
To find the head, when pressure per square inch is known: Divide the pressure by .434.
To find the volume of any rectangular or a cylindrical tank: Multiply the area of the base X height.
To find the volume of a rectangular tank: Multiply length X width X height.
To find the volume of a cylindrical tank: Multiply R² X 3.1416 X Height or D² X .7854 X height.
To find the volume of a rectangular or cylindrical tank in US gallons: When dimensions are given in inches,
divide the number of cubic inches by 231.
To find the volume of a cylindrical or rectangular tank in US gallons: When dimensions are given in feet,
multiply the number of cubic feet X 7.48.
To find the cubic contents of any length of pipe of any size: First find the cubic contents of one foot of pipe,
and then multiply that amount by the number of feet of pipe. If these dimensions are in inches, the result will be
in cubic inches. If the result desired is gallons, as it generally will be divide the result in cubic inches by 231,
there being 231 cubic inches in one gallon.
A short method of finding the number of gallons in a foot of pipe of a diameter: Multiply the square of the
inside diameter of the pipe by .0408.
Rule for Estimating the Pitch of a Pipe: Divide the total drop or fall of the pipe, measured in inches, by the
horizontal distance between the two ends of the pipe, measured in feet. The result will give the pitch per feet in
fractions of an inch.
To find the circumference of a circle: Its diameter being given, multiply the diameter by 3.1416. The product
will be the circumference.
To find the diameter of a circle the circumference being known: Divide the circumference by 3.1416. The
result will be the diameter.
To find the area of a circle when the diameter is known: Square the diameter and then multiply by .7854.
Circumference of Circle = 3.1416 X Diameter
Area of Circle = 3.1416 X Square of Radius
To find the cylindrical area of a cylinder: Multiply the circumference of a circle by the length of the cylinder.
To find the cubic content of a cylinder: Multiply the area of its circle by the length of the cylinder.
To change a common fraction to a decimal: Divide the numerator by the denominator, and point off the right
number of decimal places.
To add decimals: Arrange the numbers so that the decimal points are in line, and then carry out the addition as
for whole numbers.
To multiply two decimals: Arrange the two numbers regardless of the location of their decimal points. The
multiplication of the numbers proceeds exactly as in the case of multiplying two whole numbers together. The
proper location of the decimal point in the answer is determined by the following: In the product of the two
numbers the decimal point should have as many numbers to the right of it as the sum of the numbers to the right
of the decimal points of the two numbers that are multiplied together.
119
To divide two decimal numbers: Divide the two numbers without regard to the two decimal points. Just as in
the division of two whole numbers, subtract from the number of decimal places in the dividend the number of the
decimal places in the divisor and the remainder will be the correct number of figures to the right of the decimal
point in the quotient, which will be the answer required.
To change per cent into a common fraction: Write the number expressing the per cent as the numerator with
100 as the denominator. Often such a fraction may be simplified by reducing it to its lowest terms.
To change a number written with a per center sign into a decimal: Omit the per cent sign and move the
decimal point two places to the left.
To change a decimal to per cent: Shift the decimal point two places to the right.
To change a common fraction into per cent: Reduce the fraction to hundredths, omit the denominator and
place the per center sign after the numerator.
To find a required per cent of a number: Multiply the number by the given per cent.
In this method, the number below the line shows the number of equal parts into which the whole is
divided and is call the denominator. The number of equal parts taken is shown above the line and is
called the numerator. According in speaking of ¾ of a pound, the denominator, 4 shows the pounds
divided into four equal parts and the numerator, 3 shows that three of these four parts are taken or set
aside for some special purpose.
A fraction can be changed to higher terms (without changing its value) by multiplying both numerator
and denominator by the same number and to lower terms, (without changing its value) by dividing both
numerator and denominator by the same number.
To reduce a mixed number to an improper fraction: Multiply the whole number by the denominator of the
fraction, then add the numerator to the result and place the result over the denominator.
