User Manual
Original Instructions
PowerFlex 527 Adjustable
Frequency AC Drive
Bulletin Number 25C
2 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
PowerFlex 527 Adjustable Frequency AC Drive User Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
These labels may also be on or inside the equipment to provide specific precautions.
The following icon may appear in the text of this document.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which
may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).
Identifies information that is useful and can help to make a process easier to do or easier to understand.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 3
Table of Contents
Preface
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Download Firmware, AOP, EDS, and Other Files . . . . . . . . . . . . . . . . . . . . 7
Summary of Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Who Should Use this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Manual Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Drive Frame Sizes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
General Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 1
Installation/Wiring Mounting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Minimum Mounting Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Ambient Operating Temperatures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Current Derating Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Debris Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
AC Supply Source Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Ungrounded Distribution Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Input Power Conditioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General Grounding Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Ground Fault Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Safety Ground - (PE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Motor Ground. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Shield Termination - SHLD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
RFI Filter Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fuses and Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fusing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fuses and Circuit Breakers for PowerFlex 527 . . . . . . . . . . . . . . . . . . 21
Power and Control Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Control Module Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Power Module Terminal Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Motor Cable Types Acceptable for 100…600 Volt Installations . . . . 30
Reflected Wave Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Output Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Power Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
I/O Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Motor Start/Stop Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Signal and Control Wire Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Maximum Control Wire Recommendations. . . . . . . . . . . . . . . . . . . . 34
Control I/O Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
PowerFlex 527 Control I/O Removable Terminal Block . . . . . . . . . . 35
CE Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Table of Contents
Low Voltage Directive (2014/35/EU). . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
EMC Directive (2014/30/EU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Machinery Directive (2006/42/EC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
ATEX Directive (2014/34/EU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
UKCA Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Electrical Equipment (Safety) Regulations (2016 No. 1101) . . . . . . . 38
Electromagnetic Compatibility Regulations (2016 No. 1091). . . . . . 38
Supply of Machinery (Safety) Regulations (2008 No. 1597) . . . . . . . 38
Equipment and Protective Systems Intended for Use in Potentially
Explosive Atmospheres Regulations (2016 No. 1107) . . . . . . . . . . . . . 38
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Chapter 2
Start Up Prepare for Drive Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Drive Startup Task List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Start, Stop, Direction, and Speed Control . . . . . . . . . . . . . . . . . . . . . . 46
Understanding the PowerFlex 527 Display and Indicators. . . . . . . . . . . 46
Startup Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Device and Axis States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Information Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Real-time Information Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Drive Programming Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Language Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Using the Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Chapter 3
Configuring the PowerFlex 527
Drive with Integrated Motion
Configure the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Set the Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Configure the Logix Designer Application Project . . . . . . . . . . . . . . . . . . 54
Configure the Logix 5000 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Add a PowerFlex 527 Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Configure the PowerFlex 527 Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Configure Drive with Hardwired Safety Connections . . . . . . . . . . . 60
Configure Drive with Integrated Safety Connections . . . . . . . . . . . 61
Continue Drive Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Configure the Motion Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Configure Axis Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Download the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Apply Power to the PowerFlex 527 Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Test and Tune the Axes – Velocity and Position Control Modes . . . . . . 80
Test the Axes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Tune the Axes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 5
Table of Contents
Chapter 4
PowerFlex 527 Integrated Safe
Torque-Off
Certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Important Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Category 3 Requirements According to ISO 13849 . . . . . . . . . . . . . . . 85
Stop Category Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Performance Level (PL) and Safety Integrity Level (SIL) . . . . . . . . . 86
Description of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Probability of Dangerous Failure Per Hour (PFH) . . . . . . . . . . . . . . . . . . 86
PFH Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Safe Torque-Off (STO) Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Safe Torque-Off Feature Bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
As-Shipped Safety Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Out-of-Box (OOB) Safety State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Recognizing the Out-of-Box State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Restoring the Drive to the Out-of-Box State . . . . . . . . . . . . . . . . . . . . 88
Safe Torque-Off Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Axis Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Safety Supervisor State. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Propose TUNID Blocked. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Safe Torque-Off Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Safe Torque-Off Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Chapter 5
Hardwired Control of Safe
Torque-Off
Description of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Selection of Hardwired Safe Torque-Off . . . . . . . . . . . . . . . . . . . . . . . 93
Operation of Hardwired Safe Torque-Off . . . . . . . . . . . . . . . . . . . . . . 93
Troubleshoot the Safe Torque-Off Function . . . . . . . . . . . . . . . . . . . . 94
Safe Torque-Off Connector Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Wire the Safe Torque-Off Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Safe Torque-Off Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . 96
Safe Torque-Off Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Chapter 6
Network Control of Safe Torque-
Off
Compatible Safety Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Selection of Network Safe Torque-Off . . . . . . . . . . . . . . . . . . . . . . . . . 99
Safety Application Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Network Safe Torque-off Specifications . . . . . . . . . . . . . . . . . . . . . . 100
Safe Torque-off Assembly Tags. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
STO Fault Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Troubleshoot Network Safe Torque-Off. . . . . . . . . . . . . . . . . . . . . . . 102
Understanding Integrated Safety Drive Replacement. . . . . . . . . . . . . . 103
Replacing an Integrated Safety Drive in a GuardLogix System. . . . . . 103
Replacement with “Configure Only When No Safety Signature
Exists” Enabled. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Replacement with “Configure Always” Enabled . . . . . . . . . . . . . . . . 108
Motion Direct Commands in Motion Control Systems. . . . . . . . . . . . . 109
6 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Table of Contents
Understanding STO Bypass When Using Motion Direct Commands
110
Logix Designer Application Warning Messages. . . . . . . . . . . . . . . . 110
Torque Permitted in a Multi-workstation Environment . . . . . . . . 112
Warning Icon and Text in Axis Properties. . . . . . . . . . . . . . . . . . . . . 112
Functional Safety Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Chapter 7
Troubleshooting Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Interpret Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Display Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
PowerFlex 527 Drive Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . 120
General Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Logix 5000 Controller and Drive Behavior . . . . . . . . . . . . . . . . . . . . . . . . 123
PowerFlex 527 Drive Exception Behavior. . . . . . . . . . . . . . . . . . . . . . 124
Appendix A
Supplemental Drive Information Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Power Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Appendix B
Accessories and Dimensions Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Product Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Replacing the PowerFlex 527 Control Module Internal Fan. . . . . . 157
Appendix C
Out-of-Box Configuration Recommended Out-of-Box Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Setting the ACO/AVO Attribute. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Appendix D
Encoder Option Card Usage Installing the Encoder Option Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Removing the Encoder Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Encoder Option Card Usage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Encoder Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
HTL/TTL DIP Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 7
Preface
About This Publication The purpose of this manual is to provide you with the basic information that is
needed to install, startup, and troubleshoot the PowerFlex® 527 Adjustable
Frequency AC Drive.
Rockwell Automation recognizes that some of the terms that are currently
used in our industry and in this publication are not in alignment with the
movement toward inclusive language in technology. We are proactively
collaborating with industry peers to find alternatives to such terms and
making changes to our products and content. Please excuse the use of such
terms in our content while we implement these changes.
Download Firmware, AOP,
EDS, and Other Files
Download firmware, associated files (such as AOP, EDS, and DTM), and access
product release notes from the Product Compatibility and Download Center at
rok.auto/pcdc.
Summary of Changes This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
Who Should Use this Manual This manual is intended for qualified personnel. You must be able to program
and operate Adjustable Frequency AC Drive devices. In addition, you must
have a working knowledge and understanding of ControlLogix®/Studio 5000®
and CIP Motion™.
If you do not have a basic understanding of the PowerFlex 527 drives, contact
your local Rockwell Automation sales representative for information on
available training courses.
Topic Page
Who Should Use this Manual 7
Additional Resources 8
Manual Conventions 8
Drive Frame Sizes 9
General Precautions 10
Catalog Number Explanation 11
Topic Page
Updated template Throughout
Added Inclusive Language acknowledgment 7
Added topic UKCA Conformity 13, 38
Added footnotes to table Altitude Limit (Based on Voltage) 16
Updated section Fuses and Circuit Breakers 20
Updated Fuse and Circuit Breaker tables for 140M/140MT and UL 61800-5-1 applications 21…25
Updated section General Considerations for UK LV Regulations 39, 40
Updated table PFD and PFH Data 87
Updated Certifications 127, 128
Updated table Dynamic Brake Resistors 138
Updated table EMC Line Filters in Appendix B 139
8 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Preface
Additional Resources All recommended documentation that is listed in this section is available
online at rok.auto/literature.
The following publications provide general information:
The following publications provide information on the use and configuration
of GuardLogix® 5570, CompactLogix™ 5370, ControlLogix 5580, GuardLogix
5580, and Compact GuardLogix 5370.
The following publications provide information on the use and configuration
of PowerFlex 527 drives on an EtherNet/IP network.
Manual Conventions In this manual we refer to PowerFlex 527 Adjustable Frequency AC Drive
as: drive, PowerFlex 527, PowerFlex 527 drive, or PowerFlex 527 AC drive.
Specific drives within the PowerFlex 520-series may be referred to as:
– PowerFlex 523, PowerFlex 523 drive, or PowerFlex 523 AC drive.
– PowerFlex 525, PowerFlex 525 drive, or PowerFlex 525 AC drive.
– PowerFlex 527, PowerFlex 527 drive, or PowerFlex 527 AC drive.
The following words are used throughout the manual to describe an
action:
Title Publication
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives DRIVES-IN001
Preventive Maintenance of Industrial Control and Drive System Equipment DRIVES-TD001
Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control SGI-1.1
Guarding Against Electrostatic Damage 8000-4.5.2
Industrial Automation Wiring and Grounding Guidelines 1770-4.1
Product Certifications website, rok.auto/certifications
Title Publication
GuardLogix 5570 Controllers User Manual 1756-UM022
GuardLogix 5570 and Compact GuardLogix 5370 Safety Reference Manual 1756-RM099
CompactLogix 5370 Controllers User Manual 1769-UM021
ControlLogix 5580 and GuardLogix 5580 Controllers User Manual 1756-UM543
Compact GuardLogix 5370 Controllers User Manual 1769-UM022
PowerFlex Dynamic Braking Resistor Calculator Application Technique PFLEX-AT001
Title Publication
Integrated Motion on the EtherNet/IP Network Configuration and Startup User Manual MOTION-UM003
Integrated Motion on the EtherNet/IP Network MOTION-RM003
Words Meaning
Can Possible, able to do something
Cannot Not possible, not able to do something
May Permitted, allowed
Must Unavoidable, you must do this
Shall Required and necessary
Should Recommended
Should Not Not recommended
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 9
Preface
The Studio 5000 Automation Engineering and Design Environment®
(formerly RSLogix 5000®) combines engineering and design elements
into one standard framework that enables optimized productivity and
reduced time to commission. As part of the Studio 5000 environment,
Studio 5000 Logix Designer® application is the tool that is used to
program Logix programmable automation controllers for process, batch,
discrete, drives, safety, and motion-based systems. The Studio 5000
environment is the foundation for system engineering design tools and
capabilities — it is the one tool for engineers to design and develop all
elements of their control system.
These conventions are used throughout this manual:
Bulleted lists such as this one provide information, not procedural steps.
Numbered lists provide steps or hierarchical information.
Drive Frame Sizes The PowerFlex 527 AC drive belongs to the new generation of PowerFlex 520-
series drives, which also consist of PowerFlex 523 and PowerFlex 525 drives.
Similar PowerFlex 520-series drive sizes are grouped into frame sizes to
simplify spare parts ordering, dimensioning, and so on. A cross-reference of
drive catalog numbers and their respective frame sizes is provided in
Appendix B on page 137
.
10 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Preface
General Precautions
ATTENTION: The drive contains high-voltage capacitors, which take time to
discharge after removal of mains supply. Before working on drive, verify
isolation of mains supply from line inputs [R, S, T (L1, L2, L3)]. Wait three
minutes for capacitors to discharge to safe voltage levels (DC Bus voltage is
less than 50V DC). Failure to do so may result in personal injury or death.
Darkened display LEDs is not an indication that capacitors have discharged
to safe voltage levels.
ATTENTION: Only qualified personnel familiar with adjustable frequency AC
drives and associated machinery should plan or implement the installation,
start-up and subsequent maintenance of the system. Failure to comply may
result in personal injury and/or equipment damage.
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive
parts and assemblies. Static control precautions are required when
installing, testing, servicing, or repairing this assembly. Component damage
may result if ESD control procedures are not followed. If you are not familiar
with static control procedures, reference publication 8000-4.5.2
, “Guarding
Against Electrostatic Damage” or any other applicable ESD protection
handbook.
ATTENTION: An incorrectly applied or installed drive can result in
component damage or a reduction in product life. Wiring or application
errors, such as undersizing the motor, incorrect or inadequate AC supply, or
excessive ambient temperatures may result in malfunction of the system.
ATTENTION: The bus regulator function is extremely useful for preventing
nuisance overvoltage faults resulting from aggressive decelerations,
overhauling loads, and eccentric loads. However, it can also cause either of
the following two conditions to occur.
1. Fast positive changes in input voltage or imbalanced input voltages can
cause uncommanded positive speed changes.
2. Actual deceleration times can be longer than commanded deceleration
times.
However, a “Decel Override” fault is generated if the drive remains in this
state for one minute. If this condition is unacceptable, the bus regulator
must be disabled by setting the Bus Regulator Action in the Logix Designer
application. In addition, installing a properly sized dynamic brake resistor
provides equal or better performance in most cases. See Dynamic Brake
Resistors on page 138 to select an appropriate resistor for your drive rating.
ATTENTION: Risk of injury or equipment damage exists. Drive does not
contain user-serviceable components. Do not disassemble drive chassis.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 11
Preface
Catalog Number Explanation
Code Type
25C PowerFlex 527
1-3 4 5 6-8 9 10 11 12 13 14
25C B 2P3 N 1 1 4
Drive Dash Voltage Rating Rating Enclosure Reserved Emission Class Reserved Dash Dash
Output Current @ 1 Phase, 100...120V Input
Code Amps Frame
ND HD
HP kW HP kW
2P5
(1)
2.5 A 0.50.40.50.4
4P8
(1)
4.8 B 1.0 0.75 1.0 0.75
6P0
(1)
6.0 B 1.5 1.1 1.5 1.1
Output Current @ 1 Phase, 200...240V Input
Code Amps Frame
ND HD
HP kW HP kW
2P5
(1)
2.5 A 0.50.40.50.4
4P8
(1)
4.8 A 1.0 0.75 1.0 0.75
8P0
(1)
8.0 B 2.0 1.5 2.0 1.5
011
(1)
11.0 B 3.0 2.2 3.0 2.2
Output Current @ 3Phase, 200...240V Input
Code Amps Frame
ND HD
HP kW HP kW
2P5
(1)
2.5 A 0.50.40.50.4
5P0
(1)
5.0 A 1.0 0.75 1.0 0.75
8P0
(1)
8.0 A 2.0 1.5 2.0 1.5
011
(1)
11.0 A 3.0 2.2 3.0 2.2
017
(1)
17.5 B 5.0 4.0 5.0 4.0
024
(1)
24.0 C 7.5 5.5 7.5 5.5
032
(1)
32.2 D 10.0 7.5 10.0 7.5
048
(2)
48.3 E 15.0 11.0 10.0 7.5
Output Current @ 3 Phase, 380...480V Input
Code Amps Frame
ND HD
HP kW HP kW
1P4
(1)
1.4 A 0.5 0.4 0.5 0.4
2P3
(1)
2.3 A 1.0 0.75 1.0 0.75
4P0
(1)
4.0 A 2.0 1.5 2.0 1.5
6P0
(1)
6.0 A 3.0 2.2 3.0 2.2
010
(1)
10.5 B 5.0 4.0 5.0 4.0
013
(1)
13.0 C 7.5 5.5 7.5 5.5
017
(1)
17.0 C 10.0 7.5 10.0 7.5
024
(1)
24.0 D 15.0 11.0 15.0 11.0
030
(2)
30.0 D 20.0 15.0 15.0 11.0
037
(2)
37.0 E 25.0 18.5 20.0 15.0
043
(2)
43.0 E 30.0 22.0 25.0 18.5
Output Current @ 3 Phase, 525...600V Input
Code Amps Frame
ND HD
HP kW HP kW
0P9
(1)
0.9 A 0.5 0.4 0.5 0.4
1P7
(1)
1.7 A 1.0 0.75 1.0 0.75
3P0
(1)
3.0 A 2.0 1.5 2.0 1.5
4P2
(1)
4.2 A 3.0 2.2 3.0 2.2
6P6
(1)
6.6 B 5.0 4.0 5.0 4.0
9P9
(1)
9.9 C 7.5 5.5 7.5 5.5
012
(1)
12.0 C 10.0 7.5 10.0 7.5
019
(1)
19.0 D 15.0 11.0 15.0 11.0
022
(2)
22.0 D 20.0 15.0 15.0 11.0
Code Voltage Phase
V120V AC1
A240V AC1
B240V AC3
D480V AC3
E600V AC3
Code Enclosure
NIP20 NEMA / Open
Code Interface Module
1Standard
Code EMC Filter
0 No Filter
1 Filter
Code Braking
4Standard
(1) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(2) 110% Overload capability for up to 60 s, 150% for up to 3 s.
12 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Preface
Notes:
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 13
Chapter
Chapter 1
Installation/Wiring
This chapter provides information on mounting and wiring the PowerFlex 527
drives.
Most startup difficulties are the result of incorrect wiring. Every precaution
must be taken to verify that the wiring is done as instructed. All items must be
read and understood before the actual installation begins.
Mounting Considerations Mount the drive upright on a flat, vertical, and level surface.
Protect the cooling fan by avoiding dust or metallic particles.
Do not expose to a corrosive atmosphere.
Protect from moisture and direct sunlight.
Topic Page
Mounting Considerations 13
AC Supply Source Considerations 17
General Grounding Requirements 18
Fuses and Circuit Breakers 20
Power and Control Module 26
Control Module Cover 29
Power Module Terminal Guard 29
Power Wiring 30
Power Terminal Block 33
I/O Wiring 33
Control I/O Terminal Block 34
CE Conformity 37
UKCA Conformity 38
ATTENTION: The following information is merely a guide for proper
installation. Rockwell Automation cannot assume responsibility for the
compliance or the noncompliance to any code, national, local or otherwise
for the proper installation of this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if codes are ignored during
installation.
Frame Screw Size Screw Torque
A M5 (#10…24) 1.56…1.96 N•m (14…17 lb•in)
B M5 (#10…24) 1.56…1.96 N•m (14…17 lb•in)
C M5 (#10…24) 1.56…1.96 N•m (14…17 lb•in)
D M5 (#10…24) 2.45…2.94 N•m (22…26 lb•in)
E M8 (5/16 in) 6.0…7.4 N•m (53…65 lb•in)
14 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
Minimum Mounting Clearances
For mounting dimensions, see Product Dimensions on page 144.
(1) For Frame E with Control Module Fan Kit only, clearance of 95 mm (3.7 in.) is required.
(2) For Frame E with Control Module Fan Kit only, clearance of 12 mm (0.5 in.) is required.
Vertical, Zero Stacking
No clearance between drives.
Horizontal, Zero Stacking with
Control Module Fan Kit
No clearance between drives.
Vertical Vertical, Zero Stacking with
Control Module Fan Kit
No clearance between drives.
Vertical with Control Module Fan Kit
Horizontal with Control Module Fan Kit
25 mm
(1.0 in.)
25 mm
(1.0 in.)
(2)
(2)
25 mm
(1.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
(1)
50 mm
(2.0 in.)
(1)
50 mm
(2.0 in.)
(1)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
(1)
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 15
Chapter 1 Installation/Wiring
Ambient Operating Temperatures
For optional accessories and kits, see Accessories and Dimensions on page 137.
Current Derating Curves
Vertical Mounting
Horizontal/Floor Mounting
Mounting Enclosure Rating
(1)
Ambient Temperature
Minimum Maximum (No Derate) Maximum (Derate)
(2)
Maximum with
Control Module Fan Kit (Derate)
(3)(5)
Vertical
IP 20/Open Type
-20 °C (-4 °F)
50 °C (122 °F) 70 °C (158 °F)
IP 30/NEMA 1/UL Type 1 45 °C (113 °F) 55 °C (131 °F)
Vertical, Zero Stacking IP 20/Open Type 45 °C (113 °F) 65 °C (149 °F)
Horizontal with
Control Module Fan Kit
(4)(5)
IP 20/Open Type 50 °C (122 °F) 70 °C (158 °F)
Horizontal, Zero Stacking
with Control Module Fan Kit
(4)(5)
IP 20/Open Type 45 °C (113 °F) 65 °C (149 °F)
(1) IP 30/NEMA 1/UL Type 1 rating requires installation of the PowerFlex 520-Series IP 30/NEMA 1/UL Type 1 option kit, catalog number 25-JBAx.
(2) For catalogs 25C-D1P4N104 and 25C-E0P9N104, the temperature that is listed under the Maximum (Derate) column is reduced by 5 °C (9 °F) for all mounting methods.
(3) For catalogs 25C-D1P4N104 and 25C-E0P9N104, the temperature that is listed under the Maximum with Control Module Fan Kit (Derate) column is reduced by 10 °C (18 °F) for vertical and
vertical with zero stacking mounting methods only.
(4) Catalogs 25C-D1P4N104 and 25C-E0P9N104 cannot be mounted using either of the horizontal mounting methods.
(5) Requires installation of the PowerFlex 520-Series Control Module Fan Kit, catalog number 25-FANx-70C.
Single Drive Zero Stacking
Ambient Temperature (°C)
40
100
90
110
120
80
70
60
50
45403530
60 65 70 75 80
5550
Percentage of Rated Current (%)
IP 30/NEMA 1
with Control
Module Fan Kit
IP 20/Open Type
Ambient Temperature (°C)
40
100
90
110
120
80
70
60
50
45403530
60 65 70 75 80
5550
Percentage of Rated Current (%)
with Control
Module Fan Kit
IP 20/Open Type
Single Drive Zero Stacking
Ambient Temperature (°C)
40
100
90
120
110
80
70
60
50
30 35
70 75 80
60 6550 5540 45
Percentage of Rated Current (%)
with Control
Module Fan Kit
IP 20/Open Type
16 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
Derating Guidelines for High Altitude
The drive can be used without derating at a maximum altitude of
1000 m (3300 ft). If the drive is used above 1000 m (3300 ft):
Derate the maximum ambient temperature by 5 °C (9 °F) for every
additional 1000 m (3300 ft), subject to limits listed in Table 1
.
Or
Derate the output current by 10% for every additional 1000 m (3300 ft),
up to 3000 m (9900 ft), subject to limits listed in Table 1
.
High Altitude
Debris Protection
Take precautions to prevent debris from falling through the vents of the drive
housing during installation.
Storage
Store within an ambient temperature range of -40…+85 °C
(-140…+185 °F)
(1)
.
Store within a relative humidity range of 0…95%, noncondensing.
Do not expose to a corrosive atmosphere.
Table 1 - Altitude Limit (Based on Voltage)
Drive Rating
Center Ground (Wye Neutral)
(1)
(1) The circuit breaker that is used in the drive may have different altitude specifications. See publications 140UT-TD001 and
140-TD005
for more information.
Corner Ground, Impedance Ground,
or Ungrounded
(1)(2)
(2) Impedance Ground and Ungrounded limits are not evaluated as part of UL specifications.
100…120V 1-Phase 6000 m 6000 m
200…240V 1-Phase 2000 m 2000 m
200…240V 3-Phase 6000 m 2000 m
380…480V 3-Phase 4000 m 2000 m
525…600V 3-Phase 2000 m 2000 m
(1) The maximum ambient temperature for storing a Frame E drive is 70 °C (158 °F).
Altitude (m)
Percentage of Rated Current (%)
40
90
100
110
120
80
70
60
50
0
4000
300020001000
Altitude (m)
Ambient Temperature (°C)
20
50
60
40
30
0
4000
300020001000
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 17
Chapter 1 Installation/Wiring
AC Supply Source
Considerations
Ungrounded Distribution Systems
Disconnecting MOVs
To help prevent drive damage, the MOVs connected to ground shall be
disconnected if the drive is installed on an ungrounded distribution system (IT
mains) where the line-to-ground voltages on any phase could exceed 125% of
the nominal line-to-line voltage. To disconnect these devices, remove the
jumper that is shown in the following diagrams.
1. Turn the screw counterclockwise to loosen.
2. Pull the jumper completely out of the drive chassis.
3. Tighten the screw to keep it in place.
Jumper Location (Typical)
Phase to Ground MOV Removal
ATTENTION:
PowerFlex 527 drives contain protective MOVs that are referenced to ground.
These devices must be disconnected if the drive is installed on an
ungrounded or resistive grounded distribution system.
Removing MOVs in drives with an embedded filter will also disconnect the
filter capacitor from earth ground.
IMPORTANT Tighten screw after jumper removal.
Power module
R/L1
S/L2
T/L3
1234
3-phase
AC input
Jumper
18 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
Input Power Conditioning
The drive is suitable for direct connection to input power within the rated
voltage of the drive (see Technical Specifications
on page 129). Listed in Table 2
are certain input power conditions which may cause component damage or
reduction in product life. If any of these conditions exist, install one of the
devices that are listed under the heading Corrective Action on the line side of
the drive.
General Grounding
Requirements
The drive Safety Ground - (PE) must be connected to system ground.
Ground impedance must conform to the requirements of national and local
industrial safety regulations and/or electrical codes. The integrity of all ground
connections should be periodically checked.
Typical Grounding
Ground Fault Monitoring
If a system ground fault monitor (RCD) is to be used, only Type B (adjustable)
devices should be used to avoid nuisance tripping.
IMPORTANT Only one device per branch circuit is required. It should be mounted
closest to the branch and sized to handle the total current of the branch
circuit.
Table 2 - Input Power Conditions
Input Power Condition Corrective Action
Low Line Impedance (less than 1% line reactance)
Install Line Reactor.
(1)
or
Install Isolation Transformer.
(1) See Accessories and Dimensions on page 137 for accessory ordering information.
Greater than 120 kVA supply transformer
Line has power factor correction capacitors
Install Line Reactor.
(1)
or
Install Isolation Transformer.
Line has frequent power interruptions
Line has intermittent noise spikes in excess of 6000V (lightning)
Phase to ground voltage exceeds 125% of normal line-to-line voltage Remove MOV jumper to ground.
or
Install Isolation Transformer with
grounded secondary if necessary.
Ungrounded distribution system
240V open delta configuration (stinger leg)
(2)
(2) For drives applied on an open delta with a middle phase grounded neutral system, the phase opposite the phase that is
tapped in the middle to the neutral or earth is referred to as the “stinger leg,” “high leg,” “red leg,” and so on. This leg should
be identified throughout the system with red or orange tape on the wire at each connection point. The stinger leg should be
connected to the center Phase B on the reactor. See Bulletin 1321-3R Series Line Reactors
on page 143 for specific line
reactor part numbers.
Install Line Reactor.
(1)
SHLD
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 19
Chapter 1 Installation/Wiring
Safety Ground - (PE)
This is the safety ground for the drive that is required by code. One of these
points must be connected to adjacent building steel (girder, joist), a floor
ground rod, or busbar. Grounding points must comply with national and local
industrial safety regulations and/or electrical codes.
Motor Ground
The motor ground must be connected to one of the ground terminals on the
drive.
Shield Termination - SHLD
Either of the safety ground terminals that are located on the power terminal
block provides a grounding point for the motor cable shield. The motor cable
shield connected to one of these terminals (drive end) should also be
connected to the motor frame (motor end). Use a shield terminating or EMI
clamp to connect the shield to the safety ground terminal. The earthing plate
or conduit box option may be used with a cable clamp for a grounding point
for the cable shield.
When shielded cable is used for control and signal wiring, the shield should be
grounded at the source end only, not at the drive end.
RFI Filter Grounding
Using a drive with filter may result in relatively high ground leakage currents.
Therefore, the filter must only be used in installations with grounded AC
supply systems and be permanently installed and solidly grounded (bonded)
to the building power distribution ground. Verify that the incoming supply
neutral is solidly connected (bonded) to the same building power distribution
ground. Grounding must not rely on flexible cables and should exclude any
form of plug or socket that would permit inadvertent disconnection. Some
local codes may require redundant ground connections. The integrity of all
connections should be periodically checked.
20 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
Fuses and Circuit Breakers The PowerFlex 527 drive does not provide branch short circuit protection. This
product should be installed with either input fuses or an input circuit breaker.
National and local industrial safety regulations and/or electrical codes may
determine additional requirements for these installations.
The tables under Fuses and Circuit Breakers for PowerFlex 527
on page 21
provide recommended AC line input fuse and circuit breaker information. See
Fusing and Circuit Breakers below for UL and IEC requirements. Sizes that are
listed are the recommended sizes based on 40 °C(104 °F) and the U.S. N.E.C.
Other country, state, or local codes may require different ratings.
Fusing
The recommended fuse types are listed in the tables under Fuses and Circuit
Breakers for PowerFlex 527 on page 21. If available current ratings do not
match those listed in the tables provided, choose the next higher fuse rating.
IEC – BS88 (British Standard) Parts 1 & 2
(1)
, EN60269-1, Parts 1 & 2, type
GG or equivalent should be used.
UL – UL Class CC, T, or J should be used.
Circuit Breakers
The “non-fuse” listings in the tables under Fuses and Circuit Breakers for
PowerFlex 527 on page 21 include inverse time circuit breakers, instantaneous
trip circuit breakers (motor circuit protectors), and 140M/140MT self-protected
combination motor controllers. If one of these is chosen as the desired
protection method, the following requirements apply:
IEC – Both types of circuit breakers and 140M/140MT self-protected
combination motor controllers are acceptable for IEC installations.
