www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Technical Services
Tel: 888.862.3289
E-130
Conduit & Fittings — T&B
®
Cord & Cable Fittings
STAR TECK
®
Teck Cable Fittings
Jacketed Metal-Clad Cable and Teck Cable
Metal-Clad Cable (Type MC) Ref. NEC
®
Article 330
“Metal-Clad Cable Type MC is a factory assembly of one or more conductors,
each individually insulated and enclosed in a metallic sheath of interlocking
tape, or a smooth or corrugated tube.”
Metal-Clad Cable Type MC is rated for use up to 5,000 volts. The
National Electrical Code permits use of metallic sheath as an equipment
grounding conductor.
Metal-Clad Cables are available with a variety of phase conductor insulations
such as crosslinked polyethylene and silicone rubber ethylene propylene,
depending on rated temperature of conductors and working potential. Metallic
sheath can be of galvanized steel, aluminum, copper or bronze. Aspecial outer
covering such as PVC or Neoprene over metallic sheath isusually provided for
environmental protection.
Metal-clad cable is not permitted in locations where it could be subject
tophysical damage. Metal-clad cable can be used exposed, concealed, in
cable tray, in any approved raceway and with minor exceptions in hazardous
locations. Type MC cable can also be used for services, feeders, branch
circuits, power, lighting, control and signal circuits.
Use of metal-clad cable is permitted in wet locations, or where exposed to
destructive corrosive conditions or can be directly buried in earth, concrete
or exposed to cinder fills, strong chlorides, caustic alkalis, vapors, chlorine
orhydrochloric acids provided the construction of cable, the conductors within
the metallic sheath, the metallic sheath and protective cover over metallic
sheath comply with requirements enumerated in Sec. 330.10 of theNational
Electrical Code.
Bend radius restrictions are dependent on the size of the cable and the
typeof sheath, i.e., smooth, interlocked armor, corrugated sheath or shielded
conductors and varies from seven times to 15 times cable external diameter.
NEC Article 330 requires that approved fittings be used for termination.
Where single-conductor cables carrying alternating current enter a ferrous
metal box or enclosure, procedures described in NEC Section 300.20 must
be followed to reduce effects of heating due to induced currents. These
procedures include recommended arrangements of conductors, cutting of
slots in metal between individual conductor holes, passing of conductors
through insulating walls, or use of non-magnetic aluminum sheathed cable
and aluminum terminating fittings.
Portions of this section reprinted by permission from NFPA 70, National
Electrical Code
®
, National Fire Protection Association, Boston, MA.
Please refer to the following for further details and complete information:
1. NEC Article 330…Metal Clad Cable (Type MC)
2. UL 4, ANSI C33.9…Safety Standards for Type MC Metal Clad Cable
3. UL 514B, Safety Standards for Outlet Boxes & Fittings
4. A-A50552…Federal Specification. Fittings for Cable, Power Electrical
&Conduit Metal, Flexible
5. NEMA FM-1…Standards Publication. Fittings and Supports for Conduit and
Cable Assemblies
Teck Cables
Teck cable derived its name from one of its first users, the Teck-Hughes
GoldMines in Kirkland Lake, Ontario. Teck 90 is CSA Type designation.
Tradedesignation of this cable is Armored Cable.
Teck cables up to 5,000-volt working potential are manufactured in
accordance with CSA Standard C22.2 No. 131 and are provided with a
bare ground conductor and an optional outer jacket. Depending on phase
conductor insulation, the cables are designated as Teck 90 (X-LINK) when
insulation is cross-linked polyethylene and Teck 90 (EP) when insulation is
ethylene propylene. Both cables are rated for 90° C service (dry location)
and 75° C (wet locations). When Teck cable is suitable for installation down
to -40° F, the cables are marked Teck 90 (X-LINK) minus 40 or Teck 90 (EP)
minus 40.
Over 5,000 volts working potential Teck cables are manufactured in
accordance with IPCEA standards and are certified by CSA. Cables are
provided with or without ground wire as required.
Teck cables with outer jacket may be used for exposed or concealed wiring
in wet or dry locations, indoors/outdoors and in corrosive environments. Teck
cables are suitable for use in ventilated, non-ventilated and ladder-type cable
troughs, in ventilated flexible cable ways in both dry and wet locations. Teck
cable with outer jacket is suitable for direct earth burial and for Class II Division
2, Class III Division 1 & 2 hazardous locations per Canadian Electric Code.
Some of the features of Teck cable are its flexibility and ease of installation.
Absence of dead air space within cable increases heat transfer and minimizes
condensation. Overall protective covering provides good environmental
protection.
Bend radii for permanent training during installation usually varies between
seventimes to 12 times the cable diameter depending on cable construction
andmanufacturer’s recommendations. Larger radii bends are required for
other conditions.
Section 12-3028 of the Canadian Electric Code requires that the terminating
fittings used must provide adequate strain relief to terminal connections
andensure electrical continuity without injury to non-metallic sheath. Continuity
ismandatory whether or not the armor is used as a grounding conductor.
Except for dry locations free from corrosive atmosphere, the non-metallic
jacket is not permitted to be stripped back to a point where armor is exposed
after installation.
Where single conductor cables carrying 200 amps or more enter metal
boxes through separate openings, certain precautions are required to prevent
overheating of the metal by induction. Use of non-ferrous or non-metallic box
connectors, locknuts and bushings and installation of non-magnetic panel
inserts is suggested in the code.
Please refer to the following for further details and complete information:
1. CEC Section 12…Wiring Methods
CEC Section 4…Conductors
2. CSA C22.2 No. 131 & 131S
(Supplement #1)…Safety Standard for Type Teck Cable
3. CSA C22.2 No. 18…Safety Standards for Outlet Boxes, Conduit Boxes
and Fittings
4. UL File E82038 — Volume 1, Section 3, Page 1, Revision 1/31/2007
Note: The materials herein, whether relating to the National Electrical Code, the Underwriters Laboratories, Inc. listing, to industry practice or otherwise are not intended to provide
all relevant information required for use and installation of our products. Refer to applicable codes, instructions and industry specifications prior to installation or use.