To reduce two or more fractions to fractions having a common denominator: After deciding what the
common denominator is to be , multiply each of the several numerators by the number of times its denominator
is contained in the common denominator.
To add two or more fractions: Reduce the fraction to fractions having a least common denominator. Then add
the numerators of the fractions and place the sum over the common denominator, this fraction will be the
answer required.
To subtract fractions: Reduce them to fractions having a common denominator. Then, if necessary reduce the
result to its lowest terms and in the case of an improper fraction reduce it to a mixed number.
When mixed numbers are to be subtracted: Subtract the fractions and the whole numbers separately.
When the smaller mixed number is a larger fraction than the larger mixed number: Borrow 1 from the
whole number of the larger mixed number and add it to its fraction and then proceed to subtract.
When the larger number is a whole number and smaller is a mixed number: Borrow 1 from the whole
number.
In cancellation, any factor above the line may be divided (if without remainder) into any factor below the
line and any factor below the line may be divided into any factor above the line Multiply together the
numbers remaining above the line for the numerator and the number remaining below the line for the
denominator. If no number remains above the line, use 1.
To multiply a fraction by a fraction: Multiply the numerator together for the numerator of the answer and the
denominators together for the denominator of the answer. Cancel whenever possible.
120
Method of Making a Square
Nail together two straight pieces of 1 x 2 board to form an L as shown in
Figure 25.
Mark off a point 3 feet from the corner on one of the boards.
Mark off a point 4 feet from the corner of the other board.
Cut another board exactly 5 feet long. Line up this board with the points marked
on the other two boards.
NOTE: These measurements can have doubled to make a larger square or they may be cut in half to make a
smaller square.
Capacities of Tanks
Cylindrical Tanks
Formulas:
C = capacity in gallons
D = diameter
L = length
When measurements are in inches:
C = D x D x 0.7854 x L
231
When measurements are in feet:
C = D x D 0.7854 x L x 7.48
Example:
How many gallons of water will a tank hold which is 3 feet in diameter and 12 feet long?
C = D x D 0.7854 x L x 7.48
C = 3 x 3 0.7854 x 12 7.48 = 634.477 or 634 ½ gallons
121
To find the volume of a rectangle tank: Multiply length x width x height.
Formulas:
C = Capacity
L = Length
W = Width
H = Height
Example
10’ x 3’ x 5’ = 150 cu. ft.
150 x 7.48 = 1122.00 gallons
To find the volume in US gallons: Multiply the number of cubic inches by 231
7.48 gallons = 1 cubic foot 231 cubic inches = 1 gallon
Mechanical Engineers and Architectural blueprints usually give the city sewer main and the building
drain invert elevation (inside bottom of the barrel) in feet and decimals of a foot.
Plumbers work with feet and inches of a foot; therefore, plumbers must change feet and decimals of a foot to
feet and inches.
Rules for estimating the pitch of a pipe:
Divide the total drop or fall of the pipe, measured in inches by the horizontal distance between the two ends of
the pipe measured in feet. The result will give the pitch per feet in fractions of an inch.
Pitch to Grade
Pitch Grade
1/16” 1/2 %
1/8” 1%
1/4" 2%
1/2" 4%
Total Drop 3 ¾” or 3.75
3.75 divided by 30 = .125 or 1/8” per foot
122
To find the pressure in pounds per square inch at the base of a column of water:
Multiply the head or the height in feet by .434
Example
15’ x .434 = 6.51 lbs. or 6 1/2 lbs.