UL – Only inverse time circuit breakers and the specified 140M/140MT
self-protected combination motor controllers are acceptable for UL
installations.
Bulletin 140M/140MT (Self-Protected Combination Controller)/UL489 Circuit Breakers
When using Bulletin 140M/140MT or UL489 rated circuit breakers, the
following guidelines that are listed must be followed to meet the NEC
requirements for branch circuit protection.
Bulletin 140M/140MT can be used in single motor applications.
Bulletin 140M/140MT can be used up stream from the drive without the
need for fuses.
If the DC Bus terminals or the Dynamic Brake terminals are used, the drive
must be installed in an enclosure and fuses must be used for input protection
(for CE applications only). The ventilated enclosure needs to be IP 20 rating or
higher and at least 1.5x size larger than the drive.
(1) Typical designations include, but may not be limited to the following;
Parts 1 & 2: AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 21
Chapter 1 Installation/Wiring
Fuses and Circuit Breakers for PowerFlex 527
100...120V 1-Phase Input Protection Devices – Frames A...B — IEC (Non-UL) Applications
Catalog No.
(1)
Output Ratings Input Ratings
Frame Size
Contactor
Cat. No.
IEC (Non-UL) Applications
ND HD
AkVA
Max Current A
(2)
Fuses (Rating) Circuit Breakers
Hp kW Hp kW Min Max 140U
140M/140MT
(3)(4)(5)
25C-V2P5N104 0.5 0.4 0.5 0.4 2.5 1.3 9.6 A 100-C12 15 20 140U-D6D2-C12
140M-C2E-C10
140MT-D9E-C10
25C-V4P8N104 1.0 0.75 1.0 0.75 4.8 2.5 19.2 B 100-C23 25 40 140U-D6D2-C25
140M-D8E-C20
140MT-D9E-C20
25C-V6P0N104 1.5 1.1 1.5 1.1 6.0 3.2 24.0 B 100-C23 30 50 140U-D6D2-C30 140M-F8E-C25
(1) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(2) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(3) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005
or 140M-TD002.
(4) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 480Y/277 and 600Y/347 AC input. Not UL Listed for use on 480V or 600V Delta/Delta, corner ground, or high-
resistance ground systems.
100...120V 1-Phase Input Protection Devices – Frames A...B — UL 61800-5-1 Applications
Catalog No.
(1)
Output Ratings Input Ratings
Frame
Size
Contactor
Cat. No.
UL 61800-5-1 Applications
ND HD
AkVA
Max Current A
(2)
Fuses (Max. Rating) Circuit Breakers
Hp kW Hp kW Class / Catalog No. 140UT
140M/140MT
(3)(4)(5)
25C-V2P5N104 0.5 0.4 0.5 0.4 2.5 1.3 9.6 A 100-C12 CLASS CC, J, or T/20 140UT-D7D2-C12
140MT-C3E-C10
140MT-D9E-C10
25C-V4P8N104 1.0 0.75 1.0 0.75 4.8 2.5 19.2 B 100-C23 CLASS CC, J, or T/40
(6)
140MT-D9E-C20
25C-V6P0N104 1.5 1.1 1.5 1.1 6.0 3.2 24.0 B 100-C23 CLASS CC, J, or T/50
(6)
140M-F8E-C25
(1) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(2) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(3) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005
or 140M-TD002.
(4) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 480Y/277 and 600Y/347 AC input. Not UL Listed for use on 480V or 600V Delta/Delta, corner ground, or high-
resistance ground systems.
(6) Circuit breaker selection is not available for this drive rating.
200...240V 1-Phase Input Protection Devices – Frames A...B — IEC (Non-UL) Applications
Catalog No.
(1)
Output Ratings Input Ratings
Frame Size
Contactor
Cat. No.
IEC (Non-UL) Applications
ND HD
AkVA
Max Current A
(2)
Fuses (Rating) Circuit Breakers
Hp kW Hp kW Min Max 140U
140M/140MT
(3)(4)(5)
25C-A2P5N104 0.5 0.4 0.5 0.4 2.5 1.7 6.5 A 100-C09 10 15 140U-D6D2-C10
140M-C2E-C10
140MT-D9E-C10
25C-A2P5N114 0.5 0.4 0.5 0.4 2.5 1.7 6.5 A 100-C09 10 15 140U-D6D2-C10
140M-C2E-C10
140MT-D9E-C10
25C-A4P8N104 1.0 0.75 1.0 0.75 4.8 2.8 10.7 A 100-C12 15 25 140U-D6D2-C15
140M-C2E-C16
140MT-D9E-C16
25C-A4P8N114 1.0 0.75 1.0 0.75 4.8 2.8 10.7 A 100-C12 15 25 140U-D6D2-C15
140M-C2E-C16
140MT-D9E-C16
25C-A8P0N104 2.0 1.5 2.0 1.5 8.0 4.8 18.0 B 100-C23 25 40 140U-D6D2-C25 140M-F8E-C25
25C-A8P0N114 2.0 1.5 2.0 1.5 8.0 4.8 18.0 B 100-C23 25 40 140U-D6D2-C25 140M-F8E-C25
25C-A011N104 3.0 2.2 3.0 2.2 11.0 6.0 22.9 B 100-C37 30 50 140U-H6C2-C35 140M-F8E-C25
25C-A011N114 3.0 2.2 3.0 2.2 11.0 6.0 22.9 B 100-C37 30 50 140U-H6C2-C35 140M-F8E-C25
(1) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(2) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(3) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005
or 140M-TD002.
(4) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 480Y/277 and 600Y/347 AC input. Not UL Listed for use on 480V or 600V Delta/Delta, corner ground, or high-
resistance ground systems.
22 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
200...240V 1-Phase Input Protection Devices – Frames A...B — UL 61800-5-1 Applications
Catalog No.
(1)
Output Ratings Input Ratings
Frame
Size
Contactor
Cat. No.
UL 61800-5-1 Applications
ND HD
AkVA
Max
Current
A
(2)
Fuses (Max. Rating) Circuit Breakers
Hp kW Hp kW Class / Catalog No. 140UT
140M/140MT
(3)(4)(5)
25C-A2P5N104 0.5 0.4 0.5 0.4 2.5 1.7 6.5 A 100-C09 CLASS CC, J, or T/15 140UT-D7D2-C10 140MT-D9E-C10
25C-A2P5N114 0.5 0.4 0.5 0.4 2.5 1T.7 6.5 A 100-C09 CLASS CC, J, or T/15 140UT-D7D2-C10 140MT-D9E-C10
25C-A4P8N104 1.0 0.75 1.0 0.75 4.8 2.8 10.7 A 100-C12 CLASS CC, J, or T/25 140UT-D7D2-C15 140MT-D9E-C16
25C-A4P8N114 1.0 0.75 1.0 0.75 4.8 2.8 10.7 A 100-C12 CLASS CC, J, or T/25 140UT-D7D2-C15 140MT-D9E-C16
25C-A8P0N104 2.0 1.5 2.0 1.5 8.0 4.8 18.0 B 100-C23 CLASS CC, J, or T/40
(6)
140M-F8E-C25
25C-A8P0N114 2.0 1.5 2.0 1.5 8.0 4.8 18.0 B 100-C23 CLASS CC, J, or T/40
(6)
140M-F8E-C25
25C-A011N104 3.0 2.2 3.0 2.2 11.0 6.0 22.9 B 100-C37 CLASS CC, J, or T/50
(6)
140M-F8E-C25
25C-A011N114 3.0 2.2 3.0 2.2 11.0 6.0 22.9 B 100-C37 CLASS CC, J, or T/50
(6)
140M-F8E-C25
(1) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(2) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(3) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005
or 140M-TD002.
(4) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 480Y/277 and 600Y/347 AC input. Not UL Listed for use on 480V or 600V Delta/Delta, corner ground, or high-
resistance ground systems.
(6) Circuit breaker selection is not available for this drive rating.
200...240V 3-Phase Input Protection Devices – Frames A...B — IEC (Non-UL) Applications
Catalog No.
Output Ratings Input Ratings
Frame Size
Contactor
Cat. No.
IEC (Non-UL) Applications
ND HD
AkVA
Max Current
A
(1)
Fuses (Rating) Circuit Breakers
Hp kW Hp kW Min Max 140U
140M/140MT
(2)(3)(4)
25C-B2P5N104
(5)
0.5 0.4 0.5 0.4 2.5 1.2 2.7 A 100-C07 6 6 140U-D6D3-B40
140M-C2E-B40
140MT-D9E-B40
25C-B5P0N104
(5)
1.0 0.75 1.0 0.75 5.0 2.7 5.8 A 100-C09 10 15 140U-D6D3-B80
140M-C2E-B63
140MT-D9E-B63
25C-B8P0N104
(5)
2.0 1.5 2.0 1.5 8.0 4.3 9.5 A 100-C12 15 20 140U-D6D3-C10
140M-C2E-C10
140MT-D9E-C10
25C-B011N104
(5)
3.0 2.2 3.0 2.2 11.0 6.3 13.8 A 100-C23 20 30 140U-D6D3-C15
140M-C2E-C16
140MT-D9E-C16
25C-B017N104
(5)
5.0 4.0 5.0 4.0 17.5 9.6 21.1 B 100-C23 30 45 140U-D6D3-C25 140M-F8E-C25
25C-B024N104
(5)
7.5 5.5 7.5 5.5 24.0 12.2 26.6 C 100-C37 35 60 140U-H6C3-C35 140M-F8E-C32
25C-B032N104
(5)
10.0 7.5 10.0 7.5 32.2 15.9 34.8 D 100-C43 45 70 140U-H6C3-C60 140M-F8E-C45
25C-B048N104
(6)
15.0 11.0 10.0 7.5 48.3 20.1 44.0 E 100-C60 60 90 140U-H6C3-C70 140M-F8E-C45
25C-B062N104
(6)
20.0 15.0 15.0 11.0 62.1 25.6 56.0 E 100-C72 70 125 140U-H6C3-C90 140M-H8P-C70
(1) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(2) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005
or 140M-TD002.
(3) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(4) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 480Y/277 and 600Y/347 AC input. Not UL Listed for use on 480V or 600V Delta/Delta, corner ground, or high-
resistance ground systems.
(5) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(6) 110% Overload capability for up to 60 s, 150% for up to 3 s.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 23
Chapter 1 Installation/Wiring
200...240V 3-Phase Input Protection Devices – Frames A...E — UL 61800-5-1 Applications
Catalog No.
Output Ratings Input Ratings
Frame
Size
Contactor
Cat. No.
UL 61800-5-1 Applications
ND HD
AkVA
Max Current
A
(1)
Fuses (Max. Rating) Circuit Breakers
Hp kW Hp kW Class / Catalog No. 140UT
140M/140MT
(2)(3)(4)
25C-B2P5N104
(5)
0.5 0.4 0.5 0.4 2.5 1.2 2.7 A 100-C07 CLASS CC, J, or T/6 140UT-D7D3-B40 140MT-D9E-B40
25C-B5P0N104
(5)
1.0 0.75 1.0 0.75 5.0 2.7 5.8 A 100-C09 CLASS CC, J, or T/15 140UT-D7D3-B80 140MT-D9E-B63
25C-B8P0N104
(5)
2.0 1.5 2.0 1.5 8.0 4.3 9.5 A 100-C12 CLASS CC, J, or T/20 140UT-D7D3-C10 140MT-D9E-C10
25C-B011N104
(5)
3.0 2.2 3.0 2.2 11.0 6.3 13.8 A 100-C23 CLASS CC, J, or T/30 140UT-D7D3-C15 140MT-D9E-C16
25C-B017N104
(5)
5.0 4.0 5.0 4.0 17.5 9.6 21.1 B 100-C23 CLASS CC, J, or T/45 140UT-D7D3-C25 140M-F8E-C25
25C-B024N104
(5)
7.5 5.5 7.5 5.5 24.0 12.2 26.6 C 100-C37 CLASS CC, J, or T/60
(6)
140M-F8E-C32
25C-B032N104
(5)
10.0 7.5 10.0 7.5 32.2 15.9 34.8 D 100-C43 CLASS CC, J, or T/70
(6)
140M-F8E-C45
25C-B048N104
(7)
15.0 11.0 10.0 7.5 48.3 20.1 44.0 E 100-C60 CLASS CC, J, or T/90
(6)
140M-F8E-C45
25C-B062N104
(7)
20.0 15.0 15.0 11.0 62.1 25.6 56.0 E 100-C72 CLASS CC, J, or T/125
(6)
140M-H8P-C70
(1) When the drive is controlling motors with lower amp ratings, refer to the drive nameplate for drive input current rating.
(2) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005
or 140M-TD002.
(3) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(4) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 480Y/277 and 600Y/347 AC input. Not UL Listed for use on 480V or 600V Delta/Delta, corner ground, or high-
resistance ground systems.
(5) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(6) Circuit breaker selection is not available for this drive rating.
(7) 110% Overload capability for up to 60 s, 150% for up to 3 s.
380...480V 3-Phase Input Protection Devices – Frames A...E— IEC (Non-UL) Applications
Catalog No
Output Ratings Input Ratings
Frame
Size
Contactor
Cat. No.
IEC (Non-UL) Applications
ND HD
AkVA
Max Current A
(1)
Fuses (Rating) Circuit Breakers
Hp kW Hp kW Min Max 140U
140M/MT
(2)(3)(4)
25C-D1P4N104
(5)
0.5 0.4 0.5 0.4 1.4 1.7 1.9 A 100-C07 3 6 140U-D6D3-B30
140M-C2E-B25
140MT-C3E-B25
25C-D1P4N114
(5)
0.5 0.4 0.5 0.4 1.4 1.7 1.9 A 100-C07 3 6 140U-D6D3-B30
140M-C2E-B25
140MT-C3E-B25
25C-D2P3N104
(5)
1.0 0.75 1.0 0.75 2.3 2.9 3.2 A 100-C07 6 10 140U-D6D3-B60
140M-C2E-B40
140MT-C3E-B40
25C-D2P3N114
(5)
1.0 0.75 1.0 0.75 2.3 2.9 3.2 A 100-C07 6 10 140U-D6D3-B60
140M-C2E-B40
140MT-C3E-B40
25C-D4P0N104
(5)
2.0 1.5 2.0 1.5 4.0 5.2 5.7 A 100-C09 10 15 140U-D6D3-B60
140M-C2E-B63
40MT-C3E-B63
25C-D4P0N114
(5)
2.0 1.5 2.0 1.5 4.0 5.2 5.7 A 100-C09 10 15 140U-D6D3-B60
140M-C2E-B63
40MT-C3E-B63
25C-D6P0N104
(5)
3.0 2.2 3.0 2.2 6.0 6.9 7.5 A 100-C09 10 15 140U-D6D3-C10
140M-C2E-C10
140MT-C3E-C10
25C-D6P0N114
(5)
3.0 2.2 3.0 2.2 6.0 6.9 7.5 A 100-C09 10 15 140U-D6D3-C10
140M-C2E-C10
140MT-C3E-C10
25C-D010N104
(5)
5.0 4.0 5.0 4.0 10.5 12.6 13.8 B 100-C23 20 30 140U-D6D3-C15
140M-C2E-C16
140MT-D9E-C16
25C-D010N114
(5)
5.0 4.0 5.0 4.0 10.5 12.6 13.8 B 100-C23 20 30 140U-D6D3-C15
140M-C2E-C16
140MT-D9E-C16
25C-D013N104
(5)
7.5 5.5 7.5 5.5 13.0 14.1 15.4 C 100-C23 20 35 140U-D6D3-C25
140M-D8E-C20
140MT-D9E-C20
25C-D013N114
(5)
7.5 5.5 7.5 5.5 13.0 14.1 15.4 C 100-C23 20 35 140U-D6D3-C25
140M-D8E-C20
140MT-D9E-C20
25C-D017N104
(5)
10.0 7.5 10.0 7.5 17.0 16.8 18.4 C 100-C23 25 40 140U-D6D3-C25
140M-D8E-C20
140MT-D9E-C20
25C-D017N114
(5)
10.0 7.5 10.0 7.5 17.0 16.8 18.4 C 100-C23 25 40 140U-D6D3-C25
140M-D8E-C20
140MT-D9E-C20
25C-D024N104
(5)
15.0 11.0 15.0 11.0 24.0 24.1 26.4 D 100-C37 35 60 140U-H6C3-C40 140M-F8E-C32
25C-D024N114
(5)
15.0 11.0 15.0 11.0 24.0 24.1 26.4 D 100-C37 35 60 140U-H6C3-C40 140M-F8E-C32
25C-D030N104
(6)
20.0 15.0 15.0 11.0 30.0 30.2 33.0 D 100-C43 45 70 140U-H6C3-C50 140M-F8E-C45
25C-D030N114
(6)
20.0 15.0 15.0 11.0 30.0 30.2 33.0 D 100-C43 45 70 140U-H6C3-C50 140M-F8E-C45
25C-D037N114
(6)
25.0 18.5 20.0 15.0 37.0 30.8 33.7 E 100-C43 45 70 140U-H6C3-C50 140M-F8E-C45
25C-D043N114
(6)
30.0 22.0 25.0 18.5 43.0 35.6 38.9 E 100-C60 50 80 140U-H6C3-C60 140M-F8E-C45
24 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
(1) When the drive is controlling motors with lower ampere ratings, see the drive nameplate for drive input current rating.
(2) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005 or 140M-TD002.
(3) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(4) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 480Y/277 and 600Y/347 AC input. Not UL Listed for use on 480V or 600V Delta/Delta, corner ground, or high-
resistance ground systems.
(5) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(6) 110% Overload capability for up to 60 s, 150% for up to 3 s.
380…480V 3-Phase Input Protection Devices – Frames A…E — UL 61800-5-1 Applications
Catalog No.
Output Ratings Input Ratings
Frame
Size
Contactor
Cat. No.
UL 61800-5-1 Applications
ND HD
AkVA
Max Current A
(1)
Fuses (Max Rating) Circuit Breakers
Hp kW Hp kW Class/Catalog No.
140UT
(2)
140M/MT
(3)(4)(5)
25C-D1P4N104
(6)
0.5 0.4 0.5 0.4 1.4 1.7 1.9 A 100-C07 CLASS CC, J, or T/6 140MT-C3E-B25
25C-D1P4N114
(6)
0.5 0.4 0.5 0.4 1.4 1.7 1.9 A 100-C07 CLASS CC, J, or T/6 140MT-C3E-B25
25C-D2P3N104
(6)
1.0 0.75 1.0 0.75 2.3 2.9 3.2 A 100-C07 CLASS CC, J, or T/10 140MT-C3E-B40
25C-D2P3N114
(6)
1.0 0.75 1.0 0.75 2.3 2.9 3.2 A 100-C07 CLASS CC, J, or T/10 140MT-C3E-B40
25C-D4P0N104
(6)
2.0 1.5 2.0 1.5 4.0 5.2 5.7 A 100-C09 CLASS CC, J, or T/15 140MT-C3E-B63
25C-D4P0N114
(6)
2.0 1.5 2.0 1.5 4.0 5.2 5.7 A 100-C09 CLASS CC, J, or T/15 140MT-C3E-B63
25C-D6P0N104
(6)
3.0 2.2 3.0 2.2 6.0 6.9 7.5 A 100-C09 CLASS CC, J, or T/15 140MT-C3E-C10
25C-D6P0N114
(6)
3.0 2.2 3.0 2.2 6.0 6.9 7.5 A 100-C09 CLASS CC, J, or T/15 140MT-C3E-C10
25C-D010N104
(6)
5.0 4.0 5.0 4.0 10.5 12.6 13.8 B 100-C23 CLASS CC, J, or T/30 140MT-D9E-C16
25C-D010N114
(6)
5.0 4.0 5.0 4.0 10.5 12.6 13.8 B 100-C23 CLASS CC, J, or T/30 140MT-D9E-C16
25C-D013N104
(6)
7.5 5.5 7.5 5.5 13.0 14.1 15.4 C 100-C23 CLASS CC, J, or T/35 140MT-D9E-C20
25C-D013N114
(6)
7.5 5.5 7.5 5.5 13.0 14.1 15.4 C 100-C23 CLASS CC, J, or T/35 140MT-D9E-C20
25C-D017N104
(6)
10.0 7.5 10.0 7.5 17.0 16.8 18.4 C 100-C23 CLASS CC, J, or T/40 140MT-D9E-C20
25C-D017N114
(6)
10.0 7.5 10.0 7.5 17.0 16.8 18.4 C 100-C23 CLASS CC, J, or T/40 140MT-D9E-C20
25C-D024N104
(6)
15.0 11.0 15.0 11.0 24.0 24.1 26.4 D 100-C37 CLASS CC, J, or T/60 140M-F8E-C32
25C-D024N114
(6)
15.0 11.0 15.0 11.0 24.0 24.1 26.4 D 100-C37 CLASS CC, J, or T/60 140M-F8E-C32
25C-D030N104
(7)
20.0 15.0 15.0 11.0 30.0 30.2 33.0 D 100-C43 CLASS CC, J, or T/70 140M-F8E-C45
25C-D030N114
(7)
20.0 15.0 15.0 11.0 30.0 30.2 33.0 D 100-C43 CLASS CC, J, or T/70 140M-F8E-C45
25C-D037N114
(7)
25.0 18.5 20.0 15.0 37.0 30.8 33.7 E 100-C43 CLASS CC, J, or T/70 140M-F8E-C45
25C-D043N114
(7)
30.0 22.0 25.0 18.5 43.0 35.6 38.9 E 100-C60 CLASS CC, J, or T/80 140M-F8E-C45
(1) When the drive is controlling motors with lower ampere ratings, see the drive nameplate for drive input current rating.
(2) Circuit breaker selection is not available for this drive rating.
(3) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005
or 140M-TD002.
(4) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 480Y/277 and 600Y/347 AC input. Not UL Listed for use on 480V or 600V Delta/Delta, corner ground, or high-
resistance ground systems.
(6) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(7) 110% Overload capability for up to 60 s, 150% for up to 3 s.
525…600V 3-Phase Input Protection Devices – Frames A…E — IEC (Non-UL) Applications
Catalog No.
Output Ratings Input Ratings
Frame
Size
Contactor
Cat. No.
IEC (Non-UL) Applications
ND HD
AkVA
Max Current A
(1)
Fuses (Rating) Circuit Breakers
Hp kW Hp kW Min Max 140U/140G
140M/MT
(2)(3)(4)
25C-E0P9N104
(5)
0.5 0.4 0.5 0.4 0.9 1.4 1.2 A 100-C09 3 6 140U-D6D3-B20
140M-C2E-B25
140MT-C3E-B25
25C-E1P7N104
(5)
1.0 0.75 1.0 0.75 1.7 2.6 2.3 A 100-C09 3 6 140U-D6D3-B30
140M-C2E-B25
140MT-C3E-B25
25C-E3P0N104
(5)
2.0 1.5 2.0 1.5 3.0 4.3 3.8 A 100-C09 6 10 140U-D6D3-B50
140M-C2E-B40
140MT-C3E-B40
25C-E4P2N104
(5)
3.0 2.2 3.0 2.2 4.2 6.1 5.3 A 100-C09 10 15 140U-D6D3-B80
140M-C2E-B63
140MT-D9E-B63
25C-E6P6N104
(5)
5.0 4.0 5.0 4.0 6.6 9.1 8.0 B 100-C09 10 20 140U-D6D3-C10
140M-C2E-C10
140MT-D9E-C10
25C-E9P9N104
(5)
7.5 5.5 7.5 5.5 9.9 12.8 11.2 C 100-C16 15 25 140U-D6D3-C15
140M-C2E-C16
140MT-D9E-C16
25C-E012N104
(5)
10.0 7.5 10.0 7.5 12.0 15.4 13.5 C 100-C23 20 30 140U-D6D3-C20
140M-C2E-C16
140MT-D9E-C16
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 25
Chapter 1 Installation/Wiring
25C-E019N104
(5)
15.0 11.0 15.0 11.0 19.0 27.4 24.0 D 100-C30 30 50 140U-H6C3-C30 140M-F8E-C25
25C-E022N104
(6)
20.0 15.0 15.0 11.0 22.0 31.2 27.3 D 100-C30 35 60 140U-H6C3-C35 140M-F8E-C32
25C-E027N104
(6)
25.0 18.5 20.0 15.0 27.0 28.2 24.7 E 100-C30 35 50 140U-H6C3-C35 140M-F8E-C32
25C-E032N104
(6)
30.0 22.0 25.0 18.5 32.0 33.4 29.2 E 100-C37 40 60 140U-H6C3-C50 140M-F8E-C32
(1) When the drive is controlling motors with lower ampere ratings, see the drive nameplate for drive input current rating.
(2) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005
or 140M-TD002.
(3) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(4) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 480Y/277 and 600Y/347 AC input. Not UL Listed for use on 480V or 600V Delta/Delta, corner ground, or high-
resistance ground systems.
(5) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(6) 110% Overload capability for up to 60 s, 150% for up to 3 s.
525…600V 3-Phase Input Protection Devices – Frames A…E — IEC (Non-UL) Applications (Continued)
Catalog No.
Output Ratings Input Ratings
Frame
Size
Contactor
Cat. No.
IEC (Non-UL) Applications
ND HD
AkVA
Max Current A
(1)
Fuses (Rating) Circuit Breakers
Hp kW Hp kW Min Max 140U/140G
140M/MT
(2)(3)(4)
525…600V 3-Phase Input Protection Devices – Frames A…E — UL 61800-5-1 Applications
Catalog No.
Output Ratings Input Ratings
Frame
Size
Contactor
Cat. No.
UL 61800-5-1 Applications
ND HD
AkVA
Max Current A
(1)
Fuses (Max Rating) Circuit Breakers
Hp kW Hp kW Class/Catalog No.
140UT
(2)
140M/MT
(3)(4)(5)
25C-E0P9N104
(6)
0.5 0.4 0.5 0.4 0.9 1.4 1.2 A 100-C09 CLASS CC, J, or T/6 140MT-C3E-B25
25C-E1P7N104
(6)
1.0 0.75 1.0 0.75 1.7 2.6 2.3 A 100-C09 CLASS CC, J, or T/6 140MT-C3E-B25
25C-E3P0N104
(6)
2.0 1.5 2.0 1.5 3.0 4.3 3.8 A 100-C09 CLASS CC, J, or T/10 140MT-C3E-B40
25C-E4P2N104
(6)
3.0 2.2 3.0 2.2 4.2 6.1 5.3 A 100-C09 CLASS CC, J, or T/15 140MT-D9E-B63
25C-E6P6N104
(6)
5.0 4.0 5.0 4.0 6.6 9.1 8.0 B 100-C09 CLASS CC, J, or T/20 140MT-D9E-C10
25C-E9P9N104
(6)
7.5 5.5 7.5 5.5 9.9 12.8 11.2 C 100-C16 CLASS CC, J, or T/25 140MT-D9E-C16
25C-E012N104
(6)
10.0 7.5 10.0 7.5 12.0 15.4 13.5 C 100-C23 CLASS CC, J, or T/30 140MT-D9E-C16
25C-E019N104
(6)
15.0 11.0 15.0 11.0 19.0 27.4 24.0 D 100-C30 CLASS CC, J, or T/50 140M-F8E-C25
25C-E022N104
(7)
20.0 15.0 15.0 11.0 22.0 31.2 27.3 D 100-C30 CLASS CC, J, or T/60 140M-F8E-C32
25C-E027N104
(7)
25.0 18.5 20.0 15.0 27.0 28.2 24.7 E 100-C30 CLASS CC, J, or T/50 140M-F8E-C32
25C-E032N104
(7)
30.0 22.0 25.0 18.5 32.0 33.4 29.2 E 100-C37 CLASS CC, J, or T/60 140M-F8E-C32
(1) When the drive is controlling motors with lower ampere ratings, see the drive nameplate for drive input current rating.
(2) Circuit breaker selection is not available for this drive rating.
(3) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication 140-TD005
or 140M-TD002.
(4) Bulletin 140M/MT with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(5) Manual Self-Protected (Type E) Combination Motor Controller, UL Listed for 208V Wye or Delta, 240V Wye or Delta, 480V Y/277 or 600V Y/347. Not UL Listed for use on 480V or 600V Delta/
Delta, corner ground, or high-resistance ground systems.
(6) 150% Overload capability for up to 60 s, 180% for up to 3 s.
(7) 110% Overload capability for up to 60 s, 150% for up to 3 s.
26 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
Power and Control Module
PowerFlex 527 drives consist of a Power Module and Control Module. This
section describes how to separate the two modules and reconnect them back
together, and also how to access the power terminals and control terminals. It
is assumed that your drive is new and has not been installed.
Separating the Power and Control Module
1. Press and hold down the catch on both sides of the frame cover, then pull
out and swing upwards to remove (Frames B…E only).
2. Press down and slide out the top cover of the Control Module to unlock it
from the Power Module.
ATTENTION: If you are performing these steps on a drive that has been
installed, verify that the drive is powered down and the DC Bus voltage is
less than 50V DC before proceeding.
1
2
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 27
Chapter 1 Installation/Wiring
3. Hold the sides and top of the Control Module firmly, then pull out to
separate it from the Power Module.
Connecting the Power and Control Module
1. Align the connectors on the Power Module and Control Module, then
push the Control Module firmly onto the Power Module.
28 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
2. Push the top cover of the Control Module towards the Power Module to
lock it.
3. Insert the catch at the top of the frame cover into the Power Module, then
swing the frame cover to snap the side catches onto the Power Module
(Frames B...E only).
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 29
Chapter 1 Installation/Wiring
Control Module Cover To access the control terminals, the front cover must be removed. To remove:
1. Press and hold down the arrow on the front of the cover.
2. Slide the front cover down to remove from the Control Module.
Reattach the front cover when wiring is complete.
Power Module Terminal
Guard
To access the power terminals, the terminal guard must be removed. To
remove:
1. Press and hold down the catch on both sides of the frame cover, then pull
out and swing upwards to remove (Frames B…E only).
.
2. Press and hold down the locking tab on the terminal guard.
1
2
30 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
3. Slide the terminal guard down to remove from the Power Module.
.
Reattach the terminal guard when wiring is complete.
To access the power terminals for Frame A, you need to separate the Power and
Control Modules. See Separating the Power and Control Module
on page 26 for
instructions.
Power Wiring For general wiring and grounding practices, see the Wiring and Grounding for
Pulse Width Modulated (PWM) AC Drives Installation Instructions,
publication DRIVES-IN001
.
Motor Cable Types Acceptable for 100…600 Volt Installations
A variety of cable types are acceptable for drive installations. For many
installations, unshielded cable is adequate, provided it can be separated from
sensitive circuits. As an approximate guide, allow a spacing of 0.3 m (1 ft) for
every 10 m (32.8 ft) of length. In all cases, long parallel runs must be avoided.
Do not use cable with an insulation thickness less than 15 mils (0.4 mm/0.015
in.). Do not route more than three sets of motor leads in one conduit to
minimize “cross talk. If more than three drive/motor connections per conduit
are required, shielded cable must be used.
UL installations above 50 °C (122 °F) ambient must use 600V, 90 °C
(194 °F) wire.
UL installations in 50 °C (122 °F) ambient must use 600V, 75 °C or 90 °C
(167 °F or 194 °F) wire.
UL installations in 40 °C (104 °F) ambient should use 600V, 75 °C or 90 °C
(167 °F or 194 °F) wire.
ATTENTION:
National Codes and standards (NEC, VDE, BSI, and so on) and local codes
outline provisions for safely installing electrical equipment. Installation must
comply with specifications regarding wire types, conductor sizes, branch
circuit protection, and disconnect devices. Failure to do so may result in
personal injury and/or equipment damage.
To avoid a possible shock hazard that is caused by induced voltages, unused
wires in the conduit must be grounded at both ends. For the same reason, if
a drive sharing a conduit is being serviced or installed, all drives using this
conduit should be disabled. This will help minimize the possible shock
hazard from “cross coupled” power leads.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 31
Chapter 1 Installation/Wiring
Use copper wire only. Wire gauge requirements and recommendations are
tables that are provided on 75 °C (167 °F). Do not reduce wire gauge when using
higher temperature wire.
Unshielded
THHN, THWN, or similar wire is acceptable for drive installation in dry
environments provided adequate free air space and/or conduit fill rate limits
are provided. Any wire that is chosen must have a minimum insulation
thickness of 15 mils and should not have large variations in insulation
concentricity.
Shielded/Armored Cable
Shielded cable contains all the general benefits of multi-conductor cable with
the added benefit of a copper braided shield that can contain much of the noise
that is generated by a typical AC Drive. Strong consideration for shielded cable
should be given in installations with sensitive equipment such as weigh scales,
capacitive proximity switches, and other devices that may be affected by
electrical noise in the distribution system. Applications with large numbers of
drives in a similar location, imposed EMC regulations or a high degree of
communications / networking are also good candidates for shielded cable.
Shielded cable may also help reduce shaft voltage and induced bearing
currents for some applications. In addition, the increased impedance of
shielded cable may help extend the distance that the motor can be located from
the drive without the addition of motor protective devices such as terminator
networks. See Reflected Wave in the Wiring and Grounding for Pulse Width
Modulated (PWM) AC Drives Installation Instructions,
publication DRIVES-IN001
.
Consideration should be given to all general specifications dictated by the
environment of the installation, including temperature, flexibility, moisture
characteristics, and chemical resistance. In addition, a braided shield should
be included and be specified by the cable manufacturer as having coverage of
at least 75%. An additional foil shield can greatly improve noise containment.
A good example of recommended cable is Belden® 295xx (xx determines
gauge). This cable has four XLPE insulated conductors with a 100% coverage
foil and an 85% coverage copper braided shield surrounded by a PVC jacket.
Other types of shielded cable are available, but the selection of these types may
limit the allowable cable length. Particularly, some of the newer cables twist
four conductors of THHN wire and wrap them tightly with a foil shield. This
construction can greatly increase the cable charging current required and
reduce the overall drive performance. Unless specified in the individual
distance tables as tested with the drive, these cables are not recommended and
their performance against the lead length limits supplied is not known.
ATTENTION: The distance between the drive and motor must not exceed the
maximum cable length that is stated in the Motor Cable Length Restrictions
Tables in the Wiring and Grounding for Pulse Width Modulated (PWM) AC
Drives Installation Instructions, publication DRIVES-IN001
.
ATTENTION: Do not use THHN or similarly coated wire in wet areas.
32 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
Reflected Wave Protection
The drive should be installed as close to the motor as possible. Installations
with long motor cables may require the addition of external devices to limit
voltage reflections at the motor (reflected wave phenomena). See Reflected
Wave in the Wiring and Grounding for Pulse Width Modulated (PWM) AC
Drives Installation Instructions, publication DRIVES-IN001
.
The reflected wave data applies to all carrier frequencies 2…8 kHz.
Note: For 240V ratings and lower, reflected wave effects do not need to be
considered.
Output Disconnect
The drive is intended to be commanded by motion commands that will start
and stop the motor. A device that routinely disconnects then reapplies output
power to the motor for starting and stopping the motor should not be used. If
it is necessary to disconnect power to the motor with the drive outputting
power, use the Logix Designer application to disable the drive (Aux Fault or
Coast to Stop).
Recommended Shielded Wire
Location Rating/Type Description
Standard (Option 1)
600V, 90 °C (194 °F) XHHW2/RHW-2
Anixter B209500-B209507, Belden
29501-29507, or equivalent
Four tinned copper conductors with XLPE insulation.
Copper braid/aluminum foil combination shield and
tinned copper drain wire.
PVC jacket.
Standard (Option 2)
Tray rated 600V, 90 °C (194 °F)
RHH/RHW-2 Anixter OLF-7xxxxx or
equivalent
Three tinned copper conductors with XLPE
insulation.
5 mil single helical copper tape (25% overlap min.)
with three bare copper grounds in contact with
shield.
PVC jacket.
Class I & II;
Division I & II
Tray rated 600V, 90 °C (194 °F)
RHH/RHW-2 Anixter 7V-7xxxx-3G or
equivalent
Three bare copper conductors with XLPE insulation
and impervious corrugated continuously welded
aluminum armor.
Black sunlight resistant PVC jacket overall.
Three copper grounds on #10 AWG and smaller.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 33
Chapter 1 Installation/Wiring
Power Terminal Block Power Terminal Block
I/O Wiring Motor Start/Stop Precautions
Important points to remember about I/O wiring:
Always use copper wire.
Wire with an insulation rating of 600V or greater is recommended.
Control and signal wires should be separated from power wires by at
least 0.3 m (1 ft).
Terminal Description
R/L1, S/L2 1-Phase Input Line Voltage Connection
R/L1, S/L2, T/L3 3-Phase Input Line Voltage Connection
U/T1, V/T2, W/T3 Motor Phase Connection =
Switch any two motor leads to change
forward direction or change the
Motion Polarity within Studio 5000
Logix Designer application > Axis
Properties > Polarity category.
DC+, DC- DC Bus Connection
BR+, BR- Dynamic Brake Resistor Connection
Safety Ground - PE
IMPORTANT Terminal screws may become loose during shipment. Verify that all
terminal screws are tightened to the recommended torque before
applying power to the drive.
Power Terminal Block Wire Specifications
Frame
Maximum Wire Size
(1)
(1) Maximum/minimum sizes that the terminal block will accept. These are not recommendations.
Minimum Wire Size
(1)
Torque
A
5.3 mm
2
(10 AWG) 0.8 mm
2
(18 AWG)
1.76…2.16 N•m (15.6…19.1 lb•in)
B
8.4 mm
2
(8 AWG) 2.1 mm
2
(14 AWG)
1.76…2.16 N•m(15.6…19.1 lb•in)
C
8.4 mm
2
(8 AWG) 2.1 mm
2
(14 AWG)
1.76…2.16 N•m (15.6…19.1 lb•in)
D
13.3 mm
2
(6 AWG) 5.3 mm
2
(10 AWG)
1.76…2.16 N•m (15.6…19.1 lb•in)
E
26.7 mm
2
(3 AWG) 8.4 mm
2
(8 AWG)
3.09…3.77 N•m (27.3…33.4 lb•in)
V/T2T/L3S/L2R/L1 U/T1 W/T3
V/T2T/L3S/L2R/L1 U/T1 W/T3
BR+
BR-
DC- DC+
BR+
BR-
DC-
DC+
Frame A, B, C & D Frame E
ATTENTION: A contactor or other device that routinely disconnects and
reapplies the AC line to the drive to start and stop the motor can cause drive
hardware damage. The drive is designed to use control input signals that will
start and stop the motor. If used, the input device must not exceed one
operation per minute or drive damage can occur.
IMPORTANT I/O terminals labeled “Common” are not referenced to the safety ground
(PE) terminal and are designed to greatly reduce common mode
interference.
34 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
Signal and Control Wire Types
Recommendations are for 50 °C (122 °F) ambient temperature.
75 °C (167 °F) wire must be used for 60 °C (140 °F) ambient temperature.
90 °C (194 °F) wire must be used for 70 °C (158 °F) ambient temperature.
Maximum Control Wire Recommendations
Do not exceed control wiring length of 30 m (100 ft). Control signal cable
length is highly dependent on electrical environment and installation
practices. To improve noise immunity, the I/O terminal block Common may be
connected to ground terminal/protective earth.
Control I/O Terminal Block
ATTENTION: Driving the 4-20 mA analog input from a voltage source could
cause component damage. Verify proper configuration before applying
input signals.
ATTENTION: Due to its control circuitry difference from the PowerFlex 523
and PowerFlex 525 drives, connecting Terminals 01 and 11 on the PowerFlex
527 drive causes an internal short and results in some internal components
incurring damage to the control module I/O circuitry.
Recommended Signal Wire
Signal Type/
Where Used
Belden Wire Types
(1)
(or equivalent)
(1) Stranded or solid wire.
Description Min. Insulation
Rating
Analog I/O 8760/9460
0.750 mm
2
(18 AWG), twisted pair,
100% shield with drain
(2)
(2) If the wires are short and contained within a cabinet, which has no sensitive circuits, the use of shielded wire may not be
necessary, but is always recommended.
300V,
60 °C
(140 °F)
Remote Pot 8770
0.750 mm
2
(18 AWG), 3 conductor, shielded
Encoder 9728/9730
0.196 mm
2
(24 AWG), individually shielded pairs
Recommended Control Wire for Digital I/O
Type Wire Types Description Min. Insulation
Rating
Unshielded
Per US NEC or applicable
national or local code
300V,
60 °C
(140 °F)
Shielded
Multi-conductor shielded
cable such as Belden
8770 (or equivalent)
0.750 mm
2
(18 AWG), 3 conductor, shielded
Control I/O Terminal Block Wire Specifications
Frame
Maximum Wire Size
(1)
(1) Maximum/minimum sizes that the terminal block will accept. These are not recommendations.
Minimum Wire Size
(1)
Torque
A…E
1.3 mm
2
(16 AWG) 0.13 mm
2
(26 AWG)
0.71...0.86 N•m (6.2...7.6 lb•in)
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 35
Chapter 1 Installation/Wiring
PowerFlex 527 Control I/O Removable Terminal Block
PowerFlex 527 Control I/O Wiring Block Diagram
(1) When using an opto output with an inductive load such as a relay, install a recovery diode parallel to the relay as shown, to
help prevent damage to the output.
(2) Do not short across Terminals 01 and 11.
Control I/O Terminal Designations
No. Signal Description
R1 Relay 1 N.O. These are the Normally Open (N.O.), Common, and Normally Closed (N.C.) contacts for
the programmable relay output.
Resistive: 1.0 A @ 30V DC/ 0.2 A @ 125V AC/ 0.1 A @ 230V AC
Inductive: 0.5 A @ 30V DC/0.1 A @ 125V AC/ 0.1 A @ 230V AC
Rated minimum current is 5 mA or less @ 24V DC.
Note: These are general-purpose outputs and do not have the same functionality as
system outputs when compared to chassis or remote I/O products. See the
Logix 5000® Controllers General Instructions Reference Manual, publication
1756-RM003, for important information regarding execution conditions and action
that is taken for the respective instructions used to control the digital outputs on
the drive.
R2 Relay 1 Common
R5 Relay 2 Common
R6 Relay 2 N.C.
01 Digital Common
The return for digital I/O. It is electrically isolated (along with the digital I/O) from the
rest of the drive, except for the communications port.
R1
11
(2)
12 13 14 15 16 17
R2 R5 R6 01
(2)
02 03 04 05 06 07
C1 C2
04
05
06
07
01
02
03
11
12
13
14
15
16
17
Digital Common
Digital In 1
Digital In 2
Digital In 3
Digital In 4
R1
R2
S1
S2
S+
Relay 1 N.O.
Relay 1 Common
+24V DC
+10V DC
±10V Input
Analog Common
4-20mA Input
Analog Output
Opto Output 1
(1)
Opto Output 2
(1)
Ethernet
Comm Common
Opto Common
+24V
+10V
Safety 1
Safety 2
Safety +24V
Typical
SNK wiring
Typical
SRC wiring
Pot must be
1...10 k ohm
2 W min.
0-10V
0/4-20 mA
SNK
Digital In
Analog Out
J2
J1
SRC
ACO
AVO
SRC
SNK
R5
R6
Relay 2 Common
Relay 2 N.C.
C1
C2
Common
(1)
24V
36 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
02 Digital In 1
Configurable to Home, Registration 1, Drive Enable, Positive
Overtravel, and Negative Overtravel.
If programmed as unassigned, this becomes a general-
purpose input.
Set the Digital In
jumper (J1) as shown.
03 Digital In 2
Configurable to Registration 2, Drive Enable, Positive
Overtravel, and Negative Overtravel.
If programmed as unassigned, this becomes a general-
purpose input.
04 Digital In 3
Configurable to Drive Enable, Positive Overtravel, and
Negative Overtravel.
If programmed as unassigned, this becomes a general-
purpose input.
05 Digital In 4
Configurable to Drive Enable, Positive Overtravel, and
Negative Overtravel.
If programmed as unassigned, this becomes a general-
purpose input.
06 Opto Output 1 Programmable digital output.
Note: These are general-purpose outputs and do not have the same functionality as
system outputs when compared to chassis or remote I/O products. See the
Logix 5000 Controllers General Instructions Reference Manual, publication
1756-RM003
, for important information regarding execution conditions and action
that is taken for the respective instructions used to control the digital outputs on
the drive.
07 Opto Output 2
C1 Ethernet
This terminal is tied to the Ethernet port shield. Tie this terminal to a clean ground in
order to improve noise immunity when using external communication peripherals.
C2 Comm Common This is the signal common for the communication signals.
S1 Safety 1 Safety input 1
S2 Safety 2 Safety input 2
S+ Safety +24V +24V supply for safety circuit. This is internally tied to the +24V DC source (Pin-11).
11 +24V DC
+24V DC (+/-10%) supply for digital inputs. It is rated to supply at least 100 mA and
will use Digital Common as the return. It will also be short-circuit protected (not
damaged if tied to a Common or GND), for a short duration, and will not be damaged
if connected to the +24V DC source of a different drive.
12 +10V DC
+10V DC (-0% / +6%) supply for potentiometer or 0-10V input. It is rated to supply at
least 15 mA and will use Analog Common as the return. It will also be short-circuit
protected (not damaged if tied to a Common or GND) and will not be damaged if
connected to the +10V DC source of a different drive.
13 ±10V In
±10V bipolar analog input optically isolated from the drive to avoid ground loops.
This input has approximately 100K Ω input impedance. If a remote potentiometer is
used with this input the maximum pot impedance is 10K Ω and the minimum
impedance and the maximum is still 10K Ω. The A/D resolution will be 10-bit or better.
The drive will not be damaged if up to ±27V DC or Voltage surge up to 1 kV is applied
to this port. The input bandwidth shall be about 100 Hz.
14 Analog Common
This is the return for the analog I/O. It is electrically isolated (along with the analog
I/O) from the rest of the drive.
15 4-20mA In
4-20 mA analog input optically isolated from the drive to allow daisy chain
configurations and to avoid ground loops. The input impedance for the 4-20 mA
analog input is approximately 250 Ω. The A/D resolution will be 10-bit or better.
16 Analog Output
Configurable to a 0-20 mA or 0-10V analog output signal. Set
the Analog Out jumper (J2) as shown, then set the ACO/AVO
attribute. See Setting the ACO/AVO Attribute
on page 162 for
instructions.
17 Opto Common
The emitters of the Optocoupler Outputs (1 and 2) are tied together at Optocoupler
Common. They are therefore electrically isolated from the rest of the drive.
Control I/O Terminal Designations (Continued)
No. Signal Description
SNK
Digital In
J1
SRC
SNK
Digital In
J1
SRC
Sink Source
Analog Out
J2
ACO
AVO
Analog Out
J2
ACO
AVO
0-10V 0-20 mA
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 37
Chapter 1 Installation/Wiring
CE Conformity Compliance with the Low Voltage Directive and Electromagnetic
Compatibility Directive has been demonstrated using harmonized European
Norm (EN) standards that are published in the Official Journal of the
European Communities. PowerFlex 520-series drives comply with the EN
standards that are listed below when installed according to the installation
instructions in this manual.
Product certifications and Declarations of Conformity (DoC) are available
online at rok.auto/certifications
.
Low Voltage Directive (2014/35/EU)
EN 61800-5-1 Adjustable speed electrical power drive systems – Part 5-1:
Safety requirements – Electrical, thermal, and energy.
EMC Directive (2014/30/EU)
EN 61800-3 – Adjustable speed electrical power drive systems - Part 3:
EMC requirements and specific test methods.
Machinery Directive (2006/42/EC)
EN ISO 13849-1 – Safety of machinery – safety-related parts of control
systems -Part 1: General principles for design.
EN 61800-5-2 – Adjustable speed electrical power drive systems - Part 5-2:
Safety requirement – Functional.
EN 62061 – Safety of machinery – Functional safety of safety-related
electrical, electronic, and programmable electronic control systems.
Tag Attributes in Logix Designer for Inputs and Outputs
No. Signal Tag Attribute
Analog Input
13 ±10V In <axis tag>.AnalogInput1
15 4-20mA In <axis tag>.AnalogInput2
Analog Output
16 Analog Output <axis tag>.AnalogOutput1
Digital Input
02 Digital In 1 <axis tag>.DigitalInput0
03 Digital In 2 <axis tag>.DigitalInput1
04 Digital In 3 <axis tag>.DigitalInput2
05 Digital In 4 <axis tag>.DigitalInput3
Digital Output
(1)
06 Opto Output 1 <axis tag>.DigitalOutput0
07 Opto Output 2 <axis tag>.DigitalOutput1
R1 Relay 1 N.O. <axis tag>.DigitalOutput2
R6 Relay 2 N.C. <axis tag>.DigitalOutput3
(1) These are general-purpose outputs and do not have the same functionality as system outputs when compared to chassis or
remote I/O products. See the Logix 5000 Controllers General Instructions Reference Manual, publication 1756-RM003
, for
important information regarding execution conditions and action that is taken for the respective instructions used to control
the digital outputs on the drive.
Pollution Degree Ratings According to EN 61800-5-1
Pollution Degree Description
1 No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
2
Normally, only non-conductive pollution occurs. Occasionally, however, a temporary
conductivity caused by condensation is to be expected, when the drive is out of operation.
38 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
EN 60204-1 – Safety of machinery – Electrical equipment of machines -
Part 1: General requirements.
EN 61508 Part 1-7 Functional safety of electrical/electronic/
programmable electronic safety-related systems – Parts 1-7.
ATEX Directive (2014/34/EU)
EN 50495 – Safety devices that are required for the safe functioning of
equipment with respect to explosion risks.
UKCA Conformity Compliance with application Statutory Regulations has been demonstrated
using harmonized standards published in the UK list of Designated standards.
PowerFlex 520-series drives comply with the EN standards listed below when
installed according to the installation instructions in this manual.
UK Declarations of Conformity are available online at rok.auto/certifications
.
Electrical Equipment (Safety) Regulations (2016 No. 1101)
EN 61800-5-1 Adjustable speed electrical power drive systems – Part 5-1:
Safety requirements – Electrical, thermal, and energy.
Electromagnetic Compatibility Regulations (2016 No. 1091)
EN 61800-3 Adjustable speed electrical power drive systems – Part 3: EMC
requirements and specific test methods.
Supply of Machinery (Safety) Regulations (2008 No. 1597)
EN ISO 13849-1 – Safety of machinery – Safety related parts of control
systems -Part 1: General principles for design.
EN 61800-5-2 – Adjustable speed electrical power drive systems – Part 5-2:
Safety requirement – Functional.
EN 62061 – Safety of machinery – Functional safety of safety-related
electrical, electronic, and programmable electronic control systems.
EN 60204-1 – Safety of machinery – Electrical equipment of machines –
Part 1: General requirements.
EN 61508 Part 1-7 Functional safety of electrical, electronic, and
programmable electronic safety-related systems – Part 1-7.
Equipment and Protective Systems Intended for Use in Potentially
Explosive Atmospheres Regulations (2016 No. 1107)
EN 50495 – Safety devices required for the safe functioning of
equipment with respect to explosion risks.
Pollution Degree Ratings According to EN 61800-5-1
Pollution
Degree
Description
1 No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
2
Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity
that is caused by condensation is to be expected, when the drive is out of operation.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 39
Chapter 1 Installation/Wiring
General Considerations
For CE and UK compliance, drives must satisfy installation requirements
that are related to both EN 61800-5-1 and EN 61800-3 provided in this
document.
PowerFlex 520-series drives must be installed in a pollution degree 1 or 2
environment to be compliant with the CE LV Directive and UK LV
Regulations. See Pollution Degree Ratings According to EN 61800-5-1
on
page 37 for descriptions of each pollution degree rating.
PowerFlex 520-series drives comply with the EMC requirements of EN
61800-3 when installed according to good EMC practices and the
instructions that are provided in this document. However, many factors
can influence the EMC compliance of an entire machine or installation,
and compliance of the drive itself does not ensure compliance of all
applications.
PowerFlex 520-series drives are not intended to be used on public low-
voltage networks that supply domestic premises. Without additional
mitigation, radio frequency interference is expected if used on such a
network. The installer is responsible for taking measures such as a
supplementary line filter and enclosure (see Connections and Grounding
on page 41) to prevent interference, in addition to the installation
requirements of this document.
PowerFlex 520-series drives generate harmonic current emissions on the
AC supply system. When operated on a public low-voltage network it is
the responsibility of the installer or user to verify that applicable
requirements of the distribution network operator have been met.
Consultation with the network operator and Rockwell Automation may
be necessary.
If the optional NEMA 1 kit is not installed, the drive must be installed in
an enclosure with side openings less than 12.5 mm (0.5 in.) and top
openings less than 1.0 mm (0.04 in.) to maintain compliance with the LV
Directive and UK LV Regulations.
The motor cable should be kept as short as possible to avoid
electromagnetic emission and capacitive currents.
Use of line filters in ungrounded systems is not recommended.
In CE and UK installations, input power must be a Balanced wye with
Center Ground configuration for EMC compliance.
If the DC Bus terminals or the Dynamic Brake terminals are used, the
drive must be installed in an enclosure and fuses must be used for input
protection. The ventilated enclosure needs to be IP 20 rating or higher
and at least 1.5x size larger than the drive.
Installation Requirements Related to EN 61800-5-1 and the Low Voltage Directive/UK LV
Regulations
600V PowerFlex 520-series drives can only be used on a “center
grounded” supply system for altitudes up to and including
2000 m (6562 ft).
When used at altitudes above 2000 m (6562 ft) up to a maximum of
4800 m (15,748 ft), PowerFlex 520-series drives of voltage classes up to
480V may not be powered from a “corner-earthed” supply system to
maintain compliance with the CE LV Directive and UK LV Regulations.
See Derating Guidelines for High Altitude
on page 16.
ATTENTION: NEMA/UL Open Type drives must either be installed in a
supplementary enclosure or equipped with a “NEMA Type 1 Kit” to be
CE and UK compliant with respect to protection against electrical
shock.
40 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
PowerFlex 520-series drives produce leakage current in the protective
earthing conductor, which exceeds 3.5 mA AC and/or 10 mA DC. The
minimum size of the protective earthing (grounding) conductor that is
used in the application must comply with local safety regulations for high
protective earthing conductor current equipment.
Installation Requirements Related to EN 61800-3 and the EMC Directive and UK EMC
Regulations
The drive must be earthed (grounded) as described in Connections and
Grounding on page 41. See General Grounding Requirements on page 18
for additional grounding recommendations.
Output power wiring to the motor must employ cables with a braided
shield providing 75% or greater coverage, or the cables must be housed in
metal conduit, or equivalent shield must be provided. Continuous
shielding must be provided from the drive enclosure to the motor
enclosure. Both ends of the motor cable shield (or conduit) must
terminate with a low-impedance connection to earth.
Drive Frames A...E: At the drive end of the motor, either
a. The cable shield must be clamped to a properly installed “EMC Plate”
for the drive, kit number 25-EMC1-Fx.
or
b. The cable shield or conduit must terminate in a shielded connector
that is installed in an EMC plate, conduit box, or similar.
At the motor end, the motor cable shield or conduit must terminate in a
shielded connector, which must be properly installed in an earthed
motor wiring box that is attached to the motor. The motor wiring box
cover must be installed and earthed.
All control (I/O) and signal wiring to the drive must use cable with a
braided shield providing 75% or greater coverage, or the cables must be
housed in metal conduit, or equivalent shielding must be provided.
When shielded cable is used, the cable shield should be terminated with a
low impedance connection to earth at only one end of the cable,
preferably the end where the receiver is located. When the cable shield is
terminated at the drive end, it may be terminated either by using a
shielded connector in conjunction with a conduit plate or conduit box, or
the shield may be clamped to an “EMC plate.”
Motor cabling must be separated from control and signal wiring
wherever possible.
Maximum motor cable length must not exceed the maximum length that
is indicated in Table 3
for compliance with radio frequency emission
limits for the specific standard and installation environment.
ATTENTION: PowerFlex 520-series drives produce DC current in the
protective earthing conductor which may reduce the ability of RCD’s
(residual current-operated protective devices) or RCM’s (residual
current-operated monitoring devices) of type A or AC to provide
protection for other equipment in the installation.
Where an RCD or RCM is used for protection in case of direct or
indirect contact, only an RCD or RCM of Type B is allowed on the
supply side of this product.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 41
Chapter 1 Installation/Wiring
Connections and Grounding
(1) Some installations require a shielded enclosure. Keep wire length as short as possible between the enclosure entry point and
the EMI filter.
Additional Installation Requirements
This section provides information on additional requirements for Class C1 and
C2 installation, such as enclosures and EMC cores.
Table 3 - PowerFlex 527 RF Emission Compliance and Installation Requirements
Filter Type Standard/Limits
EN61800-3 Category C1
EN61000-6-3
CISPR11 Group 1 Class B
EN61800-3 Category C2
EN61000-6-4
CISPR11 Group 1 Class A
(Input power 20 kVA)
EN61800-3 Category C3
(I 100 A)
CISPR11 Group 1 Class A
(Input power > 20 kVA)
Internal 10 m (33 ft) 20 m (66 ft)
External
(1)
(1) See Accessories and Dimensions on page 137 for more information on optional external filters.
30 m (16 ft) 100 m (328 ft) 100 m (328 ft)
IMPORTANT EMC cores are included with:
Drives that have an internal EMC filter (25x-xxxxN114)
External EMC filter accessory kit (25-RFxxx)
IMPORTANT An enclosure, shielded input cable, and EMC cores are not required to
meet Class C3 requirements.
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
EMI ttings and metal conduit
IP 30/NEMA 1/UL Type 1
option kit or EMC kit
Shielded enclosure
(1)
Building structure steel
Enclosure ground connection
EMI lter
L1'
L2'
L3'
L1
L2
L3
Shielded motor cable
Additional Installation Requirements
Frame
Size
Class C1 Class C2
Enclosure Conduit or Shielded
Cable @ Input
EMC Cores Required
(Included with product)
Enclosure Conduit or Shielded
Cable @ Input
EMC Cores Required
(Included with product)
100...120V AC (-15%, +10%) – 1-Phase Input with External EMC Filter, 0...120V 1-Phase Output
ANoNo No NoNo No
BNoNo No NoNo No
200...240V AC (-15%, +10%) – 1-Phase Input with External EMC Filter, 0...230V 3-Phase Output
A Yes Yes No No No Input/Output
B Yes Yes Output only No No Input/Output
200...240V AC (-15%, +10%) – 1-Phase Input with Internal EMC Filter, 0...230V 3-Phase Output
(1)
A* * * Yes No No
B* * * Yes No No
42 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
200...240V AC (-15%, +10%) – 3-Phase Input with External EMC Filter, 0...230V 3-Phase Output
A Yes Yes Output only No No Input/Output
B Yes Yes Output only No No Input/Output
C Yes Yes Output only No No Input/Output
DYes Yes No No No Input only
E Yes Yes Output only No No Input only
380...480V AC (-15%, +10%) – 3-Phase Input with External EMC Filter, 0...460V 3-Phase Output
A Yes Yes No No No Input/Output
B Yes Yes No No No Input/Output
CYes Yes No No No Input only
D Yes Yes Output only No No Input/Output
E Yes Yes No Yes No Input/Output
380...480V AC (-15%, +10%) – 3-Phase Input with Internal EMC Filter, 0...460V 3-Phase Output
(1)
A * * * No No Input/Output
B * * * No No Input/Output
C * * * No No Input/Output
D * * * No No Input/Output
E * * * No No Input/Output
525...600V AC (-15%, +10%) – 3-Phase Input with External EMC Filter, 0...575V 3-Phase Output
A Yes Yes No No No Input/Output
B Yes Yes No No No Input/Output
C Yes Yes No No No Input/Output
D Yes Yes No No No Input/Output
E Yes Yes No Yes No No
(1) An (*) indicates that EMC requirements are not met.