Decimal Equivalents
Fractions of an inch Decimals of an inch Decimals of a foot
1/6” .063” .005’
1/8” .125” .010’
3/16” .188” .016’
1/4” .250” .021’
5/16” .313” .026’
3/8” .375” .031’
7/16” .438” .037’
1/2" .500” .042’
9/16” .563” .047’
5/8” .625” .052’
11/16” .688” .057’
3/4" .750” .063’
13/16” .813” .068’
7/8” .875” .073’
15/16” .938” .078’
123
Multiplier Chart
To Change
To
Multiply by
Inches
Feet
0.0833
Inches
Millimeters
25.4
Feet
Inches
12
Feet
Yards
.3333
Yards
Feet
Square Inches
Square Feet
0.00694
Square Feet
Square Inches
144
Square Feet
Square Yards
0.1111
Square Yards
Square Feet
Cubic Inches
Cubic Feet
0.00058
Cubic Feet
Cubic Inches
1728
Cubic Feet
Cubic Yards
0.03703
Cubic Yards
Cubic Feet
27
Cubic Inches
Gallons
0.00433
Cubic Feet
Gallons
7.48
Gallons
Cubic Inches
231
Gallons
Cubic Feet
0.1337
Gallons
Pounds of Water
8.33
Pounds of Water
Gallons
0.12004
Ounces
Pounds
0.0625
Pounds
Ounces
16
Inches of Water
Pounds per Square Inch
0.0361
Inches of Water
Pounds per Square Foot
5.2
Feet of Water
Pounds per Square Inch
0.434
Feet of Water
Pounds per Square Foot
62.5
Atmospheres
Pounds per Square Inch
14.696
Atmospheres
Feet of Water
34
124
Loop Vent
125
3 Compartment sink and grease trap installation
126
127
Travel Trailer Dump Station
128
Pedicure Chairs
1. A two (2) inch open recipticale may receive the discharge from up to two (2) pedicure chairs.
2. Three (3) inch open recipticle may receive the discharge from three (3) to six (6) pedicure chairs.
3. Pump discharge: each pump discharge shall be individually piped to an open recipticle.
4. If the water inlet for a pedicure chair is below the flood level rim or is equiped with a spray hose, it will be
treated as HIGH HAZARD and shall require a reduced pressure principle backflow preventer on both
hot and cold water supply.
129
Note: Sinks of any type cannot be added to these systems
130
131
132
Index
Acid Waste:
Department
8
* Discharge
76
Drainage System
25
* Joints
75
Drawings and Charts
*Laboratory Piping
72
Ejector:
Advertising 14
* Specifications
93
Air Conditioning Equipment
99
Enforcement
17
APML
Definition
33
Examining Committee
13
Apprentice
Definition
Farmstead
Back Water Valve:
Fees:
*Specifications
78
* Master and Journeyman License
40
Bar and Soda Fountain
72
* Permits
49
Basic Principles
19
Fire Protection Systems
88
Borosilicate Pipe
Tubing:
Fittings:
* Connection
75
* Directional Flow
78
* Specifications
52
* Prohibited DWV
68
Budget Review
32
Fixtures:
Cast Iron:
* Addition, Defective
55
* Installation Standards
59
* Connection Waste and Vent
69
* Joints
74
* Minimum Fixture Requirements
101
* Specifications
51
* Overflow and Strainers
55
Cement Joints
Making of
57
Floor Drains:
Changing of Direction
DWV
68
* A Fixture
54
Chemical Waste
See Acid Waste
* Basement
-
Residential
71
Clay Pipe
51
* Manufactured Floor Drain System
71
Cleanouts: * Utility Room - Residential 78
* Equivalents
78
* Vent not Required
-
Residential
71
* Required
77
Floor Flanges
53
* Specifications
77
Future Openings
69
Code:
Garage Sand Trap 99
* Amendments to
13
Grades and Supports
-
DWV
68
* Committee
12
Grease Traps
78
* Definition
Hot Water
Steam Blow Off
99
* Meeting
12
House Drain:
Commercial Laundry
Semi
99
* Definition
26
Concrete Pipe:
* Material
72
* Joints
74
Indirect Waste
72
* Specification
51
Inflammable Waste
79
Conductor