Additional Installation Requirements (Continued)
Frame
Size
Class C1 Class C2
Enclosure Conduit or Shielded
Cable @ Input
EMC Cores Required
(Included with product)
Enclosure Conduit or Shielded
Cable @ Input
EMC Cores Required
(Included with product)
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 43
Chapter 1 Installation/Wiring
Chapter
Recommended Placement of EMC Cores with Optional EMC Plate
Frame A Frame B Frame C Frame D Frame E
With Optional EMC Plate (25-EMC-Fx)
Without EMC Plate
CORE-xx-A-1
CORE-xx-A-2
CORE-xx-B-1
CORE-xx-B-2
CORE-xx-C-1
CORE-xx-C-2
CORE-xx-D-1
CORE-xx-D-2
CORE-E-1
CORE-E-2
CORE-E-3
CORE-E-4
Ground
cable
CORE-xx-x-1 CORE-xx-x-2
CORE-E-1
CORE-E-2
CORE-E-3
CORE-E-4
Ground
cable
Shows contact to
shielded layer
Secure EMC core by
using cable/zip ties
Input cable to drive (Shielded or Unshielded) Output cable from drive (Shielded)
IMPORTANT The ground cable/shield for both input and output must pass through the EMC core(s), except for the following:
Frame E drives with internal filters where the grounded input cable must not pass through EMC CORE-E-1.
600V drives with external filters where the grounded output cable must not pass through the EMC core(s).
Recommended Placement of EMC Cores Relative to External Filter
Input core Output core
Incoming power
EMC filter Drive Motor
All Frame Sizes
44 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 1 Installation/Wiring
Notes:
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 45
Chapter
Chapter
Chapter 2
Start Up
This chapter describes how to start up the PowerFlex 527 drive.
Prepare for Drive Startup Before starting up the drive, it is recommended to perform the startup tasks
described below to achieve a smooth startup and drive operation. Verify that
the drive is not powered (check that DC Bus voltage is less than 50V DC) before
proceeding with the startup task list.
Drive Startup Task List
1. Disconnect and lock out power to the machine.
2. Verify that AC line power at the disconnect device is within the rated
value of the drive.
3. If replacing a drive, verify the current catalog number of the drive. Verify
all options installed on the drive.
4. Verify that any digital control power is 24 volts.
5. Inspect grounding, wiring, connections, and environmental
compatibility.
6. Verify that the Sink (SNK)/Source (SRC) jumper is set to match your
control wiring scheme. See the PowerFlex 527 Control I/O Wiring Block
Diagram on page 35 for location.
7. Wire I/O as required for the application.
8. Wire the power input and output terminals.
9. Confirm that all inputs are connected to the correct terminals and are
secure.
Topic Page
Prepare for Drive Startup 45
Understanding the PowerFlex 527 Display and Indicators 46
Drive Programming Tools 51
Language Support 52
Using the Ethernet Port 52
IMPORTANT Read General Precautions on page 10 before proceeding.
ATTENTION: Power must be applied to the drive to perform the following
startup procedures. Some of the voltages present are at incoming line
potential. To avoid electric shock hazard or damage to equipment, only
qualified service personnel should perform the following procedure.
Thoroughly read and understand the procedure before beginning. If an event
does not occur while performing this procedure, Do Not Proceed. Remove
All Power including user supplied control voltages. User supplied voltages
may exist even when main AC power is not applied to the drive. Correct the
malfunction before continuing.
46 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 2 Start Up
10. Collect and record motor nameplate and encoder or feedback device
information. Verify motor connections.
Is the motor uncoupled?
What direction will the motor need to turn for the application?
11. Verify the input voltage to the drive. Verify if the drive is on a grounded
system. Verify that the MOV jumpers are in the correct position. See AC
Supply Source Considerations on page 17 for more information.
12. Apply AC power to the drive.
You need to establish a connection with a Logix controller and verify
that the drive is enabled using a Logix motion instruction (for example
MSO command) and no “START INHIBIT” condition exists. See
Configuring the PowerFlex 527 Drive with Integrated Motion
on
page 53 for instructions.
Verify that the drive is receiving start and stop commands correctly.
Verify that input currents are balanced.
Verify that motor currents are balanced.
Start, Stop, Direction, and Speed Control
Start, Stop, Direction, and Speed Control are done using Logix motion
instructions (for example, Motion Drive Start (MDS)). See the Logix 5000
Motion Controllers Instructions Reference Manual, publication MOTION-
RM002 for more information.
Understanding the
PowerFlex 527 Display and
Indicators
The PowerFlex 527 drive has four status indicators, a fault indicator, an LCD
display, and a membrane keypad for navigation. The display is used to view
information such as motor information, axis states, faults, and set the network
configuration. The indicators are used to monitor the module and network
status, and troubleshoot faults.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 47
Chapter 2 Start Up
PowerFlex 527 Drive LCD Display and Status Indicators
For detailed descriptions of the Fault, MOD, NET, and LINK A/B status
indicators, see PowerFlex 527 Drive Status Indicators
on page 120.
Display Display State Description
ENET
Off Drive is not connected to the network.
Steady Drive is connected to the network.
LINK
Off Drive has not established a controller connection.
Steady
Drive is connected to the network and a controller connection
has been established.
LED LED State Description
FAULT Steady
Indicates that drive is faulted. See Fault Codes
on page 116 for
more information.
Key Name Description
Up Arrow
Down Arrow
Pressing either arrow moves the selection to the next (or
previous) item. When changing values, pressing the Up arrow
increments the highlighted value. Values rollover after
reaching the end of the list.
Escape
Press to go back. Pressing enough times results in the HOME
screen.
Select Press to select a menu item.
Enter Press to confirm the selection and go to submenu items.
LED LED State Description
MOD Steady Green Drive is operational and no fault exists.
NET Steady Green Drive is online and has connections in the established state.
LINK A (Ethernet Port 1)
LINK B (Ethernet Port 2)
Steady Green Drive is connected to the network but not transmitting data.
ENET and LINK display
Fault status indicator
Module status indicator
Network status indicator
Link A status indicator (Ethernet Port 1)
Link B status indicator (Ethernet Port 2)
Navigation keypad
Esc
Sel
48 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 2 Start Up
Startup Sequence
On power-up, the drive will initialize and
status information will scroll across the
LCD display.
After initialization, the Device/Axis state
will be shown on the LCD display. In this
example, the current state is STANDBY.
Device and Axis States
Table 4 and Table 5 list the possible Device and Axis states and their
descriptions.
If a boot fault occurs during initialization, a
fault number shows up on the screen with
the format, “BFxxx”, where “BF” represents
boot fault and “xxx” refers to the fault code.
In this example, fault BF003 is shown.
For a list of other types of possible faults, see
Fault Codes
on page 116.
Table 4 - Device States
Device State Description
STANDBY The drive is waiting to receive configuration information from the controller.
CONNECTING The drive is trying to establish communication with the EtherNet/IP™ controller.
CONFIGURING The drive is receiving configuration information from the controller.
SYNCING The drive is waiting for a successful Group Sync service.
CONN_TIMEOUT
The drive is trying to establish communication with the EtherNet/IP controller but
the connection has timed out.
DUPLICATE_IP The drive has detected another device on the network with the same IP address.
FWUPDATE The drive is updating the firmware.
Table 5 - Axis States
Axis State Description
INITIALIZING The drive is initializing the motion connection.
PRECHARGE The drive is ready for mains input power.
STOPPED The drive is in the Stopped state and awaiting a motion command.
STARTING
The drive has received a motion command and is transitioning to the Running state
from the Stopped state.
RUNNING The drive is enabled and/or running.
TESTING The drive is actively executing a test procedure, for example, a hookup test.
STOPPING The drive is decelerating to a stop as the result of a disable.
ABORTING The drive is decelerating to a stop as the result of a fault or an abort request.
MAJOR FAULTED The drive is faulted due to an existing or past fault condition.
START INHIBITED The drive has an active condition that inhibits it from being enabled.
SHUTDOWN The drive has been shut down.
VOLTS
AMPS
HERTZ
RUN
FWD
REV
PROGRAM
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 49
Chapter 2 Start Up
Information Display
From the axis state screen, press Select or the Down arrow to
access the following information menu:
Network Configuration
Through the settings option, you can configure the drive IP address. There are
two methods for configuring the drive IP address:
Static IP – Use Static IP when you want to manually configure the IP
address, subnet mask, and gateway addresses.
DHCP (Dynamic Host Configuration Protocol) – Use DHCP when you
want convenience and ease-of-use compared to Static IP. The IP address,
subnet mask, and gateway addresses will be assigned automatically by
the DHCP server.
Screen Option Description
Example Display
(1)
(1) The LCD only accommodates up to five characters. Text strings that are more than five characters are scrolled.
Version Info
Provides information on the hardware and software
versions.
HW Ver 01.002 FW Ver 01.102
Device Info
Provides information on the drive type, network
configuration, and IP address.
PowerFlex 527 Static IP 192.168.1.180
or PowerFlex 527 DHCP
192.168.1.180
(2)
(2) If “0.0.0.0” is displayed and DHCP is enabled, it means that the IP address has not been assigned by the DHCP server. Check
your network settings.
Settings
Allows configuration of network settings, changing
the display language, and resetting the drive.
See Network Configuration for
instructions on how to configure the
IP address.
Navigating the Settings Menu
Settings Menu
Selections
Sub Menu
Selections
Attributes Default Description
Protected Mode
(1)
(1) This setting is only available in PowerFlex 527 firmware revision 2.001 or later.
Reset
ENABLED
DISABLED
ENABLED
When Enabled (default), identity
object resets are not possible when a
controller connection is open.
Network
Config
ENABLED
DISABLED
ENABLED
When Enabled (default), network
configuration changes are not
possible when a controller
connection is open.
Flash Update
ENABLED
DISABLED
ENABLED
When Enabled (default), firmware
updates are not possible when a
controller connection is open.
Device Config
ENABLED
DISABLED
ENABLED
When Enabled (default), only attribute
writes are possible when a controller
connection is open.
Network
Static IP
IP address 192.168.1.180 Indicates current IP address.
Subnet mask 255.255.255.0 Indicates current subnet mask.
Gateway 192.168.1.1 Indicates current gateway.
DHCP
IP address
Automatically
assigned by the
DHCP server.
Indicates current IP address.
Subnet mask Indicates current subnet mask.
Gateway Indicates current gateway.
Web
(1)
Enabled Enables the web server.
->Disabled
(2)
(2) An arrow (->) appears in front of the chosen attribute indicating that this attribute is currently configured. This is also the
factory default setting.
Disables the web server.
Sel
50 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 2 Start Up
IMPORTANT Regardless of the method used to set the adapter IP address, each node
on the EtherNet/IP network must have a unique IP address. To change
an IP address, you must set the new value and then power cycle the
drive.
You can also use the Reset function, however all safety connections will
have to be disabled before this option is available.
You must enter a valid IP address configuration. With firmware 1.008 or
later, if an illegal IP address configuration exists upon power-up, for
example, if the IP address and gateway address are identical, the drive
faults and exhibits INIT FLT M22 - ILLEGAL ADDRESS on the display and
the IP address configuration changes to DHCP.
Configuring Network Settings
Step Keys Example Display
1. On the Device/Axis state screen, press the Down
arrow to go to the Settings menu.
2. Press Enter to display the Network Settings screen.
3. Press the Up or Down arrow to select either DHCP or
Static IP, then press Enter.
If you choose DHCP, go to step 4
.
If you choose Static IP, go to step 5.
4. Press Enter to confirm DHCP as the network
configuration option. Choosing DHCP automatically
configures the IP settings for your drive.
This completes the network configuration for your
drive.
5. Choosing Static IP enables you to manually configure
the IP address, subnet mask, and gateway address for
your drive. Press the Up or Down arrow to scroll
through the settings.
6. In this example, we will start by configuring the IP
address. Select IP address, then press Enter to display
the first octet of the IP address.
7. Press the Up or Down arrow to scroll through the four
octets of the IP address.
8. Press Sel to edit an octet. The rightmost digit of the
octet will flash.
9. Press the Up or Down arrow to change the digit.
Press Sel to edit the digits on the left.
10. Press ESC to cancel a change and exit the edit mode.
Or
Press Enter to save a change and exit the edit mode.
or
or
or
or
Sel
Sel
Esc
or
or
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 51
Chapter 2 Start Up
Real-time Information Display
Once the drive is enabled and running and connected to a controller, the
following information can be accessed through the LCD screen.
Note: See Integrated Motion on the EtherNet/IP Network Reference Manual,
publication MOTION-RM003
, for complete motion attribute description.
Drive Programming Tools Some features in the PowerFlex 527 drive are not supported by older
configuration software tools. It is strongly recommended that customers
using such tools migrate to Studio 5000 Logix Designer application (version 24
or later) with Add-on Profile (AOP) to enjoy a richer, full-featured
configuration experience.
11. Repeat step 7 to step 10 to edit the values of the other
octets.
After you have finished configuring the IP address.
Press ESC to go back to the Static IP menu.
12. Repeat step 5
to step 11 to configure the subnet mask
and gateway address.
13. Power cycle the drive to store the new IP settings.
This completes the network configuration for your
drive.
IMPORTANT You must cycle power to make network configuration changes
persistent. An asterisk (*) is shown next to the network configuration
when viewing the Device Info screen option to signify that a change has
been made but has not taken effect.
For example, after changing the network configuration from Static IP to
DHCP, when viewing the Device Info screen option, an asterisk (*)
appears next to the text “DHCP” on the LCD display.
The change takes effect and the asterisk is removed
after you cycle power to the drive.
Display configuration changes take effect
immediately.
Real-time Information Description Example Display
Velocity Feedback
Displays the value of the velocity feedback in
units/sec. See motion attribute 454.
VELOCITY FDBK 0.0
Motor Current
Displays the value of the motor current in
% motor rated. See motion attribute 529.
MOTOR CURT 0.0
Motor Utilization
Displays the value of the motor utilization in %.
See motion attribute 635.
MOTOR UTIL 0.0
DC Bus Voltage
Displays the value of the DC Bus voltage in VDC.
See motion attribute 620.
DC BUS VLTG 0.0
Current Command
Displays the value of the torque current in
% motor rated. See motion attribute 524.
CURRENT CMD 0.0
Output Current
Displays the value of Output Current in Amps RMS.
See motion attribute 601.
OUTPUT CURT 0.0
Configuring Network Settings (Continued)
Step Keys Example Display
Esc
52 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 2 Start Up
Language Support
Using the Ethernet Port
The PowerFlex 527 drive has dual embedded Ethernet ports that connect the
drive to an EtherNet/IP network. This enables communication with a Logix
based control system for drive control using CIP Motion commands. You can
also upgrade the drive firmware or upload/download a configuration easily
using the Studio 5000 Logix Designer application.
The EtherNet/IP network offers a full suite of control, configuration, and data
collection services by layering the Common Industrial Protocol (CIP™) over the
standard protocols used by the Internet (TCP/IP and UDP). EtherNet/IP uses
TCP/IP for general messaging/information exchange services and UDP/IP for
I/O messaging services for control applications.
Liner, Star, and Device Level Ring network topologies are supported by the
PowerFlex 527 drive. Plus, the application of the CIP Safety™ protocol enables
the simultaneous transmission of safety and standard control data and
diagnostics information.
Language Keypad/LCD Display Logix Designer Application
English Y Y
French Y Y
Spanish Y Y
Italian Y Y
German Y Y
Japanese Y
Portuguese Y Y
Simplified Chinese Y
Korean Y
Polish
(1)
(1) Due to a limitation of the LCD display, some of the characters for Polish, Turkish, and Czech will be modified.
Y–
Turkish
(1)
Y–
Czech
(1)
Y–
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 53
Chapter 3
Chapter
Chapter
Configuring the PowerFlex 527 Drive with
Integrated Motion
This chapter describes procedures on how to configure Integrated Motion on
the EtherNet/IP network control by using a PowerFlex 527 Drive.
Configure the Drive You can include the drive in your Studio 5000 Logix Designer application by
adding it to a configured EtherNet/IP module or controller and adding it
under the I/O configuration tree. After setting the network configuration, you
can view the drive status information in the Studio 5000 environment and use
it in your Studio 5000 Logix Designer application.
Set the Network Configuration
You can set the network configuration by using the LCD display and drive
keypad.
1. When the LCD display is showing the Device/Axis state, use the keypad
to navigate to SETTINGS -> NETWORK. Then choose either STATIC IP
or DHCP.
The default setting is STATIC IP.
2. If you chose STATIC IP, then you must configure the following settings:
IP address
Gateway
•Subnet mask
If you chose DHCP, the three settings above are configured automatically
by the DHCP server.
Settings are stored in nonvolatile memory. IP addressing can also be changed
through the Module Configuration dialog box in RSLinx® software. Changes to
the IP addressing take effect after power is cycled or reset. The drive is factory
programmed to static IP address of 192.168.1.180.
See Configuring Network Settings
on page 50 for help on configuring the IP
settings.
Topic Page
Configure the Drive 53
Configure the Logix Designer Application Project 54
Add a PowerFlex 527 Drive 58
Configure the PowerFlex 527 Drive 59
Apply Power to the PowerFlex 527 Drive 79
Test and Tune the Axes – Velocity and Position Control Modes 80
Before you begin, make sure that you know the catalog number for each drive
component, the Logix module and/or controller used in your motion control
application.
54 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
Configure the Logix
Designer Application
Project
These procedures assume that you have wired your PowerFlex 527 drive
system. In this example, the CompactLogix 5370 controller is used.
For help with using the Studio 5000 Logix Designer application (version 24 or
later) application as it applies to configuring the ControlLogix or
CompactLogix controllers, see Additional Resources
on page 8.
Configure the Logix 5000 Controller
Follow these steps to configure the controller.
1. Apply power to your controller and open your Logix Designer
application.
2. From the Create menu, choose New Project.
The New Project dialog box appears.
If using a safety or non-safety ControlLogix controller, you must also use a
1756-EN2T, 1756-EN2TR, or 1756-EN3TR EtherNet/IP module. If using a
CompactLogix 5370 controller, it has dual embedded EtherNet/IP ports.
IMPORTANT If you are configuring a PowerFlex 527 drive for integrated safety in a
safety application, you must use a GuardLogix safety controller.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 55
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
In this example, the typical dialog boxes for 1756-L7xS GuardLogix 5570 safety
controllers and CompactLogix 5370 controllers are shown.
Follow these steps to configure your Logix 5000 controller.
1. Expand the Logix 5000 controller family and select your controller.
2. Type the file name.
3. Click Next.
The New Project dialog box appears.
4. From the Revision pull-down menu, choose your software revision.
5. Click Finish.
The new controller appears in the Controller Organizer under the I/O
Configuration folder.
6. Right-click I/O Configuration in the Controller Organizer and choose
New Module.
The Select Module Type dialog box appears.
IMPORTANT If your project includes a ControlLogix or GuardLogix controller, you need
to add an Ethernet communication module to your Bulletin 1756 chassis
and configure it for use in your application.
For ControlLogix or GuardLogix controllers, go to step 6
.
For CompactLogix 5370 controllers, go to step 13.
See the EtherNet/IP Network Configuration User Manual, publication,
ENET-UM001
for more information.
Controller Organizer with
GuardLogix 1756-7xS controller
Controller Organizer with
CompactLogix 5370 controller
56 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
7. By using the filters, check Communication and Allen-Bradley, and select
1756-EN2T, 1756-EN2TR, or 1756-EN3TR as appropriate for your actual
hardware configuration.
In this example, the 1756-EN2T module is selected.
8. Click Create.
The New Module dialog box appears.
a. Configure the new module.
b. Type the module Name.
c. Enter the Logix EtherNet/IP module slot (leftmost slot = 0).
d. Select an Ethernet Address option.
In this example, the Private Network address is selected.
e. Enter the address of your EtherNet/IP module.
In this example, the last octet of the address is 1.
f. Click Change in the Module Definition area.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 57
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
The Module Definition dialog box opens.
9. From the Time Sync Connection pull-down menu, choose Time Sync and
Motion.
10. Click OK to close the Module Definition dialog box.
11. Click Yes when prompted to confirm your module definition changes.
12. Click OK to close the New Module dialog box.
13. From the Edit menu, choose Controller Properties.
The Controller Properties dialog box appears.
14. Click the Date/Time tab.
15. Check Enable Time Synchronization.
IMPORTANT Time Sync functionality is what enables motion control on an
Ethernet network. Without this setting, you won’t be able to run
your motion application.
Your new 1756-ENxT Ethernet
module appears under the I/O
configuration folder in the
Controller Organizer.
58 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
The motion modules set their clocks to the module you assign as the
Grandmaster.
16. Click OK.
Add a PowerFlex 527 Drive Follow these instructions to add the PowerFlex 527 drive to your project.
1. Right-click the Ethernet network (node) and choose New Module…
2. Clear the small ‘select all’ check boxes, Module Type Category and Vendor
Filters.
Alternatively, you can simply type “527” into the search box and choose
the drive.
3. In the Module Type Category Filters window, check Drive.
In the Module Type Vendors Filters window, check Allen-Bradley.
IMPORTANT Check Enable Time Synchronization for all controllers that
participate in CIP Sync™. The overall CIP Sync network
automatically promotes a Grandmaster clock, unless the priority
is set in the Advanced tab.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 59
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
4. Choose the PowerFlex 527 drive and click Create.
The Module Properties dialog box appears.
5. Configure the new drive.
a. Type the drive Name.
b. Type a Description, if desired.
c. Select an Ethernet Address option.
In this example, the Private Network address is selected.
d. Enter the address of your PowerFlex 527 drive.
In this example, the last octet of the address is 180.
6. Proceed to Configure the PowerFlex 527 Drive
to continue configuring
your drive.
Configure the PowerFlex
527 Drive
After you have added a PowerFlex 527 drive to your project, you will need to
configure the type of safety connection suitable for your application. See the
following sections for instructions on configuring the drive for the different
types of safety connections.
Configure Drive with Hardwired Safety Connections
on page 60
Configure Drive with Integrated Safety Connections on page 61
60 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
Configure Drive with Hardwired Safety Connections
Follow these steps to configure the PowerFlex 527 drives with hardwired
safety.
1. Verify that you have done the steps in Add a PowerFlex 527 Drive
on
page 58 before proceeding.
2. Under Module Definition, click Change.
The Module Definition dialog box appears.
a. From the Electronic Keying pull-down menu, choose an option.
b. From the Connection pull-down menu, choose the Connection mode
for your motion application.
In this example, choose Motion only.
Connection Mode Controller Needed Description
Motion only
ControlLogix 5570,
GuardLogix 5570,
CompactLogix 5370,
ControlLogix 5580,
CompactLogix 5380, or
Compact GuardLogix 5370
(1)
Hard-wired Safe Torque Off (STO) connections are
possible.
This controller manages Motion.
Another controller that has a Safety only
connection to the drive manages Safety.
Motion and Safety
GuardLogix 5570,
GuardLogix 5580,
Compact GuardLogix 5370
(1)
, or
Compact GuardLogix 5380
This controller manages Motion and Safety.
Safety only
GuardLogix 5570,
GuardLogix 5580,
Compact GuardLogix 5370, or
Compact GuardLogix 5380
This controller manages Safety.
Another controller that has a Motion only
connection to the drive manages Motion.
(1) Catalog numbers containing the letter M.
IMPORTANT To configure PowerFlex 527 drives, you must use the Logix Designer
application, version 24.00 or later.
WARNING: When using motion modules, the electronic keying must be
either “Exact Match” or “Compatible Keying”.
Never use “Disable Keying” with motion modules.
When ‘Safety’ appears in the Connection mode, integrated safety is
implied.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 61
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
c. From the Power Structure pull-down menu, choose the catalog
number that matches your power structure.
d. Check the Verify Power Rating on Connection checkbox to confirm
that the proper power structure that is defined in the profile is the
same as the connected drive. If the two do not match, a connection
error occurs, which indicates a power mismatch.
Verify Power Rating on Connection is checked by default. It is enabled
in offline mode.
3. Click OK to close the Module Definition dialog box.
4. Click OK to close the Module Properties dialog box.
5. Proceed to Continue Drive Configuration
on page 64 to continue
configuring your drive.
Configure Drive with Integrated Safety Connections
Follow these steps to configure PowerFlex 527 drives with integrated safety.
1. Verify that you have done the steps in Add a PowerFlex 527 Drive
on
page 58 before proceeding.
2. Under Module Definition, click Change.
The Module Definition dialog box appears.
Your PowerFlex 527 drive appears in
the Controller Organizer under the
Ethernet controller in the I/O
configuration folder.
62 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
a. From the Electronic Keying pull-down menu, choose an option.
b. From the Connection pull-down menu, choose the Connection mode
for your motion application.
In this example, choose Motion and Safety.
The Safety Network Number (SNN) field populates automatically when
the Connection mode includes an integrated Motion and Safety or
Safety-only connection. For a detailed explanation of the safety network
number, see the GuardLogix 5570 and Compact GuardLogix 5370
Reference Manual, publication 1756-RM099
.
c. From the Power Structure pull-down menu, choose the catalog
number that matches your power structure.
d. Check the Verify Power Rating on Connection check box to confirm
that the proper power structure that is defined in the profile is the
same as the connected drive. If the two do not match, a connection
error occurs, which indicates a power mismatch.
Verify Power Rating on Connection is checked by default. It is enabled
in offline mode.
3. Click OK to close the Module Definition dialog box.
WARNING: When using motion modules, the electronic keying must be
either “Exact Match” or “Compatible Keying”.
Never use “Disable Keying” with motion modules.
When ‘Safety’ appears in the Connection mode, integrated safety is
implied.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 63
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
4. Click the Safety tab.
The connection between the controller and the PowerFlex 527 drive is
based on the following:
Drive catalog number must be 527 (integrated)
Drive catalog number must be PowerFlex 527 (integrated)
Drive Safety Network Number (SNN)
•GuardLogix slot number
GuardLogix safety network number
Path from the GuardLogix controller to the PowerFlex 527 drive
Configuration signature
If any differences are detected, the connection between the GuardLogix
controller and the PowerFlex 527 drive is lost, and the yellow icon appears
in the controller project tree after you download the program.
5. Click Advanced.
The Advanced Connection Reaction Time Limit Configuration dialog box
appears.
64 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
Analyze each safety channel to determine the appropriate settings. The
smallest Input RPI allowed is 6 ms. Selecting small RPI values consumes
network bandwidth and can cause nuisance trips because other devices
cannot get access to the network.
For more information about the Advanced Connection Reaction Time
Limit Configuration, see the GuardLogix 5570 Controllers User Manual,
publication 1756-UM022
.
6. Click OK to close the Advanced Connection Reaction Time Limit
Configuration dialog box.
7. Click OK to close the Module Properties dialog box.
8. Proceed to Continue Drive Configuration
to continue configuring your
drive.
Continue Drive Configuration
After you have established your PowerFlex 527 drive in the Logix Designer
application, the remaining configuration steps are the same regardless of the
drive catalog number.
1. Right-click the PowerFlex 527 drive you created and choose Properties.
The Module Properties dialog box appears.
2. Click the Associated Axes tab.
3. Click New Axis.
Your PowerFlex 527 drive appears
in the Controller Organizer under
the Ethernet controller in the I/O
Configuration folder.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 65
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
The New Tag dialog box appears.
4. Type the axis Name.
AXIS_CIP_DRIVE is the default Data Type.
5. Click Create.
6. Click Apply.
The axis (Axis_1 in this example) appears
in the Controller Organizer under Motion
Groups > Ungrouped Axes and is
assigned as Axis 1.
66 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
7. Click the Power tab.
8. From the pull-down menu, choose the power options appropriate for
your actual hardware configuration.
9. Click OK.
10. Repeat step 1
through step 9 for each PowerFlex 527 drive.
Attribute Menu Description
PWM Frequency
•2 kHz
4 kHz (Default)
•8 kHz
The value sets the carrier frequency for the Pulse Width
Modulation (PWM) output to the motor.
See the PWM Frequency Chart
on page 67 for derating
guidlines.
Bus Regulator Action
Disabled
This selection disables the internal DC bus voltage regulation
feature of the drive. Select this option if there is an external
regenerative brake or regenerative line supply that is
connected to the drive DC bus.
Shunt Regulator
This selection is used when either an external shunt resistor is
connected to the drive or the internal IGBT will be controlling
the power dissipation to the resistor (the type of shunt resistor
is selected below).
Adjustable Frequency
(Default)
This selection allows the drive to either change the torque
limits or ramp rate of the velocity to control the DC bus voltage.
This option is not recommended for positioning applications
because it will override the velocity and the system will
overshoot or may not stop.
Shunt then Adjustable
Frequency
This selection allows the shunt resistor to absorb as much
energy as it is designed for, then transitions to adjustable
frequency control if the limit of the resistor has been reached.
Adjustable Frequency
then Shunt
This selection allows for adjustable frequency control of the DC
bus. If adjustable frequency control cannot maintain the DC
bus within limits, the shunt resistor will be activated.
Shunt Regulator Resistor
Type
Internal Not applicable for PowerFlex 527 drives.
External Enables the external shunt (internal shunt option is disabled).
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 67
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
PWM Frequency Chart
Configure the Motion Group
Follow these steps to configure the motion group.
1. In the Controller Organizer, right-click Motion Groups and choose New
Motion Group.
The New Tag dialog box appears.
2. Type the new motion group Name.
3. Click Create.
.
IMPORTANT Ignoring derating guidelines can cause reduced drive performance. The
drive may automatically reduce the PWM carrier frequency at low output
speeds, unless prevented from doing so.
84
88
80
96
100
92
8
7
6
54321
% Output Current (A)
Carrier Frequency (kHz)
Your new motion group appears in the Controller
Organizer under the Motion Groups folder.
68 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
4. Right-click the new motion group and choose Properties.
The Motion Group Properties dialog box appears.
5. Click the Axis Assignment tab and move your axes (created earlier) from
Unassigned to Assigned.
6. Click the Attribute tab and edit the default values as appropriate for your
application.
7. Click OK.
.
Configure Axis Properties
Axis configuration depends on the motor or other devices (for example, an
external encoder) associated with each axis. This section provides guidelines
for configuring induction motors.
Configure Induction Motor Axis Properties (Frequency Control)
Configure Induction Motors Axis Properties (Velocity Loop) on page 72
Configure Induction Motors Axis Properties (Position Loop) on page 76
Configure Induction Motor Axis Properties (Frequency Control)
The PowerFlex 527 drives support basic Volts/Hertz (V/Hz), Fan/Pump Volts/
Hertz, Sensorless Vector Control (SVC), and Sensorless Vector Control (SVC)
Economy frequency control methods.
Follow these steps to configure the induction motor axis properties.
1. In the Controller Organizer, right-click an axis and choose Properties.
Your axis moves to the new motion group.
To get the minimum motion group base update
rate, see Motion Group Base Update Rate
on
page 161.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 69
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
2. Select the General category.
The General and Associated Module dialog box appears.
3. From the Axis Configuration pull-down menu, choose Frequency
Control.
4. From the Module pull-down menu, choose your PowerFlex 527 drive.
The Module Type and Power Structure fields populate with the chosen
drive catalog number.
5. Click Apply.
6. Select the Motor category.
The Motor Device Specification dialog box appears.
7. From the Data Source pull-down menu, choose Nameplate Datasheet.
This is the default setting.
8. From the Motor Type pull-down menu, choose Rotary Induction.
9. From the motor Nameplate / Datasheet, enter the Phase to Phase values.
10. Click Apply.
11. Select the Frequency Control category.
70 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
The Frequency Control dialog box appears.
12. From the Frequency Control Method pull-down menu, choose the
method appropriate for your application.
13. If you chose the Basic Volts/Hertz method, enter the nameplate data for
your motor in the Basic Volts/Hertz fields.
If you chose the Sensorless Vector method, the Basic Volts/Hertz fields
are dimmed.
14. Click Apply.
15. If you chose the Sensorless Vector or Sensorless Vector Economy
method, select the Motor > Analyzer category.
The Analyze Motor to Determine Motor Model dialog box appears.
16. Click the Static Motor Test tab.
17. Click Start to run the test and measure Motor Stator Resistance.
If you chose the Basic Volts/Hertz category, you can skip this test.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 71
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
18. Select the Actions category.
The Actions to Take Upon Conditions dialog box appears.
From this dialog box, you can program actions and change the action for
exceptions (faults). See Logix 5000 Controller and Drive Behavior
on
page 123 for more information.
Some out-of-box (OOB) settings will need to be applied here. See
Recommended Out-of-Box Settings
on page 159 for more information.
19. Select the Parameter List category.
The Motion Axis Parameters dialog box appears.
72 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
From this dialog box, you can program actions and change the action for
exceptions (faults). See Logix 5000 Controller and Drive Behavior
on
page 123 for more information.
To obtain the best performance from the drive regardless of which
control method you are using, you should configure the recommended
out-of-box settings as described in Recommended Out-of-Box Settings
on page 159 first before configuring further for your application.
20. Click OK.
21. Repeat step 1
through step 20 for each induction motor axis.
Configure Induction Motors Axis Properties (Velocity Loop)
Follow these steps to configure the induction motor axis properties.
1. In the Controller Organizer, right-click an axis and choose Properties.
2. Select the General category.
The General and Associated Module dialog box appears.
3. From the Axis Configuration pull-down menu, choose Velocity Loop.
4. From the Module pull-down menu, choose your PowerFlex 527 drive.
The Module Type and Power Structure fields populate with the chosen
drive catalog number.
5. Click Apply.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 73
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
6. Select the Motor category.
The Motor Device Specification dialog box appears.
7. From the Data Source pull-down menu, choose Nameplate Datasheet.
This is the default setting.
8. From the Motor Type pull-down menu, choose Rotary Induction.
9. From the motor Nameplate / Datasheet, enter the Phase to Phase values.
10. Click Apply.
11. Select the Motor Feedback category.
12. Enter the specifications of your encoder into the fields.
13. Click Apply.
74 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
14. Select the Scaling category and edit the values as appropriate for your
application.
15. Click Apply if you make changes.
16. Select the Actions category.
The Actions to Take Upon Conditions dialog box appears.
From this dialog box, you can program actions and change the action for
exceptions (faults). See Logix 5000 Controller and Drive Behavior
on
page 123 for more information.
Some out-of-box (OOB) settings will need to be applied here. See
Recommended Out-of-Box Settings
on page 159 for more information.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 75
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
17. Select the Parameter List category.
The Motion Axis Parameters dialog box appears.
From this dialog box, you can program actions and change the action for
exceptions (faults). See Logix 5000 Controller and Drive Behavior
on
page 123 for more information.
To obtain the best performance from the drive regardless of which
control method you are using, you should configure the recommended
out-of-box settings as described in Recommended Out-of-Box Settings
on page 159 first before configuring further for your application.
18. Click OK.
19. Repeat step 1
through step 18 for each induction motor axis.
76 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
Configure Induction Motors Axis Properties (Position Loop)
Follow these steps to configure the induction motor axis properties.
1. In the Controller Organizer, right-click an axis and choose Properties.
2. Select the General category.
The General and Associated Module dialog box appears.
3. From the Axis Configuration pull-down menu, choose Position Loop.
4. From the Module pull-down menu, choose your PowerFlex 527 drive.
The Module Type and Power Structure fields populate with the chosen
drive catalog number.
5. Click Apply.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 77
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
6. Select the Motor category.
The Motor Device Specification dialog box appears.
7. From the Data Source pull-down menu, choose Nameplate Datasheet.
This is the default setting.
8. From the Motor Type pull-down menu, choose Rotary Induction.
9. From the motor Nameplate / Datasheet, enter the Phase to Phase values.
10. Click Apply.
11. Select the Motor Feedback category.
12. Enter the specifications of your encoder into the fields.
13. Click Apply.
78 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
14. Select the Scaling category and edit the values as appropriate for your
application.
15. Click Apply if you make changes.
16. Select the Actions category.
The Actions to Take Upon Conditions dialog box appears.
From this dialog box, you can program actions and change the action for
exceptions (faults). See Logix 5000 Controller and Drive Behavior
on
page 123 for more information.
Some out-of-box (OOB) settings will need to be applied here. See
Recommended Out-of-Box Settings
on page 159 for more information.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 79
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
17. Select the Parameter List category.
The Motion Axis Parameters dialog box appears.
From this dialog box, you can program actions and change the action for
exceptions (faults). See Logix 5000 Controller and Drive Behavior
on
page 123 for more information.
To obtain the best performance from the drive regardless of which
control method you are using, you should configure the recommended
out-of-box settings as described in Recommended Out-of-Box Settings
on page 159 first before configuring further for your application.
18. Click OK.
19. Repeat step 1
through step 18 for each induction motor axis.
Download the Program
After completing the Logix Designer application and saving the file, you must
download your program to the Logix 5000 controller.
Apply Power to the
PowerFlex 527 Drive
This procedure assumes that you have done the following:
Wired and configured your PowerFlex 527 system and your Logix 5000
controller.
Downloaded the project to the controller.
Connected the Ethernet port to the drive.
If you have not done the steps that are listed above, you will achieve a different
result in step 5
.
SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting
and wiring of the PowerFlex 527 drives before applying power. Once power is
applied, connector terminals can have voltage present even when not in use.
80 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
Follow these steps to apply power to the PowerFlex 527 system.
1. Disconnect the load to the motor.
2. Apply AC power.
The LCD display begins the startup sequence. See Startup Sequence
on
page 48 for more information.
3. When the startup sequence completes, verify that the MOD and NET
status indicators are steady green.
If the two status indicators are not solid green, see PowerFlex 527 Drive
Status Indicators on page 120 for more information.
4. Monitor the DC Bus voltage on the LCD display. See Real-time
Information Display on page 51 for more information.
If the DC Bus does not reach the expected voltage level, check the 3-phase
input power connections. Also it can take as many as 1.8 seconds after
input power is applied before the drive can accept motion commands.
5. Verify that the axis state changes to STOPPED.
If the axis state does not change to STOPPED, see Fault Codes
on
page 116.
Test and Tune the Axes –
Velocity and Position
Control Modes
This procedure assumes that you have configured your PowerFlex 527 drive,
your Logix 5000 controller, and applied power to the system.
For help using the Logix Designer application as it applies to testing and
tuning your axes with ControlLogix EtherNet/IP modules or CompactLogix
5370 controllers, see Additional Resources
on page 8.
Test the Axes
Note: In the following example, the Axis Configuration is set to Position Loop.
Follow these steps to test the axes.
1. Verify that the load was removed from each axis.
2. In your Motion Group folder, right-click an axis and choose Properties.
The Axis Properties dialog box appears.
ATTENTION: To avoid personal injury or damage to the equipment,
disconnect the load to the motor. Make sure that each motor is free of
all linkages when initially applying power to the system.
IMPORTANT Before proceeding with testing and tuning your axes, verify that the MOD
and NET status indicators are operating as described in PowerFlex 527
Drive Status Indicators on page 120.
ATTENTION: Verify if drive I/O connection is in the running state and the
axis is in a stopped state.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 81
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
3. Click the Hookup Tests category.
4. In the Test Distance field, type 2.0 as the number of revolutions for the
test.
5. Click the Motor Feedback tab.
6. Click Start.
7. Manually move the motor to the specific test distance. In this case, Step 4
dictated 2 revolutions.
8. Click the Motor and Feedback tab.
The Marker and Motor Feedback tests are not supported in Frequency
Control mode.
9. Click Start.
The Logix Designer - Motor and Feedback Test dialog box appears. The
Test State is Executing. TESTING appears on the drive LCD display.
Test Description
Marker Verifies marker detection capability as you rotate the motor shaft.
Motor Feedback Verifies feedback connections are wired correctly as you rotate the motor shaft.
Motor and Feedback
Verifies motor power and feedback connections are wired correctly as you command the
motor to rotate.
82 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
When the test completes successfully, the Test State changes from
Executing to Passed.
10. Click OK.
This dialog box appears asking if the direction was correct.
11. Click Yes.
12. Click Accept Test Results.
13. If the test fails, this dialog box appears.
Tune the Axes
Tuning the Axes is not applicable when using the Frequency Control method.
Follow these steps to tune the axes.
1. Verify that the load is still removed from the axis being tuned.
ATTENTION: Verify if drive I/O connection is in the running state and the
axis is in a stopped state.
ATTENTION: To reduce the possibility of unpredictable motor
response, tune your motor with the load removed first, then reattach
the load and perform the tuning procedure again to provide an
accurate operational response.
a. Click OK.
b. Verify the DC Bus voltage.
c. Verify unit values entered in the
Scaling category.
d. Return to step 9
and run the test
again.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 83
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
2. Click the Autotune category.
3. Type values for Travel Limit and Speed.
In this example, Travel Limit = 5 and Speed = 10. The actual value of
programmed units depending on your application.
4. From the Direction pull-down menu, choose a setting appropriate for
your application.
The default setting is Forward Uni-directional.
5. Edit other fields as appropriate for your application.
6. Click Start.
The Logix Designer - Autotune dialog box appears. When the test
completes, the Test State changes from Executing to Success.
Tuned values populate the Loop and Load Parameters tables. Actual
bandwidth values (Hz) depend on your application and can require
adjustment once motor and load are connected.
7. Click Accept Tuned Values.
8. Click OK to close the Logix Designer - Autotune dialog box.
84 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 3 Configuring the PowerFlex 527 Drive with Integrated Motion
9. Click OK to close the Axis Properties dialog box.
10. If the test fails, this dialog box appears.
11. Repeat Test and Tune the Axes for each axis.
a. Click OK.
b. Make an adjustment to motor velocity.
c. See the Integrated Motion on the
EtherNet/IP Network: Configuration
and Startup User Manual, publication
MOTION-UM003
for more
information.
d. Return to step 6
and run the test again.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 85
Chapter 4
Chapter
Chapter
PowerFlex 527 Integrated Safe Torque-Off
This chapter introduces you to how the PowerFlex 527 integrated safe torque-
off feature meets the requirements of Performance Level e (PLe), Category 3
according to EN ISO 13849, and SIL CL3 according to IEC 61508,
EN 61800-5-2, and EN 62061.
Certification The TÜV Rheinland group has approved PowerFlex 527 drives with integrated
safe torque-off for use in safety-related applications up to PLe, Category 3
according to EN ISO 13849, and SIL CL3 according to IEC 61508, EN 61800-5-2,
and EN 62061, in which removing the motion-producing power is considered
to be the safe state.
See CE Conformity
on page 37 for more information regarding certification.
Important Safety Considerations
The system user is responsible for the following:
Validation of any sensors or actuators connected to the system.
Completing a machine-level risk assessment.
Certification of the machine to the desired EN ISO 13849 performance
level or EN 62061 SIL level.
Project management and proof testing performed in accordance with
EN ISO 13849.
Category 3 Requirements According to ISO 13849
Safety-related parts are designed with these attributes:
A single fault in any of these parts does not lead to the loss of the safety
function.
A single fault is detected whenever reasonably practicable.
Accumulation of undetected faults can lead to the loss of the safety
function and a failure to remove motion producing power from the
motor.
Topic Page
Certification 85
Description of Operation 86
Probability of Dangerous Failure Per Hour (PFH) 86
Safe Torque-Off (STO) Feature 87
Out-of-Box (OOB) Safety State 88
Safe Torque-Off Status 90
Explicit Messages 91
86 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 4 PowerFlex 527 Integrated Safe Torque-Off
Stop Category Definition
Stop category 0 as defined in EN 60204 or Safe Torque-Off as defined by
EN 61800 5 2 is achieved with immediate removal of motion-producing power
to the actuator.
Performance Level (PL) and Safety Integrity Level (SIL)
For safety-related control systems, Performance Level (PL), according to
EN ISO 13849, and SIL levels, according to EN 61508 and EN 62061, include a
rating of the system's ability to perform its safety functions. All of the safety-
related components of the control system must be included in both a risk
assessment and the determination of the achieved levels.
Refer to the EN ISO 13849, EN 61508, and EN 62061 standards for complete
information on requirements for PL and SIL determination.
Description of Operation The Safe Torque-Off (STO) feature provides a method, with sufficiently low
probability of failure, to force the power-transistor control signals to a disabled
state. When the command to allow torque ceases, all of the drive output-power
transistors are released from the On state. This results in a condition where the
motor is coasting (stop category 0). Disabling the power transistor output does
not provide mechanical isolation of the electrical output that is required for
some applications.
The PowerFlex 527 drive STO function response time is less than 12 ms.
Response time is the delay between the time the drive STO function receives
the STO request and the time when motion producing power is removed from
the motor.
Probability of Dangerous
Failure Per Hour (PFH)
Safety-related systems are classified as operating in a High-demand/
continuous mode where the frequency of demands for operation made on a
safety-related system is greater than once per year.
The SIL value for a High-demand/continuous mode safety-related system is
directly related to the probability of a dangerous failure occurring per
hour (PFH).
PFH Data
This PFH calculation is based on the equations from EN 61508 and show worst-
case values.
Determination of safety parameters is based on the assumptions that the
system operates in High-demand mode and that the safety function is
requested at least once a year.
IMPORTANT In the event of a malfunction, the most likely stop category is category 0.
When designing the machine application, timing and distance must be
considered for a coast to stop. For more information regarding stop
categories, refer to EN 60204-1.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 87
Chapter 4 PowerFlex 527 Integrated Safe Torque-Off
Table 6 provides data for a 20-year proof test interval and demonstrates the
worst-case effect of various configuration changes on the data.
Safe Torque-Off (STO)
Feature
The safe torque-off circuit, when used with suitable safety components,
provides protection according to EN ISO 13849 (PLe), Category 3 or according
to IEC EN 61508, EN 61800-5-2, and EN 62061 (SIL CL3). All components in the
system must be chosen and applied correctly to achieve the desired level of
operator safeguarding.
The safe torque-off circuit is designed to safely turn off all of the output-power
transistors. You can use the safe torque-off circuit in combination with other
safety devices to achieve the stop and protection-against-restart as specified in
IEC 60204-1.
Safe Torque-Off Feature Bypass
PowerFlex 527 drives do not operate without a safety circuit or safety bypass
wiring. For applications that do not require the safe torque-off feature, you
must install jumper wires to bypass the safe torque-off circuitry.
PowerFlex 527 drives ship with the safety control in the out-of-box state and
with a safety bypass jumper in place. In this configuration, the PowerFlex 527
safe torque-off function is disabled.
IMPORTANT Determination of safety parameters is based on the assumptions that
the system operates in High-demand mode and that the safety function
is requested at least once every three months.
Table 6 - PFD and PFH Data
Attribute Value (Hardwired and Network)
PFD (average) 1.53E-4
PFH 1.91E-9
SIL CL 3
PL e
Category 3
MTTFd (years) 166
DCavg (%) 90 (medium)
HFT 1 (1oo2)
Mission time (years) 20
ATTENTION: This option is suitable only for performing mechanical work on
the drive system or affected area of a machine. It does not provide
electrical safety.
SHOCK HAZARD: In Safe Torque-Off mode, hazardous voltages can still be
present at the drive. To avoid an electric shock hazard, disconnect power to
the system and verify that the voltage is zero before performing any work on
the drive.
88 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 4 PowerFlex 527 Integrated Safe Torque-Off
Safe Torque-Off Bypass Wiring
As-Shipped Safety Configuration
The PowerFlex 527 drive is shipped with:
Safety control in out-of-box state
Safety Bypass Jumper installed
In this configuration, the PowerFlex 527 safe torque-off function is disabled.
Out-of-Box (OOB) Safety
State
The PowerFlex 527 drives ship in the out-of-box safety state.
Recognizing the Out-of-Box State
The safety control state can be read from the axis tag AxisSafetyState, or by
using a MSG command in the Logix Designer application to read the Safety
Supervisor State.
If the state is “Waiting for TUNID” (8) or “Waiting for TUNID with Torque
Permitted” (51), then the safety control is in the out-of-box state.
Restoring the Drive to the Out-of-Box State
After the integrated safety connection configuration is applied to the
PowerFlex 527 drive at least once, you can follow these steps to restore your
PowerFlex 527 drive to the out-of-box state.
IMPORTANT If safe torque-off is not required, the drive must be returned to the
as-shipped safety configuration to allow operation.
IMPORTANT If the Safety Bypass Jumper is misplaced, it is acceptable to wire the S1,
S2, and S+ input terminals together.
S1 S2 S+
Safety Bypass Jumper
Hardwired Safety Inputs
Table 7 - Safety Supervisor State: Values
Value Definition Definition Mode
2 Idle No active connections Network
4 Executing Normal running state Network
7 Configuring Transition state Network
8 Waiting for TUNID Out-of-Box state Hardwired
51
Waiting for TUNID with Torque
Permitted
Out-of-Box state Hardwired
52 Executing with Torque Permitted STO Bypass state Network
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 89
Chapter 4 PowerFlex 527 Integrated Safe Torque-Off
1. Right-click the PowerFlex 527 drive you created, and choose Properties.
Click the Connection tab.
The Connection tab appears.
2. Check Inhibit Module.
3. Click Apply, then click the Safety tab.
The Safety tab appears.
4. In the Configuration Ownership field, click Reset Ownership.
The safety connection must be inhibited before the reset is attempted. If
any active connection to the drive is detected, the reset is rejected.
5. Cycle drive power.
IMPORTANT Only authorized personnel should attempt Reset Ownership.
90 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 4 PowerFlex 527 Integrated Safe Torque-Off
The drive is in the out-of-box state.
6. On power-up, make sure that the drive does not have a safety connection.
Safe Torque-Off Status This section describes the safety-related status that is available to the motion
controller.
Axis Tags
When a PowerFlex 527 Add-On-Profile (AOP) is added to a Logix I/O tree, Axis
tags are added to the controller tags.
Table 8
lists the safety-related STANDARD tags that are added when a new
AXIS_CIP_DRIVE axis is defined.
IMPORTANT If power to the drive is not cycled after step 4, the drive does not
transition to the out-of-box state and maintains STO function.
IMPORTANT When the drive returns to the out-of-box state, the STO function
reverts to hardwired control.
ATTENTION: The status data described in this section is STANDARD data
(not SAFETY data) and may not be used as part of a safety function.
Table 8 - Safety-Related Axis Tags
Logix Designer Tag Name Attribute
[bit]
Type Description
AxisFault 34 DINT
GuardFaultStatus [5] BOOL STO Fault - Hardwired
SafetyFaultStatus [8] BOOL STO Fault - Network
GuardStatus
(1)
980 DINT
GuardOKStatus [0] BOOL Not STO Fault - Hardwired
GuardGateDriveOutputStatus [2] BOOL Torque Permitted - Hardwired
GuardStopInputStatus [3] BOOL Safety Inputs Enabled
GuardStopRequestStatus [4] BOOL Torque Disabled - Hardwired
GuardFault
(1)
981 DINT
GuardStopInputFault [9] BOOL STO Fault - Hardwired
GuardGateDriveFault [2] BOOL Internal STO Circuit Fault - Hardwired
CIPAxisFaultsRA 903 LINT
SafetyModuleCommunicationErrorFault [28] BOOL Loss of communications to Safety Control
CIPAxisAlarmsRA 904 LINT
SafetyModuleCommunicationErrorAlarm [28] BOOL Loss of communications to Safety Control
CIPInitializationFaultsRA 910 DINT
InvalidSafetyFirmwareFault [14] BOOL Invalid Safety Control Firmware
CIPStartInhibits 676 INT
SafeTorqueOffActiveInhibit [5] BOOL Torque Disabled - Network
CIPStartInhibitsRA 912 INT
SafeTorqueOffInhibit [5] BOOL Torque Disabled - Hardwired
AxisSafetyState 760 INT Safety Supervisor State
AxisSafetyStatus
(1)
761 DINT
SafetyFaultStatus [0] BOOL Status of SI.SafetyFault
SafetyResetRequestStatus [1] BOOL Status of SO.ResetRequest
SafetyResetRequiredStatus [2] BOOL Status of SI.ResetRequired
SafeTorqueOffActiveStatus [3] BOOL Status of SO.SafeTorqueOff
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 91
Chapter 4 PowerFlex 527 Integrated Safe Torque-Off
Explicit Messages Explicit messages can be used to obtain additional diagnostic information
from the safety control using a MSG instruction.
Safety Supervisor State
The Safety Supervisor State provides information on the state of the CIP Safety
connection and the mode of operation.
Propose TUNID Blocked
The attribute Propose TUNID Blocked can be used to check if the drive is in a
state where it will accept a safety connection. If the drive is enabled, it will not
accept a safety connection.
SafeTorqueDisabledStatus [4] BOOL Status of SI.TorqueDisabled
SafetyOutputConnectionClosed [30] BOOL 1 if all output connections are closed
SafetyOutputConnectionIdleStatus [31] BOOL 1 if output controller is in program mode
AxisSafetyFaults
(1)
763 DINT
SafetyCoreFault [1] BOOL Loss of communications to Safety Control
SafeTorqueOffFault [3] BOOL Status of SI.SafetyFault
(1) Bits not shown are always zero.
Table 8 - Safety-Related Axis Tags (Continued)
Logix Designer Tag Name Attribute
[bit]
Type Description
Safety Supervisor State: MSG
Parameter Value Description
Service Code 0x0E Get Attribute Single
Class 0x39 Safety Supervisor
Instance 1
Attribute 0x0B Device Status
Data Type SINT Unsigned Short Integer
Safety Supervisor State: Values
Value Definition Definition Mode
2 Idle No Active Connections Network
4 Executing Normal Running State Network
7 Configuring Transition State Network
8 Waiting for TUNID Out-of-Box State Hardwired
51
Waiting for TUNID
with Torque Permitted
Out-of-Box State Hardwired
52
Executing
with Torque Permitted
STO Bypass State Network
Propose TUNID Blocked: MSG
Parameter Value Description
Service Code 0x0E Get Attribute Single
Class 0x5A Safety Stop Functions
Instance 0 Class Attribute
Attribute 0x65 STO Mode
Data Type SINT Unsigned Short Integer
92 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 4 PowerFlex 527 Integrated Safe Torque-Off
Safe Torque-Off Mode
The attribute STO Mode can be used to check if the PowerFlex 527 is in STO
Bypass Mode.
Safe Torque-Off Faults
When a safety fault is indicated in any of the following tags:
SI.SafetyFault
Axis.SafetyFaultStatus
Axis.SafetyTorqueOffFault
The cause of the fault can be read using an explicit message.
Safe Torque-Off Mode: Values
Value Definition
0 Accept a Safety Connection
1 Block a Safety Connection
Safe Torque-Off Mode: MSG
Parameter Value Description
Service Code 0x0E Get Attribute Single
Class 0x5A Safety Stop Functions
Instance 1 Axis Number
Attribute 0x104 STO Mode
Data Type SINT Unsigned Short Integer
Safe Torque-Off Mode: Values
Value Definition
1 Normal Operation
2 STO Bypass Mode
Safe Torque-Off Fault Type: MSG
Parameter Value Description
Service Code 0x0E Get Attribute Single
Class 0x5A Safety Stop Functions
Instance 1 Axis Number
Attribute 0x108 STO Fault Type
Data Type SINT Unsigned Short Integer
Safe Torque-Off Fault Type: Values
Value Definition
1No Fault
3 Circuit Error
102 Hardwired Input Discrepancy
104 Hardwired Input in Network Mode
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 93
Chapter 5
Hardwired Control of Safe Torque-Off
This chapter introduces you to how the PowerFlex 527 integrated safe torque-
off feature is configured for hardwired control of safe torque-off.
Description of Operation The safe torque-off feature provides a method, with sufficiently low probability
of failure, to force the power-transistor control signals to a disabled state. If
either hardwired safety input is de-energized, all drive output-power
transistors are released from the On state. This results in a condition where the
drive is coasting (stop category 0). Disabling the power transistor output does
not provide mechanical isolation of the electrical output that is required for
some applications.
Selection of Hardwired Safe Torque-Off
To select hardwired control of safe torque-off (STO):
The safety control must be in the out-of-box state.
The Safety Bypass Jumper must be removed.
An appropriate safety device must be connected to terminals S1, S2, and
01 (Digital Common).
Operation of Hardwired Safe Torque-Off
Under normal operation, the safe torque-off inputs are energized. If either of
the safety enable inputs are de-energized, then all output power transistors
turn off. The safe torque-off response time is less than 12 ms.
Topic Pages
Description of Operation 93
Safe Torque-Off Connector Data 96
Wire the Safe Torque-Off Circuit 96
Safe Torque-Off Specifications 97
ATTENTION: If any of the safety enable inputs de-energize, the Start Inhibit
field indicates SafeTorqueOffInhibit and the GuardStopRequestStatus bit of
the axis GuardStatus tag are set to 1. Both inputs must be de-energized
within 1 second and re-energized within 1 second to avoid
GuardStopInputFault conditions.
94 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 5 Hardwired Control of Safe Torque-Off
System Operation when Inputs are Meeting Timing Requirements
Troubleshoot the Safe Torque-Off Function
Event Description
1 At least one input is switched off. GuardStopRequestStatus bit is set to 1.
2
Second input is switched off within 1 second. This must always occur within 1 second to help
prevent a GuardStopInputFault condition.
3 First input is switched on.
4 Second input is switched on within 1 second of event 3.
5
Both inputs are in the ON state simultaneously within 1 second. As a result, the GuardStopInputFault
is not posted.
6
The GuardStopRequestStatus bit is set back to 0 if both inputs are in the ON state for 100 ms
continuously (100 ms debounce time).
(Safety Input) S1
13456
Start Permitted
OK
Permit Torque
Torque Permitted
Torque Permitted
(Safety Input) S2
GuardFault
SafeTorqueOInhibit
GuardOKStatus
GuardGateDriveOutputStatus
GuardStopInputStatus
GuardStopRequestStatus
GuardStopInputFault
2
100 ms Debounce Time
1 second Discrepancy Limit
Start Inhibit
Torque Disabled
Disable Torque
No Fault
No Fault
Torque Disabled
PowerFlex 527 Drive Troubleshooting
Exception Code on Drive Display
Fault Message
Logix Designer
Problem Possible Solutions
SAFE FLT 09 - SS IN GuardStopInputFault
Safe torque-off function mismatch. System does
not allow motion. Safe torque-off mismatch is
detected when safety inputs are in a different
state for more than 1.0 second.