Specifications
94
Inspection:
Continuous Waste
-
Specifications
78
* Specifications
96
Continuing Education:
* Testing
97
* Plumbers
43 Island Sink - Drawing 124
* Providers
45
Joints and Connection:
Copper Pipe
* Definition and Installation
74
* Installation Standards
61
* Prohibited
76
*
Specifications
51
* Roof
76
CPVC
* Slip
75
* Installation Standards
64
Journeyman Plumber:
* Specifications
64
* Definition
Cross-Link Polyethylene Pipe (PEX)
66
* Requirements
42
Dead Ends
68
Lead
Use of
52
Definitions:
* Laws
* Regulations
23
133
Index Continue
d
License:
* Appeal
12
Plumber:
* Application - Requirements
40
* Application
40
* Company Having
13
* Definition
* Continuing Education
43
* Examination
40
* Expiration - Renewal
41
* Qualification
10
* Qualifications
10
Plumbing:
* Re-examination
11
* Basic Principles
19
* Required
* Definition
* Suspension
11
* System
27
* Unlicensed
14
Polyethylene Pipe
52
Maintenance Man
Public Building
Manholes
78
Refrigeration Waste
72
Master Plumber:
Roof Leaders
94
* Application - Examination
41
Sand Trap:
* Definition
* Definition
28
* Requirement
41
SDR 11
64
Material:
SDR 35
51
* Label
51
Semi
-
Commercial Laundries
99
* List
33
Sewer:
* New
53
* Below Drainage
92
* Quality and Weight
51
* Change in Direction
90
* Soil, Waste and Vent
68
* Depth
89
* Specification
16
* Material
90
Mild Steel Pipe:
* Size
90
* Installation Standards
63
* Specifications
89
* Specifications
51
Shower Drains
54
Mobile Home:
Soil and Waste Pipe:
* Drawing
128
* Change in Existing Building
70
* Individual
98
* Prohibited Connection
70
* Sewer
98
* Protection
70
Oil Separator - Specifications
99
* Size Per Fixture Unit
69
Open Receptacle
72
* Stacks
69
Overflow Pipe:
Special Connections
99
* Definition
72
Stable Manure Pits
100
* Discharge
95
Stainless Steel Tubing:
* Tank and Vats
87
* Installation Standards
60
Pedicure Chair:
* Specifications
52
* Drawing
128
Storm Systems:
* Specification
100
* Material
90
Penalties
17
* Size
91
Permits:
Sump:
* Fees
49
* Specification
93
* Installation
15
Temperature and Pressure
* Insurance
49
* Shower
86
* When Required
49
* Water Heater
87
Person
Terminal
70
Plans and Specifications
16
Testing:
Plastic Pipe:
* Covering of / Uncovering of
97
* Expansion joint drawing
131
* Commingling
58
* Methods
96
* Firestop Requirement
52
* Required
97
* 45 Foot Limitations
52
Thermal Expansion
* Joints
57
* CPVC
64
* Specifications
57
* Plastic Pipe
58
* Storage and Installation
57
Threaded Fittings
53
134
Index Continued
Traps:
* Distance from Vent
70
* Grease
78
* Kind and Size
77
* Prohibited
77
* Required
77
* Sand
78
* Tubular
77
Truss
Pipe
51
Unions
75
Vehicle Identification
48
Vents:
* Branch
71
* Common Vents
71
* Flat or Wet Vents
73
* Grades and Connections
71
* Main
71
* Not Required
71
* Required Size
71
Vitrified Clay Pipe:
* Joints
74
*
specifications
51
Washing Machine
99
Waste Pipe Size:
* Trap, Branch and Fixture Units
65
Water Conservation
80
Water Closet:
* Material
54
* Specifications
54
Water Company Exemption
Water Heater:
* Drawing
126
* Preheating
87
* Reports
50
* Serial Number
17
* Solar
87
* Specification
55
Water Supply:
* Air Gap
79
* Boiler
84
* Control
86
* Fan Coil Unit
88
* Fixtures
84
* Material
85
* Mobile Homes
88
* Protection
87
* Required
83
* Service and Distribution
83
* Sizing
85
* Specifications
79
135