Verify safety wiring and connections:
Wire terminations at safe torque-off (STO)
connector
Cable/header not seated correctly
+24V power
Check state of safety inputs.
Reset error and run proof test.
Return drive for repair if fault continues.
SAFE FLT 01 - GUARD INTERNALFAULT
CPUWatchdogFault
(1)
Drive safety diagnostic detected internal STO
design failure.
•Cycle power.
Return drive for repair if fault continues.
SAFE FLT 03 - GUARD GATE DRIVE
FAULT
SafeTorqueOffFault
(2)
Drive safety diagnostic detected internal STO
design failure.
•Cycle power.
Execute STO function.
Return drive for repair if fault continues.
Hardwired safe torque off input energized when
drive is in network safety mode.
Reset the drive to out-of-box settings, hardwired
safety mode. See Restoring the Drive to the Out-
of-Box State on page 88 for instructions.
(1) Displayed in the LCD display as Module Fault.
(2) Displayed in the LCD display as Safety Fault.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 95
Chapter 5 Hardwired Control of Safe Torque-Off
Figure 1 demonstrates when the safe torque-off mismatch is detected and a
GuardStopInputFault is posted.
Figure 1 - System Operation in the Event that the Safety Enable Inputs Mismatch
When one safety input is turned off, the second input must also be turned off,
otherwise a fault is asserted (See Figure 2 on page 95). The fault is asserted
even if the first safety input is turned on again.
Figure 2 - System Operation in the Event that the Safety Enable Inputs Mismatch Momentarily
ATTENTION: The safe torque-off fault is detected upon demand of the safe
torque-off function. After troubleshooting, a safety function must be
executed to verify correct operation.
IMPORTANT The Safe Torque-Off fault can be reset only if both inputs are in the Off
state for more than 1 second. After the fault reset requirement is
satisfied, an MASR command in the Logix Designer application must be
issued to reset the GuardFault and GuardStopInputFault conditions.
(Safety Input) S1
1 second Discrepancy Limit
No Fault Faulted
No Fault Faulted
Start Inhibited
OK Not OK
Torque Disabled
Stop Requested
Start Permitted
Torque Permitted
(Safety Input) S2
GuardFault
SafeTorqueOInhibit
GuardOKStatus
GuardGateDriveOutputStatus
GuardStopInputStatus
GuardStopRequestStatus
GuardStopInputFault
(Safety Input) S1
1 second
Start Inhibit
Torque Disabled
Torque Disabled
(Safety Input) S2
GuardFault
SafeTorqueOInhibit
GuardOKStatus
GuardGateDriveOutputStatus
GuardStopInputStatus
GuardStopRequestStatus
GuardStopInputFault
96 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 5 Hardwired Control of Safe Torque-Off
Safe Torque-Off Connector
Data
PowerFlex 527 terminals S1, S2, and 01 are used for hardwired control of safe
torque-off.
Terminals for Safe Torque-Off (STO) Connection
Wire the Safe Torque-Off
Circuit
This section provides guidelines for wiring safe torque-off connections to your
PowerFlex 527 drive.
Safe Torque-Off Wiring Requirements
The safe torque-off (STO) connection wire must be copper with 75 °C (167 °F)
minimum rating.
Safe Torque-Off (STO) Connector Pinouts Control
STO Pin Signal Description
01 Digital Common
The return for digital I/O. It is electrically isolated (along with the digital inputs
and encoder power) from the rest of the drive.
S1 Safety 1 Safety input 1.
S2 Safety 2 Safety input 2.
S+ Safety +24V
+24V supply for safety circuit. This is internally tied to the +24V DC source
(terminal 11).
IMPORTANT Digital Common (terminal 01) is common for the digital inputs, the safety
inputs, and the encoder power supply (optional).
R1
11 12 13 14 15 16 17
R2 R5 R6 01 02 03 04 05 06 07
S1 S2 S+
Safety Bypass Jumper
Hardwired Safety Inputs
IMPORTANT The National Electrical Code and local electrical codes take precedence
over the values and methods provided.
IMPORTANT Pin S+ (Safety +24V) is used to disable the safe torque-off function.
When wiring to the STO connector, use an external 24V supply for the
external safety device that triggers the safe torque-off request. To avoid
jeopardizing system performance, do not use pin S+ as a power supply
for the external safety device.
IMPORTANT The National Electrical Code and local electrical codes take precedence
over the values and methods provided.
IMPORTANT Stranded wires must terminate with ferrules to help prevent short
circuits, per table D.7 of EN ISO 13849-2.
Safe Torque-Off (STO) Terminal Wiring
Maximum Wire Size
(1)
(1) Maximum and minimum sizes that the terminal block will accept. These are not recommended wire sizes.
Minimum Wire Size
(1)
Torque
1.3 mm
2
(16 AWG) 0.13 mm
2
(26 AWG)
0.71…0.86 N•m (6.2…7.6 lb•in)
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 97
Chapter 5 Hardwired Control of Safe Torque-Off
Safe Torque-Off
Specifications
To maintain their safety rating, PowerFlex 527 drives must be installed inside
protected control panels or cabinets appropriate for the environmental
conditions of the industrial location. The protection class of the panel or
cabinet must be IP54 or higher.
Safe Torque-Off Signal Specifications
Attribute Value
Safety inputs
(per channel)
Input current < 10 mA
Input ON voltage, max 18…26.4V DC
Input OFF voltage, max 5V DC
Input ON current 10 mA
Input OFF current 500 µA
Pulse rejection width 700 µs
External power supply SELV/PELV
Input type Optically isolated and reverse voltage protected
98 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 5 Hardwired Control of Safe Torque-Off
Notes:
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 99
Chapter
Chapter 6
Network Control of Safe Torque-Off
This chapter describes network control of the safe torque-off function. This
example uses a 1756-L7xS GuardLogix safety controller to issue the safe torque-
off (STO) command over the EtherNet/IP network and the PowerFlex 527 drive
executes the STO command.
Compatible Safety Controllers
The Studio 5000 Logix Designer application:
Version 24.00 or later, provides support for programming,
commissioning, and maintaining the 1756-L7xS GuardLogix safety
controller.
Version 28.00 or later, provides support for programming,
commissioning, and maintaining the Compact GuardLogix 5370 safety
controller.
A 1756-L7xS GuardLogix or Compact GuardLogix 5370 safety controller is
required for network control of the PowerFlex 527 safe torque-off function.
The PowerFlex 527 safety connection can originate from a safety controller that
provides both safety and motion control.
The PowerFlex 527 safety connection can originate from a safety controller that
controls only the safety, while a separate Logix processor controls motion.
Selection of Network Safe Torque-Off
To select network control of safe torque-off:
1. The PowerFlex 527 drive must be added to a 1756-EN2T, 1756-EN2TR,
1756-EN2F, 1756-EN3T, or 1756-EN3TR EtherNet/IP bridge in a 1756-L7xS
GuardLogix controller I/O tree.
2. The 1756-EN2T, 1756-EN2TR, 1756-EN2F, 1756-EN3T, or 1756-EN3TR
EtherNet/IP bridge must be configured for “Safety Only” or “Motion and
Safety”.
3. Download the new configuration to the controller.
The drive display may show fault code “SAFE FLT 03 - GUARD GATE
DRIVE FAULT”.
4. Turn off incoming power to the drive.
Topic Page
Understanding Integrated Safety Drive Replacement 103
Replacing an Integrated Safety Drive in a GuardLogix System 103
Motion Direct Commands in Motion Control Systems 109
Functional Safety Considerations 114
100 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 6 Network Control of Safe Torque-Off
5. Remove the Safety Bypass jumper.
6. Turn on incoming power to the drive.
Any display fault should now be cleared.
Safety Application Requirements
Creating, recording, and verifying the safety signature is also a required part
of the safety application development process. Safety signatures are created by
the safety controller. The safety signature consists of an identification
number, date, and time that uniquely identifies the safety portion of a project.
This signature covers all safety logic, data, and safety I/O configuration.
For safety system requirements, including information on the safety network
number (SNN), verifying the safety signature, and functional verification
tests, see the GuardLogix 5570 and Compact GuardLogix 5370 Reference
Manual, publication 1756-RM099
.
Network Safe Torque-off Specifications
Safe Torque-off Assembly Tags
With network control, a 1756-L7xS GuardLogix safety controller controls the
PowerFlex STO function through the SO.SafeTorqueOff tag in the safety
output assembly.
The SO.Command tags are sent from the GuardLogix safety output assembly
to the PowerFlex 527 to control the safe torque-off function.
The SI.Status tags are sent from the PowerFlex 527 to the GuardLogix safety
input assembly and indicate the PowerFlex 527 safety control status.
The SI.ConnectionStatus tags indicate the status of the safety input
connection.
Table 9 on page 101
lists the SAFETY tags added to the controller tags when a
PowerFlex 527 drive is added to a GuardLogix I/O configuration and the
connection is configured for “Motion and Safety” or for “Safety only”.
IMPORTANT You must read, understand, and fulfill the requirements that are detailed
in this publication before operating a safety system that uses a
GuardLogix controller and PowerFlex 527 drive.
Safe Torque-off Network Specifications
Attribute Value
Safety connection RPI, minimum 6 ms
Input assembly connections 1
Output assembly connections 1
Integrated safety open request support Type 1 and Type 2 requests
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 101
Chapter 6 Network Control of Safe Torque-Off
The “Attribute” values that are listed are the Assembly Object attribute values.
STO Fault Reset
If a PowerFlex 527 drive safety control detects a fault, the input assembly tag
SI.SafetyFault is set to 1. A transition from logic 0 to 1 of the SO.Reset tag is
required after the SO.SafeTorqueOff tag has transitioned from logic 0 to 1.
To reset Axis.SafetyFault, a MAFR command must be issued.
See Figure 3 on page 102 for an understanding of the PowerFlex 527 STO Fault
reset functionality.
Table 9 - Safe Torque-off Assembly Tags
Logix Designer Tag Name
Attribute
[bit]
Type Description
SI.ConnectionStatus
(1)(2)
(1) Bits not listed are always zero.
(2) ConnectionStatus is determined by the Safety Validator in the GuardLogix controller. For more information, see the Safety
Connection Status table in the GuardLogix 5570 and Compact GuardLogix 5370 Reference Manual, publication 1756-RM099
.
DINT
SI.RunMode [0] BOOL
See Table 10
.
SI.ConnectionFaulted [1] BOOL
SI.Status
(1)(3)
(3) The Status is sent from the drive to the controller using the CIP Safety protocol.
0x1A0 SINT
SI.TorqueDisabled [0] BOOL 0 = Torque Permitted; 1 = Torque Disabled
SI.SafetyFault [6] BOOL 1 = STO Fault present
SI.ResetRequired [7] BOOL 1 = A reset is required
SO.Command
(1)(4)
(4) The Command is sent from the controller to the drive using the CIP Safety protocol.
0x180 SINT
SO.SafeTorqueOff [0] BOOL 0 = Disable Permit; 1 = Permit Torque
SO.Reset [7] BOOL
01 = Reset STO Fault
ATTENTION: Only data that is listed in Table 10 is SAFETY data with SIL 3
integrity.
Table 10 - Safety Connection Status
RunMode Status
ConnectionFaulted
Status
Safety Connection Operation
1 = Run 0 = Valid
Data is actively being controlled by the producing device. The
producing device is in Run mode.
0 = Idle 0 = Valid
The connection is active and the producing device is in the Idle
state. The safety data is reset to zero.
0 = Idle 1 = Faulted
The safety connection is faulted. The state of the producing
device is unknown. The safety data is reset to zero.
11Invalid state.
IMPORTANT Transition of the SO.SafeTorqueOff tag to logic 1 must always be
executed before transition of the SO.Reset tag to logic 1.
IMPORTANT PowerFlex 527 drives enter the STO Fault state if any STO function fault
is detected. See Table 11 on page 102
for integrated safety
troubleshooting.
IMPORTANT An STO Fault sets the Axis.SafetyFault tag. After the STO Fault is reset, a
MAFR command must be issued by the motion controller to clear the
Axis.SafetyFault tag to enable motion.
102 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 6 Network Control of Safe Torque-Off
Figure 3 - Reset Safe Torque-Off Fault Diagram
Troubleshoot Network Safe Torque-Off
Drv:SO.SafeTorqueO
Disable Torque Permit Torque
Faulted
SO.ResetRequest
No Fault
No Fault
No Fault
Faulted (cleared by MAFR)
No Fault
Start Inhibited
Reset Not Required
Reset Not Required Reset Required
Torque Disabled
Start Permitted
Torque Permitted
Torque Disabled
Torque Permitted
Drv:SO.ResetRequest
Drv:SI.TorqueDisabled
Drv:SI.SafetyFault
DrvSI:ResetRequired
Axis.SafetyFault
Axis.SafeTorqueOActiveInhibit
Axis.SafetyFaultStatus
Axis.SafetyResetRequestStatus
Axis.SafetyResetRequiredStatus
Axis.SafeTorqueOActiveStatus
Axis.SafeTorqueODisabledStatus
Axis.SafeTorqueOFault
Permit Torque Disable Torque
Table 11 - PowerFlex 527 Drive Troubleshooting
Exception Code on Drive Display
Fault Message
Logix Designer
Problem Possible Solutions
SAFE FLT 01 - GUARD INTERNAL FAULT
CPUWatchDogFault
(1)
Drive safety diagnostic detected internal
STO design failure.
Cycle power.
Return drive for repair if fault
continues.
FLT AXIS FLT M28 - SAFETY COMM
SafetyModuleCommunicationErrorFault
(1)
Drive safety diagnostic detected internal
STO design failure.
Cycle power.
Return drive for repair if fault
continues.
SAFE FLT 03 - GUARD GATE DRIVE FAULT
(STO Fault Type = 3)
SafeTorqueOffFault
(2)
Drive safety diagnostic detected internal
STO design failure
Cycle power.
Execute STO function.
Return drive for repair if fault
continues.
SAFE FLT 03 - GUARD GATE DRIVE FAULT
(STO Fault Type = 104)
SafeTorqueOffFault
(2)
Hardwired input energized in network
mode.
Remove power.
Remove any connection to hardwired
safety inputs.
Restore power.
INIT FLT M14 - INVALID SAFETY FIRMWARE
InvalidSafeyFirmwareFault
(2)
The safety firmware is not compatible
with the drive firmware, or the main
safety firmware is missing.
Cycle power.
Upgrade drive firmware.
Return drive for repair if fault
continues.
(1) Displayed in the LCD display as Module Fault.
(2) Displayed in the LCD display as Safety Fault.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 103
Chapter 6 Network Control of Safe Torque-Off
Understanding Integrated
Safety Drive Replacement
GuardLogix controllers retain I/O device configuration onboard and are able
to download the configuration to the replacement device.
Replacing a PowerFlex 527 drive that sits on an integrated safety network is
more complicated than replacing standard devices because of the Safety
Network Number (SNN). The device number and SNN make up the safety
device's DeviceID. Safety devices require this more complex identifier to make
sure that duplicate device numbers do not compromise communication
between the correct safety devices. The SNN is also used to provide integrity
on the initial download to the PowerFlex 527 drive.
When the Logix Designer application is online, the Safety tab of the Module
Properties dialog box displays the current configuration ownership. When the
opened project owns the configuration, Local is displayed.
A communication error is displayed if the module read fails. See Replacing an
Integrated Safety Drive in a GuardLogix System for integrated safety drive
replacement examples.
Replacing an Integrated
Safety Drive in a
GuardLogix System
If you are relying on a portion of the integrated safety system to maintain SIL 3
behavior during drive replacement and functional testing, do not use the
Configure Always feature.
Use the Configure Always feature when you are not relying on the entire
routable integrated safety control system to maintain PLe/SIL 3 behavior
during the replacement and functional testing of a PowerFlex 527 drive. Drive
replacement is configured on the Safety tab of the GuardLogix controller.
Setting the SNN with a GuardLogix Controller
IMPORTANT If the replacement PowerFlex 527 drive was used previously, clear its
existing configuration before installing it on a safety network by
resetting the drive to its out-of-box condition. To see how this is done,
see Out-of-Box (OOB) Safety State
on page 88.
104 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 6 Network Control of Safe Torque-Off
Replacement with “Configure Only When No Safety Signature Exists”
Enabled
When a PowerFlex 527 drive is replaced and the DeviceID of the new drive
matches the original, you can download the configuration from the safety
controller. The DeviceID is a combination of the node/IP address and the
safety network number (SNN), and is updated whenever the SNN is set.
If the project is configured as Configure Only When No Safety Signature
Exists, follow the appropriate instructions in Table 12
to replace a PowerFlex
527 drive based on your scenario. Once you have completed the steps correctly
and the DeviceID matches the original, the safety controller can download the
proper drive configuration and re-establish the safety connection.
Scenario 1 – Replacement Integrated Safety Drive Is Out-of-Box and Safety Signature
Exists
1. Remove and replace the existing integrated safety drive.
2. Right-click the replacement drive and choose Properties.
The General tab appears in the Module Properties dialog box.
Table 12 - Replacing a PowerFlex 527 Drive
GuardLogix Safety
Signature Exists
GuardLogix Safety Signature Exists Action Required
No No SNN (out-of-box)
None. The module is ready for use.
Yes or No Same SNN as original safety task configuration
Yes No SNN (out-of-box) See Scenario 1 on page 104
.
Yes
Different SNN than original safety task
configuration
See Scenario 2 on page 106
.
No See Scenario 3 on page 108
.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 105
Chapter 6 Network Control of Safe Torque-Off
3. Click to the right of the Safety Network Number (SNN).
The Safety Network Number dialog box appears.
4. Click Set.
5. Verify that the Network Status (NET) status indicator is alternating red/
green on the correct drive.
6. Click Yes to set the SNN and accept the replacement drive.
7. Power cycle the drive.
8. Follow your company-prescribed procedures to functionally test the
replacement drive and system and to authorize the system for use.
106 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 6 Network Control of Safe Torque-Off
Scenario 2 – Replacement Integrated Safety Drive SNN is Different from Original and
Safety Signature Exists
1. Remove and replace the existing integrated safety drive.
2. Right-click the replacement drive and choose Properties.
3. Click the Safety tab.
4. Click Reset Ownership.
5. Click OK.
6. Right-click the replacement drive and chooses Properties.
The General tab appears in the Module Properties dialog box.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 107
Chapter 6 Network Control of Safe Torque-Off
7. Click to the right of the Safety Network Number (SNN).
The Safety Network Number dialog box appears.
8. Click Set.
9. Verify that the Network Status (NET) status indicator is alternating red/
green on the correct drive.
10. Power cycle the drive.
11. Follow your company-prescribed procedures to functionally test the
replacement drive and system and to authorize the system for use.
108 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 6 Network Control of Safe Torque-Off
Scenario 3 – Replacement Integrated Safety Drive SNN is Different from Original and no
Safety Signature Exists
1. Remove and replace the existing integrated safety drive.
2. Right-click the replacement drive and choose Properties.
3. Click the Safety tab.
4. Click Reset Ownership.
5. Click OK.
6. Power cycle the drive.
7. Follow your company-prescribed procedures to functionally test the
replacement drive and system and to authorize the system for use.
Replacement with “Configure Always” Enabled
When the Configure Always feature is enabled, the controller automatically
checks for and connects to a replacement drive that meets all the following
requirements:
The controller has configuration data for a compatible drive at that
network address.
The drive is in the Out-of-box condition or has an SNN that matches the
configuration.
If the project is configured for Configure Always, follow the appropriate steps
to replace a PowerFlex 527 drive.
ATTENTION: Enable the Configure Always feature only if the entire
integrated safety control system is not being relied on to maintain SIL 3
behavior during the replacement and functional testing of a PowerFlex 527
drive. Do not place drives that are in the Out-of-box condition on an
integrated safety network when the Configure Always feature is enabled,
except while following this replacement procedure.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 109
Chapter 6 Network Control of Safe Torque-Off
Follow these steps when the Configure Always feature is enabled.
1. Remove and replace the existing integrated safety drive.
2. Right-click the replacement drive and choose Properties.
3. Click the Safety tab.
4. Click Reset Ownership.
5. Click OK.
6. Follow your company-prescribed procedures to functionally test the
replacement drive and system and to authorize the system for use.
Motion Direct Commands in
Motion Control Systems
You can use the Motion Direct Command (MDC) feature to initiate motion
while the controller is in Program mode, independent of application code that
is executed in Run mode. These commands let you perform a variety of
functions, for example, move an axis, jog an axis, or home an axis. See the
Logix 5000 Controllers Motion Instructions Reference Manual, publication
MOTION-RM002
for more information.
A typical use might involve a machine integrator testing different parts of the
motion system while the machine is being commissioned, or a maintenance
engineer, under certain restricted scenarios in accordance with safe machine
operating procedures, wanting to move an axis (like a conveyor) to clear a jam
before resuming normal operation.
If Then
The drive is in the Out-of-box condition
Go to step 6.
No action is needed for the GuardLogix controller to take
ownership of the drive.
An SNN mismatch error occurs Go to the next step to reset the drive to the Out-of-box condition.
ATTENTION: To avoid personal injury or damage to equipment, follow these
rules regarding Run mode and Program mode.
Only authorized, trained personnel with knowledge of safe machine
operation should be allowed to use Motion Direct Commands.
Additional supervisory methods, like removing the controller keyswitch,
should be used to maintain the safety integrity of the system after returning
the safety controller to RUN mode.
110 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 6 Network Control of Safe Torque-Off
Understanding STO Bypass When Using Motion Direct Commands
If a Safety-only connection between the GuardLogix safety controller and the
PowerFlex 527 drive was established at least once after the drive was received
from the factory, the drive does not allow motion while the safety controller is
in Program mode by default.
This is because the safety task is not executed while the GuardLogix safety
controller is in Program mode. This applies to applications running in a single
safety controller (with Motion and Safety connections). When an integrated
safety drive has a Motion connection to a standard controller and a separate
Safety connection to a dual-safety controller, the standard controller can
transition to Program mode while the safety controller stays in Run mode and
continues to execute the safety task.
However, PowerFlex 527 drive systems are designed with a bypass feature for
the STO function in single-safety controller configurations. You can use the
MDC feature to allow motion while following all necessary and prescribed
steps per your machine's safety operating procedures.
Logix Designer Application Warning Messages
When the controller is in Run mode, executing safety functions, the
PowerFlex 527 drive follows the commands that it receives from the safety
controller. The controller will report Safety state = Running and Axis state =
Stopped/Running, as shown in Figure 4
.
Figure 4 - Safety State Indications When Controller is in Run Mode (Safety Task Executing)
ATTENTION: Consider the consequences of allowing motion through the use
of MDC when the controller is in Program mode. You must acknowledge
warning messages in the Logix Designer application that warn of the drive
bypassing the STO function and unintended motion can occur. The
integrated safety drive does not respond to requests of the STO function if
MDC mode is entered.
ATTENTION: It is your responsibility to maintain machine safety integrity
while executing motion direct commands. One alternative is to provide
ladder logic for Machine Maintenance mode that leaves the controller in Run
mode with safety functions executing.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 111
Chapter 6 Network Control of Safe Torque-Off
When the controller transitions to Program mode, the integrated safety drive
is in the safe state and torque is not permitted. The controller will report Safety
state = Not Running and Axis state = Start Inhibited, as shown in Figure 5
.
Figure 5 - Safety State Indications After Controller Transitions to Program Mode
When you issue a motion direct command to an axis to produce torque in
Program mode, for example MSO or MDS, with the safety connection present
to the drive, a warning message is presented before the motion direct
command is executed, as shown in Figure 6
.
Figure 6 - STO Bypass Prompt When the Safety Controller is in Program Mode
The warning in Figure 6 is displayed the first time a motion direct command is
issued.
After you acknowledge the warning message by clicking Yes, torque is
permitted by the drive and a warning message is indicated in the software as
shown in Figure 7 on page 112
. The controller will report Safety state = Not
Running (Torque Permitted), Axis state = Stopped/Running, and Persistent
Warning = Safe Torque Off Bypassed.
IMPORTANT Switch the controller to Run mode to exit Motion Direct Command mode
and end the bypass of the STO function.
112 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 6 Network Control of Safe Torque-Off
Figure 7 - Safety State Indications After Controller Transitions to Program Mode (MDC Executing)
Torque Permitted in a Multi-workstation Environment
The warning in Figure 8 is displayed to notify a second user working in a
multi-workstation environment that the first user has placed the integrated
safety drive in the STO state and that the current action is about to bypass the
STO state and permit torque.
Figure 8 - STO Bypass Prompt When MDC is Issued in Multi-workstation Environment
Warning Icon and Text in Axis Properties
In addition to the other warnings that require your acknowledgment, the
Logix Designer application also provides warning icons and persistent
warning messages in other Axis Properties dialog boxes when the integrated
safety drive is in STO Bypass mode.
IMPORTANT The persistent warning message text Safe Torque Off bypassed appears
when a motion direct command is executed.
The warning message persists - even after the dialog is closed and
reopened - as long as the integrated safety drive is in STO Bypass mode.
The persistent warning message is removed only after the integrated
safety drive is restored to the Safe state.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 113
Chapter 6 Network Control of Safe Torque-Off
Axis and Safe State Indications on the Hookup Services Dialog Box
Axis and Safe State Indications on Motion Direct Commands Dialog Box
Axis and Safe State Indications on the Motion Console Dialog Box
114 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 6 Network Control of Safe Torque-Off
Functional Safety
Considerations
ATTENTION: Before maintenance work can be performed in Program mode,
the developer of the application must consider the implications of allowing
motion through motion direct commands and should consider developing
logic for runtime maintenance operations to meet the requirements of
machine safety operating procedures.
ATTENTION: Motion is allowed and the STO function is not available when
motion direct commands are used in Program mode.
Motion direct commands that are issued when the controller is in Program
mode cause the drive to bypass the STO Active condition.
It is your responsibility to implement additional preventive measures to
maintain safety integrity of the machinery during execution of motion direct
commands in Program mode.
ATTENTION: To avoid personal injury and damage to equipment in the event
of unauthorized access or unexpected motion during authorized access,
return the controller to Run mode and remove the key before leaving the
machine unattended.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 115
Chapter 7
Chapter
Troubleshooting
This chapter provides troubleshooting tables and related information for your
PowerFlex 527 drive.
Safety Precautions Observe the following safety precautions when troubleshooting your
PowerFlex 527 drive.
Interpret Status Indicators See these troubleshooting tables to identify faults, potential causes, and the
appropriate actions to resolve the fault. If the fault persists after attempting to
troubleshoot the system, contact your Rockwell Automation sales
representative for further assistance.
Display Interface
The LCD display provides fault messages and troubleshooting information by
using the soft menu items and navigation buttons. See Understanding the
PowerFlex 527 Display and Indicators on page 46 for more information.
Topic Page
Safety Precautions 115
Interpret Status Indicators 115
General Troubleshooting 122
Logix 5000 Controller and Drive Behavior 123
ATTENTION: Capacitors on the DC bus can retain hazardous voltages after
input power has been removed. Before working on the drive, measure the DC
bus voltage to verify it has reached less than 50V DC, or wait three minutes.
Failure to observe this precaution could result in severe bodily injury or loss
of life.
ATTENTION: Do not attempt to defeat or override the drive fault circuits.
You must determine the cause of a fault and correct it before you attempt to
operate the system. Failure to correct the fault could result in personal
injury and/or damage to equipment as a result of uncontrolled machine
operation.
ATTENTION: Provide an earth ground for test equipment (oscilloscope) used
in troubleshooting. Failure to ground the test equipment could result in
personal injury.
116 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 7 Troubleshooting
Fault Codes
The fault code tables are designed to help you determine the source of the fault
or exception. When a fault condition is detected, the drive performs the
appropriate fault action, the fault is displayed, and the fault is added to a
persistent fault log (along with diagnostics data). The earlier faults have
priority to be displayed.
The drive removes the fault text from the display when a Fault Reset service is
sent from the controller and the fault is no longer active. If a fault is still active
following a Fault Reset service, the fault is again posted to the display and
written to the fault log.
See Troubleshoot the Safe Torque-Off Function
on page 94 for information on
troubleshooting SAFE FLT fault codes.
Fault Code Summary
Fault Code Type Description
FLT Sxx
Standard runtime axis exceptions.
FLT Mxx
INIT FLT Sxx
Exceptions that prevent normal operation and occur during the initialization process.
INIT FLT Mxx
INHIBIT Sxx
Exceptions that prevent normal operation and indicate whenever the drive is active.
INHIBIT Mxx
NODE FLTxx Exceptions that prevent normal operation of the drive.
NODE ALARM xx
Exceptions that prevent normal operation of the drive, but do not result in any action
other than reporting the alarm to the controller.
Fault codes triggered by conditions that fall outside factory set limits
are identified by FL at the end of the display message. For example,
FLT S07 – MTR OVERLOAD FL.
Fault codes triggered by conditions that fall outside user set limits are
identified by UL at the end of the display message. For example,
FLT S08 – MTR OVERLOAD UL.
INIT FLT S03 NVMEM CHKSUM
Fault type
Fault code
Fault description
When the drive enters a fault or
inhibit scenario, the fault information
will be shown and scrolled across the
LCD display.
FLT Sxx Fault Codes
Exception Code on Display Exception Text Problem Possible Solutions
FLT S03 – MTR OVERSPEED FL Motor Overspeed Factory Limit Fault Motor speed has exceeded 590 Hz. Check control loop tuning.
FLT S04 – MTR OVERSPEED UL Motor Overspeed User Limit Fault
Motor speed has exceeded the user-
defined speed limit that is given by Motor
Overspeed User Limit.
Check control loop tuning.
FLT S07 – MTR OVERLOAD FL
Motor Thermal Overload Factory Limit
Fault
The motor thermal model has exceeded its
factory set thermal capacity limit of 110%.
Modify the command profile to reduce
speed or increase time.
FLT S08 – MTR OVERLOAD UL Motor Thermal Overload User Limit Fault
The motor thermal model has exceeded
the thermal capacity limit that is given by
Motor Thermal Overload User Limit.
Modify the command profile.
Increase the Motor Thermal Overload UL
attribute value.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 117
Chapter 7 Troubleshooting
FLT S10 – INV OVERCURRENT Inverter Overcurrent Fault
Inverter current has exceeded the
instantaneous current limit (determined by
hardware).
Check motor power cable for shorts.
Verify that motor windings are not
shorted.
Verify motor power wire gauge.
Operate within the continuous power
rating.
Reduce acceleration times.
FLT S11 – INV OVERTEMP FL
Inverter Overtemperature Factory Limit
Fault
The measured inverter temperature has
exceeded the factory set temperature
limit.
Modify the command profile to reduce
speed or increase time.
Reduce drive ambient temperature.
Verify that airflow through drive is not
obstructed.
FLT S13 – INV OVERLOAD FL
Inverter Thermal Overload Factory Limit
Fault
The thermal model for the power
transistors indicates that the temperature
has exceeded the factory set thermal
capacity rating of 110%.
Modify the command profile to reduce
speed or increase time.
FLT S16 – GROUND CURRENT Ground Current Factory Limit Fault
The sensing circuitry in the power stage
has detected excessive ground current.
Check motor power wiring; check power
cable for shorts.
Replace motor if the fault persists.
FLT S23 – AC PHASE LOSS AC Single Phase Loss Fault
A single AC input phase was lost while the
drive was enabled.
Check AC input voltage on all phases.
FLT S25 – PRECHARGE FAILURE Pre-charge Failure Fault
The pre-charge circuit monitoring
algorithm detected that the DC bus did not
reach a factory set voltage level after
charging for a period of time.
Check AC input voltage on all phases.
Check input power wiring.
Replace drive if fault persists.
FLT S29 – BUS OVERLOAD FL
Bus Regulator Thermal Overload Factory
Limit Fault
The shunt thermal model has exceeded its
factory set thermal capacity limit.
Modify the duty cycle of the application.
Add external shunt for additional
capacity.
Add capacitor module if needed.
FLT S34 – BUS UNDERVOLT UL Bus Undervoltage User Limit Fault
DC Bus voltage level is below the user set
limit as given by Bus Undervoltage User
Limit.
Verify voltage level of the incoming AC.
Monitor AC power source for glitches or
line droop.
Install UPS on AC input.
Decrease Bus Undervoltage UL attribute
value.
FLT S35 – BUS OVERVOLT FL Bus Overvoltage Factory Limit Fault
DC Bus voltage level is above the factory
set limit as determined by the configured
input voltage.
Change the deceleration or motion
profile of all drives that are connected to
the DC bus.
Unplug the shunt connector and
measure the resistance of the shunt.
Replace drive if shunt resistor is open.
FLT S37 – BUS POWER LOSS Bus Power Loss
DC Bus voltage level is below the Bus
Power Loss Threshold for more than the
timeout period specified Bus Power Loss
Time value.
Verify voltage level of the incoming AC.
Monitor AC power source for glitches or
line droop.
Install UPS on AC input.
FLT S41 – FDBK SIGNAL NOISE FL Feedback Signal Noise Fault
Noise induced A/B channel state changes
(illegal states) from a feedback device
were detected by the drive. Specifically,
the number of these noise events that
have occurred on this channel has
exceeded the Feedback Noise Factory
Limit. The offending feedback channel
number is encoded in the associated
Fault/Alarm Sub Code.
Check motor feedback cable and
connector.
Cycle power.
Check feedback shield connection.
Reduce shock and vibration to motor.
Replace motor if fault continues.
Verify all HTL/TTL DIP switches on the
25-ENC-2/B encoder are set in the same
position.
FLT S43 – FDBK SIG FL
Feedback Signal Loss Factory Limit
Fault
The absolute value of the differential A/B
signals is below a factory limit.
Check motor feedback cable and
connector.
Check that motor power cable and
feedback wire shields are secured
correctly.
Check that motor frame is grounded
correctly.
FLT S50 – HARDWARE OVERTRAVEL
POSITIVE
Hardware Overtravel Positive
Axis moved beyond the physical travel
limits in the positive direction and
activated the Positive Overtravel limit
switch.
•Check wiring.
Verify motion profile.
Verify axis configuration in software.
FLT Sxx Fault Codes (Continued)
Exception Code on Display Exception Text Problem Possible Solutions
118 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 7 Troubleshooting
FLT S51 – HARDWARE OVERTRAVEL
NEGATIVE
Hardware Overtravel Negative
Axis moved beyond the physical travel
limits in the negative direction and
activated the Negative Overtravel limit
switch.
•Check wiring.
Verify motion profile.
Verify axis configuration in software.
FLT S54 – POSN ERROR Excessive Position Error Fault
The position error of the position control
loop has exceeded the value that is given
by Position Error Tolerance for a time
period that is given by Position Error
Tolerance Time.
Check position loop tuning.
Increase the feedforward gain.
Verify sizing of the drive and motor.
Check motor power wiring.
Increase Position Error Tolerance and/
or Position Error Tolerance Time
attribute values.
FLT S55 – VEL ERROR Excessive Velocity Error Fault
The velocity error of the velocity control
loop has exceeded the value that is given
by Velocity Error Tolerance for a time
period that is given by Velocity Error
Tolerance Time.
Check velocity loop tuning.
Reduce acceleration.
Verify sizing of the drive and motor.
Check motor power wiring.
Increase Velocity Error Tolerance and/or
Velocity Error Tolerance Time attribute
values.
FLT S56 – OVERTORQUE LIMIT Overtorque Limit Fault
Motor torque has risen above user-defined
maximum torque level that is given by
Overtorque Limit for a time period that is
given by Overtorque Limit Time.
Verify Torque Trim value.
Verify motion profile.
Verify sizing of the drive and motor.
Increase Overtorque Limit and/or
Overtorque Limit Time attribute values.
FLT S57 – UNDERTORQUE LIMIT Undertorque Limit Fault
Motor torque has dropped below user-
defined minimum torque level that is given
by Undertorque Limit for a time period that
is given by Undertorque Limit Time.
Verify motion profile.
Verify sizing of the drive and motor.
Decrease Undertorque Limit and/or
Undertorque Limit Time attribute values.
FLT S61 – ENABLE INPUT DEACTIVATED Enable Input Deactivated
Enable Input has been deactivated while
the axis power structure is in Running
state, enabled, and supplying current to
the DC Bus or motor.
Verify Enable Input level.
Check Enable Input wiring.
FLT Sxx Fault Codes (Continued)
Exception Code on Display Exception Text Problem Possible Solutions
FLT Mxx Fault Codes
Exception Code on Display Exception Text Problem Possible Solutions
FLT M10 – CONTROL MODULE
OVERTEMPERATURE FL
Control Module Overtemperature Fault
The temperature sensor on the Main
Control Board detected excessive heat.
Reduce drive ambient temperature.
Verify that airflow through drive is not
obstructed.
Check control module internal fan.
Replace if error persists.
FLT M19 – DECEL OVERRIDE Decel Override
The drive is not following a commanded
deceleration because it is attempting to
limit bus voltage.
Reprogram Bus Regulator Action to
eliminate any “Adjustable Freq”
selection.
Reprogram Bus Regulator Action to
Shunt Regulator and add external shunt.
•Correct AC input line instability or add an
isolation transformer.
Reset drive.
FLT M21 – MOTOR TEST FAILURE Motor Test Failure The Motor Test procedure has failed.
Verify sizing of the drive and motor.
Verify motor data.
Check motor power wiring.
FLT M26 – RUNTIME ERROR Runtime Error
The drive firmware encountered an
unrecoverable runtime error.
•Cycle power.
Reset the drive.
Return drive for repair if fault continues.
FLT M28 – SAFETY MODULE COM ERROR Safety Module Communication Error
Error in communicating to the Safety
module.
•Cycle power.
Replace module.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 119
Chapter 7 Troubleshooting
INIT FLT Fault Codes
Exception Code on Display Exception Text Problem Possible Solutions
INIT FLT S03 – NVMEM CHKSUM Nonvolatile Memory Checksum Error
Data in the nonvolatile memory has a
checksum error.
•Cycle power.
Reset the drive.
Return drive for repair if fault continues.
INIT FLT M14 – INVALID SAFETY
FIRMWARE
Invalid Safety Firmware
The safety firmware is not compatible with
the drive firmware, or the main safety
firmware is missing.
•Cycle power.
Upgrade drive firmware.
Return drive for repair if fault continues.
INIT FLT M15 – POWER BOARD Power Board Checksum Error The power board has a checksum error.
•Cycle power.
Reset the drive.
Return drive for repair if fault continues.
INIT FLT M22 – ILLEGAL ADDRESS Illegal IP Address Configuration
Invalid Ethernet IP Address configuration
or device Node Address is out of range
(>254)
For example, this fault will occur when the
IP address and Gateway address are
identical.
When this fault occurs, IP address
configuration will be changed to DHCP.
Change IP address, subnet mask, and
gateway address to a legal configuration
and cycle power.
INHIBIT Fault Codes
Exception Code on Display Exception Text Problem Possible Solutions
INHIBIT S01 – AXIS ENABLE INPUT Axis Enable Input Axis Enable Input is not active.
Verify Enable Input level.
Check Enable Input wiring.
INHIBIT S02 – MOTOR NOT CONFIGURED Motor Not Configured
The motor has not been properly
configured for use.
Verify motor configuration in the Studio
5000 Logix Designer application.
INHIBIT S05 – SAFE TORQUE OFF
(1)
Start Inhibit – Safe Torque Off
The safety function has disabled the power
structure.
Check that Ethernet components such
as cables are secured and switches are
operational.
Check state of safety devices.
INHIBIT M05 – SAFE TORQUE OFF
(2)
Start Inhibit – Safe Torque Off
The safety function has disabled the power
structure.
Check safety input wiring.
Check state of safety devices.
(1) Network STO.
(2) Hardwired STO.
NODE FLT Fault Codes
Exception Code on Display Exception Text Problem Possible Solutions
NODE FLT 01 – LATE CTRL UPDATE Control Connection Update Fault
Several consecutive updates from the
controller have been lost.
Remove unnecessary network devices
from the motion network.
Change network topology so that fewer
devices share common paths.
Use high-performance network
equipment.
Use shielded cables.
Separate signal wiring from power
wiring.
NODE FLT 02 – PROC WATCHDOG nn Processor Watchdog Fault
The processor on the power board or
control board failed to update in a certain
amount of time.
The nn sub-codes 00…05 are internal and
result in the same possible solution.
•Cycle power.
Update the drive firmware.
Return drive for repair if fault continues.
NODE FLT 03 – HARDWARE 00 Hardware Fault - PwrIF
Communication with the power board
could not be established.
•Cycle power.
Update the drive firmware.
Return drive for repair if fault continues.
NODE FLT 03 – HARDWARE 01 Hardware Fault - Piccolo HW DSP chip on the power board failure.
•Cycle power.
Return motor for repair if fault
continues.
NODE FLT 05 – CLOCK SKEW FLT Clock Skew Fault
The controller time and the drive system
time are not the same.
•Cycle power.
Check controller and Ethernet switch
operation.
120 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 7 Troubleshooting
PowerFlex 527 Drive Status Indicators
The fault status indicator is located between the LCD display and keypad.
There are also four status indicators that are located at the bottom right of the
drive and can be seen through the front cover of the control module.
NODE FLT 06 – LOST CTRL CONN Lost Controller Connection Fault
Communication with the controller has
been lost.
Check Ethernet connection.
Check controller and Ethernet switch
operation.
NODE FLT 07 – CLOCK SYNC Clock Sync Fault
Drive local clock has lost synchronization
with controller's clock and was not able to
resynchronize within allotted time.
Check Ethernet connection.
Check controller and Ethernet switch
operation.
NODE FLT 09 – DUPLICATE IP ADDRESS Duplicate IP Address Fault
Several consecutive updates from the
controller have been lost.
Select an IP address not already in use on
the network.
NODE FLT Fault Codes (Continued)
Exception Code on Display Exception Text Problem Possible Solutions
NODE ALARM Fault Codes
Exception Code on Display Exception Text Problem Possible Solutions
NODE ALARM 01 – LATE CTRL UPDATE Control Connection Update Alarm
Updates from the controller have been
late.
Remove unnecessary network devices
from the motion network.
Change network topology so that fewer
devices share common paths.
Use high-performance network
equipment.
Use shielded cables.
Separate signal wiring from power
wiring.
NODE ALARM 03 – CLOCK JITTER Clock Jitter Alarm
The sync variance has exceeded the sync
threshold while the device is running in
sync mode.
Check the Ethernet connection.
Check controller and Ethernet switch
operation.
NODE ALARM 04 – CLOCK SKEW ALARM Clock Skew Alarm
The controller time and the drive system
time are not the same.
Check the Ethernet connection.
Check controller and Ethernet switch
operation.
NODE ALARM 05 – CLOCK SYNC ALARM Clock Sync Alarm
Drive local clock has lost synchronization
with controller's clock for a short time
during synchronous operation.
Check the Ethernet connection.
Check controller and Ethernet switch
operation.
Module status
Network status
Link A status (Ethernet port 1)
Link B status (Ethernet port 2)
Fault status
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 121
Chapter 7 Troubleshooting
Fault Status Indicator
Condition Safety Supervisor State CIP Motion Axis State Governing Object Identity State
Steady Red
Any State
(1)
Aborting Motion Axis
Major Recoverable or
Major Unrecoverable
Steady Red
Any State
(1)
Major Faulted Motion Axis
Major Recoverable or
Major Unrecoverable
Steady Red Abort
Any State
(1)
Safety Supervisor Major Recoverable
Steady Red Critical Fault
Any State
(1)
Safety Supervisor Major Unrecoverable
(1) “Any State” means any state that has lower precedence.
Module Status Indicator
Condition Safety Supervisor State CIP Motion Axis State Governing Object Identity State
Flashing Green/Red Self-Testing
Any State
(1)
Safety Supervisor Device Self-Testing
Flashing Green/Red
Any State
(1)
Self-Testing Motion Axis Device Self-Testing
Steady Red Self-Test Exception
Any State
(1)
Safety Supervisor Major Unrecoverable
Flashing Green/Red
Waiting for TUNID
(2)
Any State
(1)
Safety Supervisor Standby
Flashing Green/Red Configuring
Any State
(1)
Safety Supervisor Standby
Flashing Green Idle
Any State
(1)
Safety Supervisor Standby
Flashing Green
Waiting for TUNID with Torque
Permitted
(2)(3)
•Executing
Executing with Torque
Permitted
(4)
Initializing
Pre-Charge
•Shutdown
•Start Inhibit
Motion Axis Standby
Steady Green
Stopped
Stopping
•Starting
Running
•Testing
Motion Axis Operational
Flashing Red or Steady Red
Any State
(1)
Aborting Motion Axis
Major Recoverable or
Major Unrecoverable
Flashing Red
Any State
(1)
Major Faulted Motion Axis
Major Recoverable or
Major Unrecoverable
Flashing Red Abort
Any State
(1)
Safety Supervisor Major Recoverable
Steady Red Critical Fault
Any State
(1)
Safety Supervisor Major Unrecoverable
(1) “Any State” means any state that has lower precedence.
(2) After Propose_TUNID service request, the Network Status indicator flashes Green/Red (fast flash) until successful Apply_TUNID.
(3) Unlike many safety I/O devices, a CIP Motion safety drive is free to operate in its “Out-of-Box state. This behavior is made explicit by the device specific Safety Supervisor state, Waiting for
TUNID with Torque Permitted. In this “Out-of-Box” state, operation of the CIP Motion safety drive is the same as that of a CIP Motion drive to facilitate commissioning.
(4) Unlike many safety I/O devices, a CIP Motion safety drive may be operated when the safety output assemblies Run/Idle bit is set to Idle. If in the Executing state, the Run/Idle bit is set to Idle,
the device is forced to a Safe State. However, if in this condition, the safety controller sends a Mode_Change service request with Torque Permitted to the Safety Stop Functions object, drive
operation is permitted while the Run/Idle bit remains Idle. See the Safety Stop Function object for details on the Mode_Change service.
Network Status Indicator
Condition Status
Off No power applied to the drive or IP address is not configured.
Flashing Green Drive connection is not established, but has obtained an IP address.
Steady Green Drive is online and has connections in the established state.
Flashing Red One or more Exclusive Owner connections has timed out.
Steady Red Duplicate IP address. IP address that is specified is already in use.
Flashing Green/Red (slow flash) The drive performs self-test during powerup.
Flashing Green/Red (fast flash) Safety Supervisor is waiting for “Apply TUNID” service request.
122 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 7 Troubleshooting
General Troubleshooting These conditions do not always result in a fault code, but can require
troubleshooting to improve performance.
Link A Status Indicator (Ethernet Port 1)
Condition Status
Off Drive is not connected to the network.
Steady Green Drive is connected to the network but not transmitting data.
Flashing Green Drive is connected to the network and transmitting data.
Link A Status Indicator (Ethernet Port 2)
Condition Status
Off Drive is not connected to the network.
Steady Green Drive is connected to the network but not transmitting data.
Flashing Green Drive is connected to the network and transmitting data.
General Troubleshooting
Condition Potential Cause Possible Resolution
Axis or system is unstable.
The position feedback device is incorrect or open. Check wiring.
Motor tuning limits are set too high. Run Tune in the Logix Designer application.
Position loop gain or position controller accel/decel rate is improperly
set.
Run Tune in the Logix Designer application.
Improper grounding or shielding techniques are causing noise to be
transmitted into the position feedback or velocity command lines,
causing erratic axis movement.
Check wiring and ground.
Motor Data is incorrectly set (induction motor is not matched to axis
module).
Check setups.
Run Motor Test in the Logix Designer application.
Mechanical resonance.
Notch filter or output filter can be required (refer to Axis
Properties dialog box, Output tab in the Logix Designer
application).
You cannot obtain the motor
acceleration/deceleration that you
want.
Torque Limit limits are set too low. Verify that torque limits are set properly.
Incorrect motor selected in configuration.
Select the correct motor and run Tune in the Logix Designer
application again.
The system inertia is excessive.
Check motor size versus application need.
Review induction system sizing.
The system friction torque is excessive. Check motor size versus application need.
Available current is insufficient to supply the correct accel/decel rate.
Check motor size versus application need.
Review induction system sizing.
Acceleration limit is incorrect. Verify limit settings and correct them, as necessary.
Velocity Limit limits are incorrect. Verify limit settings and correct them, as necessary.
Motor does not respond to a
command.
The motor wiring is open. Check the wiring.
The motor cable shield connection is improper.
Check feedback connections.
Check cable shield connections.
The motor has malfunctioned. Repair or replace the motor.
The coupling between motor and machine has broken (for example, the
motor moves, but the load/machine does not).
Check and correct the mechanics.
Primary operation mode is set incorrectly. Check and properly set the limit.
Velocity or torque limits are set incorrectly. Check and properly set the limits.
Brake connector not wired Check brake wiring.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 123
Chapter 7 Troubleshooting
Logix 5000 Controller and
Drive Behavior
By using the Logix Designer application, you can configure how the
PowerFlex 527 drives respond when a drive fault/exception occurs.
The drive supports fault action for Ignore, Alarm, Minor Fault, and Major Fault
as defined in Table 13
. See the drive behavior tables beginning on page 125 for
information on how the fault and stopping actions apply to each of the
exception fault codes.
The drive supports these configurable stopping actions
(1)
:
Disable and Coast
Current Decel and Disable
Ramped Decel and Disable
(1) Disable and Coast and Current Decel and Disable are available in Frequency Control, Velocity Loop and Position Loop.
Ramped Decel and Disable is available in Frequency Control and Velocity Loop only and is not supported in Position Loop.
Presence of noise on command or
motor feedback signal wires.
Recommended grounding per installation instructions have not been
followed.
Verify grounding.
Route wire away from noise sources.
See the System Design for Control of Electrical Noise
Reference Manual, publication GMC-RM001
.
Line frequency can be present.
Verify grounding.
Route wire away from noise sources.
Variable frequency can be velocity feedback ripple or a disturbance that
is caused by gear teeth or ballscrew, and so forth. The frequency can be
a multiple of the motor power transmission components or ballscrew
speeds resulting in velocity disturbance.
Decouple the motor for verification.
Check and improve mechanical performance, for
example, the gearbox or ballscrew mechanism.
No rotation
The motor connections are loose or open. Check motor wiring and connections.
Foreign matter is lodged in the motor. Remove foreign matter.
The motor load is excessive. Verify the induction system sizing.
The bearings are worn. Return the motor for repair.
The motor brake is engaged (if supplied).
Check brake wiring and function.
Return the motor for repair.
The motor is not connected to the load. Check coupling.
Motor overheating
The duty cycle is excessive.
Change the command profile to reduce accel/decel or
increase time.
The rotor is partially demagnetized causing excessive motor current. Return the motor for repair.
Abnormal noise
Motor tuning limits are set too high. Run Tune in the Logix Designer application.
Loose parts are present in the motor.
Remove the loose parts.
Return motor for repair.
Replace motor.
Through bolts or coupling is loose. Tighten bolts.
The bearings are worn. Return motor for repair.
Mechanical resonance.
Notch filter can be required (See the Axis Properties dialog
box, Output tab in the Logix Designer application).
Erratic operation - Motor locks into
position, runs without control or
with reduced torque.
Motor power phases U and V, U and W, or V and W reversed. Check and correct motor power wiring.
General Troubleshooting (Continued)
Condition Potential Cause Possible Resolution
The INIT FLT xxx faults are always generated after powerup, but before
the drive is enabled, so the stopping behavior does not apply.
NODE ALARM xxx faults do not apply because they do not trigger stopping
behavior.
124 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 7 Troubleshooting
PowerFlex 527 Drive Exception Behavior
For PowerFlex 527 drives, you can configure exception behavior in the
Logix Designer application from the Axis Properties dialog box, Actions
category.
Only selected drive exceptions are configurable. In the fault behavior tables,
the controlling attribute is given for programmable fault actions.
Logix Designer Axis Properties - Actions Category
Table 13 - PowerFlex 527 Drive Exception Action Definitions
Exception Action Definition
Ignore
The controller completely ignores the exception condition. For some exceptions
that are fundamental to the operation of the planner, Ignore is not an available
option.
Alarm
The controller sets the associated bit in the Motion Alarm Status word, but does not
otherwise affect axis behavior. Like Ignore, if the exception is so fundamental to
the drive, Alarm is not an available option. When an exception action is set to
Alarm, the Alarm goes away by itself when the exceptional condition has cleared.
Fault Status Only – Minor Fault
Like Alarm, Fault Status Only instructs the controller to set the associated bit in the
Motion Fault Status word, but does not otherwise affect axis behavior. However,
unlike Alarm an explicit Fault Reset is required to clear the fault once the
exceptional condition has cleared.
Like Ignore and Alarm, if the exception is so fundamental to the drive, Fault Status
Only is not an available option.
Stop Planner – Minor Fault
The controller sets the associated bit in the Motion Fault Status word and instructs
the Motion Planner to perform a controlled stop of all planned motion at the
configured maximum deceleration rate and holds at zero speed. An explicit Fault
Reset is required to clear the fault once the exceptional condition has cleared. If
the exception is so fundamental to the drive, Stop Planner is not an available
option.
Stop Drive – Major Fault
When the exception occurs, the associated bit in the Fault Status word is set and
the axis comes to a stop by using the stopping action that is defined by the drive
for the particular exception that occurred. There is no controller based
configuration to specify what the stopping action is, the stopping action is device
dependent.
Shutdown – Major Fault
When the exception occurs, the drive brings the motor to a stop by using the
stopping action defined by the drive (as in Stop Drive) and the power module is
disabled. An explicit Shutdown Reset is required to restore the drive to operation.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 125
Chapter 7 Troubleshooting
Drive Behavior, FLT Sxx Fault Codes
Exception Fault Code Exception Text
Induction
Motor
Fault Action
Best Available Stopping
Action (applies to major
faults)
Ignore Alarm
Minor
Fault
Major
Fault
FLT S03 – MTR OVERSPEED FL Motor Overspeed Factory Limit Fault X X Disable and Coast
FLT S04 – MTR OVERSPEED UL Motor Overspeed User Limit Fault X XXXXDisable and Coast
FLT S07 – MTR OVERLOAD FL Motor Thermal Overload Factory Limit Fault X X Disable and Coast
FLT S08 – MTR OVERLOAD UL Motor Thermal OverLoad User Limit Fault X XXXXDisable and Coast
FLT S10 – INV OVERCURRENT Inverter Overcurrent Fault X X Disable and Coast
FLT S11 – INV OVERTEMP FL Inverter Overtemperature Factory Limit Fault X X Disable and Coast
FLT S13 – INV OVERLOAD FL Inverter Thermal Overload Factory Limit Fault X X Disable and Coast
FLT S16 – GROUND CURRENT Ground Current Factory Limit Fault X X Disable and Coast
FLT S23 AC PHASE LOSS AC Single Phase Loss Fault X XXXXDisable and Coast
FLT S25 – PRECHARGE FAILURE Pre-charge Failure Fault X X Disable and Coast
FLT S29 – BUS OVERLOAD FL
Bus Regulator Thermal OverLoad Factory Limit
Fault
XXDisable and Coast
FLT S34 – BUS UNDERVOLT UL Bus Undervoltage User Limit Fault X XXXXDisable and Coast
FLT S35 – BUS OVERVOLT FL Bus Overvoltage Factory Limit Fault X X Disable and Coast
FLT S37 – BUS POWER LOSS Bus Power Loss X XXXXDisable and Coast
FLT S41 FDBK SIGNAL NOISE FLFeedback Signal Noise Fault X XXXXDisable and Coast
FLT S43 FDBK SIG FL Feedback Signal Loss Factory Limit Fault X XXXXDisable and Coast
FLT S50 – HARDWARE OVERTRAVEL
POSITIVE
Hardware Overtravel Positive X XXXXCurrent Decel and Disable
FLT S51 – HARDWARE OVERTRAVEL
NEGATIVE
Hardware Overtravel Negative X XXXXCurrent Decel and Disable
FLT S54 POSN ERROR Excessive Position Error Fault X XXXXDisable and Coast
FLT S55 VEL ERROR Excessive Velocity Error Fault X XXXXDisable and Coast
FLT S56 OVERTORQUE LIMITOvertorque Limit Fault X XXXXDisable and Coast
FLT S57 – UNDERTORQUE LIMIT Undertorque Limit Fault X XXXXDisable and Coast
FLT S61 – ENABLE INPUT
DEACTIVATED
Enable Input Deactivated X XXXXDisable and Coast
Drive Behavior, FLT Mxx Fault Codes
Exception Fault Code Exception Text
Induction
Motor
Fault Action
Best Available Stopping
Action (applies to major
faults)
Ignore Alarm
Minor
Fault
Major
Fault
FLT M10 – CONTROL MODULE
OVERTEMPERATURE FL
Control Module Overtemperature Fault X X Disable and Coast
FLT M19 DECEL OVERRIDE Decel Override X XXXXDisable and Coast
FLT M21 – MOTOR TEST FAILURE Motor Test Failure X X Disable and Coast
FLT M26 – RUNTIME ERROR Runtime Error X X Disable and Coast
FLT M28 – SAFETY COMM Safety Module Communication Error X X Disable and Coast
Drive Behavior, NODE FLT xx Fault Codes
Exception Fault Code Exception Text
Induction
Motor
Fault Action
Best Available Stopping
Action (applies to major
faults)
Ignore Alarm
Minor
Fault
Major
Fault
NODE FLT 01 –
LATE CTRL UPDATE
Control Connection Update Fault X X Current Decel and Disable
NODE FLT 02 – PROC WATCHDOG Processor Watchdog Fault X X Disable and Coast
NODE FLT 03 – HARDWARE Hardware Fault X X Disable and Coast
NODE FLT 05 – CLOCK SKEW FLT Clock Skew Fault X X Disable and Coast
126 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Chapter 7 Troubleshooting
NODE FLT 06 – LOST CTRL CONN Lost Controller Connection Fault X X Current Decel and Disable
NODE FLT 07 – CLOCK SYNC Clock Sync Fault X X Disable and Coast
NODE FLT 09 –
DUPLICATE IP ADDRESS
Duplicate IP Address Fault X X Disable and Coast
Drive Behavior, NODE FLT xx Fault Codes (Continued)
Exception Fault Code Exception Text
Induction
Motor
Fault Action
Best Available Stopping
Action (applies to major
faults)
Ignore Alarm
Minor
Fault
Major
Fault
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 127
Appendix A
Supplemental Drive Information
Certifications
Topic Page
Certifications 127
Environmental Specifications 128
Technical Specifications 129
Power Specifications 132
Certifications
Certifications PowerFlex 527
c-UL-us
Listed to UL61800 and CAN/CSA-C22.2 No. 14-05.
RCM Australian Communications and Media Authority
In conformity with the following:
Radiocommunications Act: 1992 (including amendments up to 2018)
Radiocommunications (Electromagnetic Compatibility) Standard: 2017
Radiocommunications Labeling (Electromagnetic Compatibility) Notice: 2017
Standards applied:
EN 61800-3
CE In conformity with the following European Directives:
2014/35/EU Low Voltage Directive (LVD)
2014/30/EU EMC Directive (EMC)
2014/34/EU ATEX Directive (ATEX)
2006/42/EC Machinery Directive (MD)
2011/65/EU RoHS Directive (RoHS)
Standards applied:
EN 61800-5-1
EN 61800-3
EN 50495
UKCA In conformity with the following UK Regulations:
2016 No. 1101 Electrical Equipment (Safety) Regulations (LV)
2016 No. 1091 Electromagnetic Compatibility Regulations (EMC)
2016 No. 1107 Equipment and Protective Systems Intended for Use in Potentially
Explosive Atmospheres Regulations (Ex)
2008 No. 1597 Supply of Machinery (Safety) Regulations (MD)
2012 No. 3032 Restriction of the Use of Certain Hazardous Substances in Electrical
and Electronic Equipment Regulations (RoHS)
2021 No. 745 Ecodesign for Energy-Related Products and Energy Information
Regulations (Eco)
Standards applied:
EN 61800-5-1
EN 61800-3
EN 50495
128 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix A Supplemental Drive Information
Environmental
Specifications
Functional Safety TÜV Rheinland
Standards applied:
EN ISO 13849-1
EN 61800-5-2
EN 62061
EN 60204-1
IEC 61508 Part 1-7
Certified to ISO 13849-1 SIL3/PLe with embedded Safe Torque-Off function
Certified to ISO 61800-5-2 and EN 62061 SIL3/PLe with Network Torque-Off function
Meets Functional Safety (FS) when used with embedded Safe Torque-Off function
ATEX
TÜV 15 ATEX 7696 X
TUV 21 UKEX 7033 X
Certified to ATEX Directive 2014/34/EU
Group II Category (2) GD Applications with ATEX Approved Motors
Certified to UK Equipment and Protective Systems Intended for Use in Potentially
Explosive Atmospheres Regulations (2016 No. 1107)
Group II Category (2) GD Applications with ATEX Approved Motors
KCC Korean Registration of Broadcasting and Communications Equipment
Compliant with the following standards:
Article 58-2 of Radio Waves Act, Clause 3
EAC
Customs Union:
Low Voltage TR CU 004/2011
EMC TR CU 020/2011
AC 156 Tested by Trentec to be compliant with AC156 Acceptance Criteria for Seismic
Qualification Testing of Nonstructural Components and 2003 International Building
Code for worst-case seismic level for USA excluding site class F
SEMI F47 Electric Power Research Institute
Certified compliant with the following standards:
SEMI F47
IEC 61000-4-34
ODVA
ODVA conformance tested to EtherNet/IP specifications
Lloyd’s Register Lloyd’s Register Type Approval Certificate 15/80016(E1)
IEEE P1668 Product meets the requirements of IEEE P1668
RoHS Compliant with the European “Restriction of Hazardous Substances” Directive
The drive is also designed to meet the appropriate portions of the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 7.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable
Speed Drive Systems.
Certifications (Continued)
Certifications PowerFlex 527
Functional
Safety
Typ e
Approved
www.tuv.com
ID 0600000000
II (2) G D
Environmental Specifications
Specifications PowerFlex 527
Altitude
Without derating
With derating
See Current Derating Curves
on page 15 for derating guidelines.
1000 m (3300 ft) max.
Up to 4000 m (13,200 ft) max., with the exception of 600V drives @ 2000 m (6600 ft)
max.
Max. Surrounding Air
Temperature
Without derating
With derating
See Current Derating Curves
on page 15 for derating guidelines.
-20…+50 °C (-4…+22 °F)
-20…+60 °C (-4…+140 °F) or -20…+70 °C (-4…+158 °F) with optional Control Module
Fan kit
Storage Temperature
Frame AD
Frame E
-40…+85 °C (-40…+185 °F)
-40…+70 °C (-40…+158 °F)
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 129
Appendix A Supplemental Drive Information
Technical Specifications
Atmosphere
Relative Humidity 0…95% noncondensing
Shock Complies with IEC 60068-2-27
Vibration Complies with IEC 60068-2-6:2007
Conformal Coating
Complies with:
IEC 60721-3-3 to level 3C2 (chemical and gases only)
Surrounding Environment
Pollution Degree
Pollution Degree 1 & 2
See Pollution Degree Ratings According to EN 61800-5-1
on page 37
for descriptions.
All enclosures acceptable.
Sound Pressure Level
(A-weighted)
Frame A & B
Frame C
Frame D
Frame E
Measurements are taken 1 m from the drive.
Maximum 53 dBA
Maximum 57 dBA
Maximum 64 dBA
Maximum 68 dBA
Environmental Specifications (Continued)
Specifications PowerFlex 527
IMPORTANT Drive must not be installed in an area where
the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the drive is not
going to be installed for a period of time, it
must be stored in an area where it will not be
exposed to a corrosive atmosphere.
Frame
Size
Operating and Nonoperating Nonoperating (Transportation)
Force
(Shock/Vibration) Mounting Type
Force
(Shock/Vibration) Mounting Type
A 15 g / 2 g DIN rail or screw 30 g/ 2.5 g Screw only
B 15 g / 2 g DIN rail or screw 30 g/ 2.5 g Screw only
C 15 g / 2 g DIN rail or screw 30 g/ 2.5 g Screw only
D 15 g / 2 g Screw only 30 g/ 2.5 g Screw only
E 15 g / 1.5 g Screw only 30 g/ 2.5 g Screw only
Protection
Specifications PowerFlex 527
Bus Overvoltage Trip
100…120V AC Input
200…240V AC Input
380…480V AC Input
525…600V AC Input
405V DC bus (equivalent to 150V AC incoming line)
405V DC bus (equivalent to 290V AC incoming line)
810V DC bus (equivalent to 575V AC incoming line)
1005V DC bus (equivalent to 711V AC incoming line)
Bus Undervoltage Trip
100…120V AC Input
200…240V AC Input
380…480V AC Input
525…600V AC Input
190V DC bus (equivalent to 75V AC incoming line)
190V DC bus (equivalent to 150V AC incoming line)
390V DC bus (equivalent to 275V AC incoming line)
487V DC bus (equivalent to 344V AC incoming line)
Power Ride-Thru 100 ms
Logic Control Ride-Thru 0.5 s minimum, 2 s typical
Electronic Motor Overload
Protection
Provides class 10 motor overload protection according to NEC article 430 and
motor over-temperature protection according to NEC article 430.126 (A) (2).
UL 508C File 29572.
Overcurrent 200% hardware limit, 300% instantaneous fault
Ground Fault Trip Phase-to-ground on drive output
Short Circuit Trip Phase-to-phase on drive output
130 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix A Supplemental Drive Information
Electrical
Specifications PowerFlex 527
Voltage Tolerance -15% / +10%
Frequency Tolerance 47…63 Hz
Input Phases
3-Phase input provides full rating. 1-Phase input provides 35% rating on 3-phase
drives.
Displacement Power Factor 0.98 across entire speed range
Maximum Short Circuit Rating 100,000 Amps Symmetrical
Actual Short Circuit Rating Determined by AIC Rating of installed fuse/circuit breaker
Transistor Type Isolated Gate Bipolar Transistor (IGBT)
Internal DC Bus Choke
200…240V AC Input
380…480V AC Input
525…600V AC Input
Only for Frame E drive ratings
11 kW (15 HP)
15…18.5 kW (20…25 HP) – Heavy Duty
15…18.5 kW (20…25 HP) – Heavy Duty
Control
Specifications PowerFlex 527
Method
Frequency Control:
Basic Volts/Hertz
Fan/Pump Volts/Hertz
Sensorless Vector Control (SVC)
Sensorless Vector Control (SVC) Economizer
Position Loop:
Closed Loop Position Vector Control (with optional encoder card)
Velocity Loop:
Closed Loop Velocity Vector Control (with optional encoder card)
Carrier Frequency 2...8 kHz, Drive rating based on 4 kHz
Frequency Accuracy Within ±0.05% of set output frequency
Performance
V/Hz (Volts per Hertz)
SVC (Sensorless Vector)
SVC Economizer
±1% of base speed across a 60:1 speed range
±0.5% of base speed across a 100:1 speed range
±0.5% of base speed across a 100:1 speed range
Performance with Encoder
Closed Loop Velocity Vector
Control ±0.1% of base speed across a 100:1 speed range
Output Voltage Range 0V to rated motor voltage
Output Frequency Range 0…590 Hz (programmable)
Efficiency 97.5% (typical)
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 131
Appendix A Supplemental Drive Information
Stop Modes
Multiple programmable stop modes including – Disable and Coast, Current Decel
and Disable, and Ramped Decel and Disable
Accel/Decel
“REAL” tag programmable with Studio 5000 motion instructions.
For more information, see the Logix 5000 Controllers Motion Instructions
Reference Manual, publication MOTION-RM002
.
Intermittent Overload
Normal Duty
Heavy Duty
110% Overload capability for up to 60 s, 150% for up to 3 s
Applies to following drives:
•25C-B048*
•25C-B062*
25C-D030*
25C-D030*
•25C-D037*
•25C-D043*
25C-E022*
•25C-E027*
•25C-E032*
150% Overload capability for up to 60 s, 180% for up to 3 s
Applies to following drives:
25C-V2P5*
25C-V4P8*
•25C-V6P0*
25C-A2P5*
•25C-A4P8*
•25C-A8P0*
•25C-A011*
25C-B2P5*
25C-B5P0*
•25C-B8P0*
•25C-B011*
•25C-B017*
•25C-B024*
•25C-B032*
•25C-D1P4*
•25C-D2P3*
•25C-D4P0*
•25C-D6P0*
25C-D010*
•25C-D013*
•25C-D017*
•25C-D024*
•25C-E0P9*
•25C-E1P7*
•25C-E3P0*
•25C-E4P2*
•25C-E6P6*
25C-E9P9*
•25C-E012*
•25C-E019*
Control Inputs
Specifications PowerFlex 527
Digital
Quantity (4) Programmable
Current 6 mA
Type
Source Mode (SRC)
Sink Mode (SNK)
18…24V = ON, 0…6V = OFF
0…6V = ON, 18…24V = OFF
Analog
Quantity (2) Isolated, ±10V and 4-20mA
Specification
Resolution
±10V DC Analog
4-20mA Analog
External Pot
10-bit
100k ohm input impedance
250 ohm input impedance
1…10k ohm, 2 W minimum
Control (Continued)
Specifications PowerFlex 527
132 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix A Supplemental Drive Information
Power Specifications Watts Loss
Safety
(per
channel)
Input Current <10 mA
Input ON Voltage, max 18…26.4V DC
Input OFF Voltage, max 5V DC
Input ON Current 10 mA
Input OFF Current 500 µA
Pulse Rejection Width 700 µs
External Power Supply SELV/PELV
Input Type Optically isolated and reverse voltage protected
Control Outputs
Specifications PowerFlex 527
Relay
Quantity (2) 1 Programmable Form A and 1 Programmable Form B
Specification
Resistive Rating
Inductive Rating
3.0 A @ 30V DC, 3.0 A @ 125V, 3.0 A @ 240V AC
0.5 A @ 30V DC, 0.5 A @ 125V, 0.5 A @ 240V AC
Opto
Quantity (2) Programmable
Specification 30V DC, 50 mA Non-inductive
Analog
Quantity
(1) Non-Isolated 0-10V or 0-20 mA
See Analog Output
on page 36 for instructions on setting the jumper.
See Setting the ACO/AVO Attribute on page 162 for instructions on setting the
attribute.
Specification
Resolution
0-10V DC Analog
0-20 mA Analog
10-bit
1 k Ω minimum
525 Ω maximum
Encoder
Specifications PowerFlex 527
Type Incremental, dual channel
Supply 5V, 12V, 250 mA
Quadrature 90°, ±27 ° @ 25 °C
Duty Cycle 50%, +10%
Requirements
Encoders must be line driver type, quadrature (dual channel), 3.5…26V DC output, single-
ended or differential and capable of supplying a minimum of 10 mA per channel.
Allowable input is DC up to a maximum frequency of 250 kHz. The encoder I/O automatically
scales to allow 5V, 12V, and 24V DC nominal voltages.
Control Inputs (Continued)
Specifications PowerFlex 527
PowerFlex 527 Estimated Watts Loss (Rated Load, Speed and PWM)
Voltage Output Current (A) Total Watts Loss
100...120V,
50/60 Hz 1-Phase
2.5 27.0
4.8 53.0
6.0 67.0
200...240V,
50/60 Hz 1-Phase
2.5 29.0
4.8 50.0
8.0 81.0
11.0 111.0
200...240V,
50/60 Hz 1-Phase
w/ EMC Filter
2.5 29.0
4.8 53.0
8.0 84.0
11.0 116.0
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 133
Appendix A Supplemental Drive Information
Input Current Scaling
200...240V,
50/60 Hz 3-Phase
2.5 29.0
5.0 50.0
8.0 79.0
11.0 107.0
17.5 148.0
24.0 259.0
32.2 323.0
48.3 584.0
62.1 708.0
380...480V,
50/60 Hz 3-Phase
1.4 27.0
2.3 37.0
4.0 62.0
6.0 86.0
10.5 129.0
13.0 170.0
17.0 221.0
24.0 303.0
30.0 387.0
380...480V,
50/60 Hz 3-Phase
w/ EMC Filter
1.4 27.0
2.3 37.0
4.0 63.0
6.0 88.0
10.5 133.0
13.0 175.0
17.0 230.0
24.0 313.0
30.0 402.0
37.0 602.0
43.0 697.0
525…600V,
50/60 Hz 3-Phase
0.9 22.0
1.7 32.0
3.0 50.0
4.2 65.0
6.6 95.0
9.9 138.0
12.0 164.0
19.0 290.0
22.0 336.0
27.0 466.0
32.0 562.0
PowerFlex 527 Input Current Scaled By Motor Current
Catalog Number
Output Input
12345678
100120V AC (-15%, +10%) – 1-Phase Input, 0230V 3-Phase Output
25C-V2P5N104 2.5 2.0 1.6 1.3 9.6 7.7 6.2 4.8
25C-V4P8N104 4.8 3.8 3.1 2.4 19.2 15.4 12.5 9.6
25C-V6P0N104 6.0 4.8 3.9 3.0 24.0 19.2 15.6 12.0
PowerFlex 527 Estimated Watts Loss (Rated Load, Speed and PWM) (Continued)
Voltage Output Current (A) Total Watts Loss
134 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix A Supplemental Drive Information
200240V AC (-15%, +10%) – 1-Phase Input, 0230V 3-Phase Output
25C-A2P5N104 2.5 2.0 1.6 1.3 6.5 5.2 4.2 3.3
25C-A4P8N104 4.8 3.8 3.1 2.4 10.7 8.6 7.0 5.4
25C-A8P0N104 8.0 6.4 5.2 4.0 18.0 14.4 11.7 9.0
25C-A011N104 11.0 8.8 7.2 5.5 22.9 18.3 14.9 11.5
200240V AC (-15%, +10%) – 1-Phase Input with EMC Filter, 0230V 3-Phase Output
25C-A2P5N114 2.5 2.0 1.6 1.3 6.5 5.2 4.2 3.3
25C-A4P8N114 4.8 3.8 3.1 2.4 10.7 8.6 7.0 5.4
25C-A8P0N114 8.0 6.4 5.2 4.0 18.0 14.4 11.7 9.0
25C-A011N114 11.0 8.8 7.2 5.5 22.9 18.3 14.9 11.5
200240V AC (-15%, +10%) – 3-Phase Input, 0230V 3-Phase Output
25C-B2P5N104 2.5 2.0 1.6 1.3 2.7 2.2 1.8 1.4
25C-B5P0N104 5.0 4.0 3.2 2.5 5.8 4.6 3.8 2.9
25C-B8P0N104 8.0 6.4 5.2 4.0 9.5 7.6 6.2 4.8
25C-B011N104 11.0 8.8 7.2 5.5 13.8 11.0 9.0 6.9
25C-B017N104 17.5 14.0 11.4 8.8 21.1 16.9 13.7 10.6
25C-B024N104 24.0 19.2 15.6 12.0 26.6 21.3 17.3 13.3
25C-B032N104 32.2 25.8 20.9 16.1 34.8 27.8 22.6 17.4
25C-B048N104 48.3 38.6 31.4 24.2 44.0 35.2 28.6 22.0
25C-B062N104 62.1 49.7 40.4 31.1 56.0 44.8 36.4 28.0
380480V AC (-15%, +10%) – 3-Phase Input, 0460V 3-Phase Output
25C-D1P4N104 1.4 1.1 0.9 0.7 1.9 1.5 1.2 1.0
25C-D2P3N104 2.3 1.8 1.5 1.2 3.2 2.6 2.1 1.6
25C-D4P0N104 4.0 3.2 2.6 2.0 5.7 4.6 3.7 2.9
25C-D6P0N104 6.0 4.8 3.9 3.0 7.5 6.0 4.9 3.8
25C-D010N104 10.5 8.4 6.8 5.3 13.8 11.0 9.0 6.9
25C-D013N104 13.0 10.4 8.5 6.5 15.4 12.3 10.0 7.7
25C-D017N104 17.0 13.6 11.1 8.5 18.4 14.7 12.0 9.2
25C-D024N104 24.0 19.2 15.6 12.0 26.4 21.1 17.2 13.2
25C-D030N104 30.0 24.0 19.5 15.0 33.0 26.4 21.5 16.5
380480V AC (-15%, +10%) – 3-Phase Input with EMC Filter, 0460V 3-Phase Output
25C-D1P4N114 1.4 1.1 0.9 0.7 1.9 1.5 1.2 1.0
25C-D2P3N114 2.3 1.8 1.5 1.2 3.2 2.6 2.1 1.6
25C-D4P0N114 4.0 3.2 2.6 2.0 5.7 4.6 3.7 2.9
25C-D6P0N114 6.0 4.8 3.9 3.0 7.5 6.0 4.9 3.8
25C-D010N114 10.5 8.4 6.8 5.3 13.8 11.0 9.0 6.9
25C-D013N114 13.0 10.4 8.5 6.5 15.4 12.3 10.0 7.7
25C-D017N114 17.0 13.6 11.1 8.5 18.4 14.7 12.0 9.2
25C-D024N114 24.0 19.2 15.6 12.0 26.4 21.1 17.2 3.2
25C-D030N114 30.0 24.0 19.5 15.0 33.0 26.4 21.5 16.5
25C-D037N114 37.0 29.6 24.1 18.5 33.7 27.0 21.9 16.9
25C-D043N114 43.0 34.4 28.0 21.5 38.9 31.1 25.3 19.5
525600V AC (-15%, +10%) – 3-Phase Input, 0575V 3-Phase Output
25C-E0P9N104 0.9 0.7 0.6 0.5 1.2 1.0 0.8 0.6
25C-E1P7N104 1.7 1.4 1.1 0.9 2.3 1.8 1.5 1.2
25C-E3P0N104 3.0 2.4 2.0 1.5 3.8 3.0 2.5 1.9
25C-E4P2N104 4.2 3.4 2.7 2.1 5.3 4.2 3.4 2.7
25C-E6P6N104 6.6 5.3 4.3 3.3 8.0 6.4 5.2 4.0
25C-E9P9N104 9.9 7.9 6.4 5.0 11.2 9.0 7.3 5.6
25C-E012N104 12.0 9.6 7.8 6.0 13.5 10.8 8.8 6.8
PowerFlex 527 Input Current Scaled By Motor Current (Continued)
Catalog Number
Output Input
12345678
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 135
Appendix A Supplemental Drive Information
Appendix
25C-E019N104 19.0 15.2 12.4 9.5 24.0 19.2 15.6 12.0
25C-E022N104 22.0 17.6 14.3 11.0 27.3 21.8 17.7 13.7
25C-E027N104 27.0 21.6 17.6 13.5 24.7 19.8 16.1 12.4
25C-E032N104 32.0 25.6 20.8 16.0 29.2 23.4 19.0 14.6
PowerFlex 527 Input Current Scaled By Motor Current (Continued)
Catalog Number
Output Input
12345678
136 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix A Supplemental Drive Information
Notes:
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 137
Appendix B
Accessories and Dimensions
Product Selection
Catalog Number Description
25C - V 2P5 N 1 0 4
Drive Voltage Rating Rating Enclosure HIM Emission Class Version
PowerFlex 527 Drive Ratings
Output Ratings
Input
Voltage Range
Frame
Size
Catalog No.Normal Duty Heavy Duty
Output
Current (A)
HP kW HP kW
100...120V AC (-15%, +10%) – 1-Phase Input, 0...230V 3-Phase Output
0.5 0.4 0.5 0.4 2.5 85...132 A 25C-V2P5N104
1.0 0.75 1.0 0.75 4.8 85...132 B 25C-V4P8N104
1.5 1.1 1.5 1.1 6.0 85...132 B 25C-V6P0N104
200...240V AC (-15%, +10%) – 1-Phase Input, 0...230V 3-Phase Output
0.5 0.4 0.5 0.4 2.5 170...264 A 25C-A2P5N104
1.0 0.75 1.0 0.75 4.8 170...264 A 25C-A4P8N104
2.0 1.5 2.0 1.5 8.0 170...264 B 25C-A8P0N104
3.0 2.2 3.0 2.2 11.0 170...264 B 25C-A011N104
200...240V AC (-15%, +10%) – 1-Phase Input with EMC Filter, 0...230V 3-Phase Output
0.5 0.4 0.5 0.4 2.5 170...264 A 25C-A2P5N114
1.0 0.75 1.0 0.75 4.8 170...264 A 25C-A4P8N114
2.0 1.5 2.0 1.5 8.0 170...264 B 25C-A8P0N114
3.0 2.2 3.0 2.2 11.0 170...264 B 25C-A011N114
200...240V AC (-15%, +10%) – 3-Phase Input, 0...230V 3-Phase Output
0.5 0.4 0.5 0.4 2.5 170...264 A 25C-B2P5N104
1.0 0.75 1.0 0.75 5.0 170...264 A 25C-B5P0N104
2.0 1.5 2.0 1.5 8.0 170...264 A 25C-B8P0N104
3.0 2.2 3.0 2.2 11.0 170...264 A 25C-B011N104
5.0 4.0 5.0 4.0 17.5 170...264 B 25C-B017N104
7.5 5.5 7.5 5.5 24.0 170...264 C 25C-B024N104
10.0 7.5 10.0 7.5 32.2 170...264 D 25C-B032N104
15.0 11.0 10.0 7.5 48.3 170...264 E 25C-B048N104
20.0 15.0 15.0 11.0 62.1 170...264 E 25C-B062N104
380...480V AC (-15%, +10%) – 3-Phase Input, 0...460V 3-Phase Output
(1)
0.5 0.4 0.5 0.4 1.4 323...528 A 25C-D1P4N104
1.0 0.75 1.0 0.75 2.3 323...528 A 25C-D2P3N104
2.0 1.5 2.0 1.5 4.0 323...528 A 25C-D4P0N104
3.0 2.2 3.0 2.2 6.0 323...528 A 25C-D6P0N104
5.0 4.0 5.0 4.0 10.5 323...528 B 25C-D010N104
7.5 5.5 7.5 5.5 13.0 323...528 C 25C-D013N104
10.0 7.5 10.0 7.5 17.0 323...528 C 25C-D017N104
15.0 11.0 15.0 11.0 24.0 323...528 D 25C-D024N104
138 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
20.0 15.0 15.0 11.0 30.0 323...528 D 25C-D030N104
380...480V AC (-15%, +10%) – 3-Phase Input with EMC Filter, 0...460V 3-Phase Output
0.5 0.4 0.5 0.4 1.4 323...528 A 25C-D1P4N114
1.0 0.75 1.0 0.75 2.3 323...528 A 25C-D2P3N114
2.0 1.5 2.0 1.5 4.0 323...528 A 25C-D4P0N114
3.0 2.2 3.0 2.2 6.0 323...528 A 25C-D6P0N114
5.0 4.0 5.0 4.0 10.5 323...528 B 25C-D010N114
7.5 5.5 7.5 5.5 13.0 323...528 C 25C-D013N114
10.0 7.5 10.0 7.5 17.0 323...528 C 25C-D017N114
15.0 11.0 15.0 11.0 24.0 323...528 D 25C-D024N114
20.0 15.0 15.0 11.0 30.0 323...528 D 25C-D030N114
25.0 18.5 20.0 15.0 37.0 323...528 E 25C-D037N114
30.0 22.0 25.0 18.5 43.0 323...528 E 25C-D043N114
525...600V AC (-15%, +10%) – 3-Phase Input, 0...575V 3-Phase Output
0.5 0.4 0.5 0.4 0.9 446...660 A 25C-E0P9N104
1.0 0.75 1.0 0.75 1.7 446...660 A 25C-E1P7N104
2.0 1.5 2.0 1.5 3.0 446...660 A 25C-E3P0N104
3.0 2.2 3.0 2.2 4.2 446...660 A 25C-E4P2N104
5.0 4.0 5.0 4.0 6.6 446...660 B 25C-E6P6N104
7.5 5.5 7.5 5.5 9.9 446...660 C 25C-E9P9N104
10.0 7.5 10.0 7.5 12.0 446...660 C 25C-E012N104
15.0 11.0 15.0 11.0 19.0 446...660 D 25C-E019N104
20.0 15.0 15.0 11.0 22.0 446...660 D 25C-E022N104
25.0 18.5 20.0 15.0 27.0 446...660 E 25C-E027N104
30.0 22.0 25.0 18.5 32.0 446...660 E 25C-E032N104
(1) A non-filtered drive is not available for 380…480V AC 25 HP (18.5 kW) and 30 HP (22.0 kW) ratings. Filtered drives are
available, however you must verify that the application supports a filtered drive.
Dynamic Brake Resistors
Drive Ratings Minimum
Resistance,
Ω ±10%
Resistance,
Ω ±5%
Catalog No.
(1)(2)
Dynamic Brake
Fuse Rating, A
(3)
Fuse Model
Number
(4)
Input Voltage HP kW
100...120V
50/60 Hz
1-Phase
0.25 0.2 56 91 AK-R2-091P500 15 PV-15A10F
0.5 0.4 56 91 AK-R2-091P500 15 PV-15A10F
1.0 0.75 56 91 AK-R2-091P500 15 PV-15A10F
1.5 1.1 41 91 AK-R2-091P500 15 PV-15A10F
200...240V
50/60 Hz
1-Phase
0.25 0.2 56 91 AK-R2-091P500 15 PV-15A10F
0.5 0.4 56 91 AK-R2-091P500 15 PV-15A10F
1.0 0.75 56 91 AK-R2-091P500 15 PV-15A10F
2.0 1.5 41 91 AK-R2-091P500 32 PV-32ANH1
3.0 2.2 32 47 AK-R2-047P500 32 PV-32ANH1
PowerFlex 527 Drive Ratings (Continued)
Output Ratings
Input
Voltage Range
Frame
Size
Catalog No.Normal Duty Heavy Duty
Output
Current (A)
HP kW HP kW
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 139
Appendix B Accessories and Dimensions
200...240V
50/60 Hz
3-Phase
0.25 0.2 56 91 AK-R2-091P500 20 PV-20A10F
0.5 0.4 56 91 AK-R2-091P500 20 PV-20A10F
1.0 0.75 56 91 AK-R2-091P500 20 PV-20A10F
2.0 1.5 41 91 AK-R2-091P500 20 PV-20A10F
3.0 2.2 32 47 AK-R2-047P500 20 PV-20A10F
5.0 4.0 18 47 AK-R2-047P500 32 PV-32ANH1
7.5 5.5 16 30 AK-R2-030P1K2 40 PV-40ANH1
10.0 7.5 14 30 AK-R2-030P1K2 50 1000GH-040
15.0 11.0 14 15
AK-R2-030P1K2
(5)
80 1000GH-050
20.0 15.0 10 15
AK-R2-030P1K2
(5)
80 1000GH-050
380...480V
50/60 Hz
3-Phase
0.5 0.4 89 360 AK-R2-360P500 10 PV-10A10F
1.0 0.75 89 360 AK-R2-360P500 10 PV-10A10F
2.0 1.5 89 360 AK-R2-360P500 10 PV-10A10F
3.0 2.2 89 120 AK-R2-120P1K2 10 PV-10A10F
5.0 4.0 47 120 AK-R2-120P1K2 20 PV-20A10F
7.5 5.5 47 120 AK-R2-120P1K2 32 PV-32ANH1
10.0 7.5 47 120 AK-R2-120P1K2 32 PV-32ANH1
15.0 11.0 43 60
AK-R2-120P1K2
(5)
50 1000GH-025
20.0 15.0 43 60
AK-R2-120P1K2
(5)
50 1000GH-025
25.0 18.5 27 40
AK-R2-120P1K2
(6)
63 1000GH-040
30.0 22.0 27 40
AK-R2-120P1K2
(6)
63 1000GH-040
525...600V
50/60 Hz
3-Phase
0.5 0.4 112 360 AK-R2-360P500 10 PV-10A10F
1.0 0.75 112 360 AK-R2-360P500 10 PV-10A10F
2.0 1.5 112 360 AK-R2-360P500 10 PV-10A10F
3.0 2.2 112 120 AK-R2-120P1K2 10 PV-10A10F
5.0 4.0 86 120 AK-R2-120P1K2 12 PV-12A10F
7.5 5.5 59 120 AK-R2-120P1K2 20 PV-20A10F
10.0 7.5 59 120 AK-R2-120P1K2 20 PV-20A10F
15.0 11.0 59 60
AK-R2-120P1K2
(5)
40 1000GH-025
20.0 15.0 59 60
AK-R2-120P1K2
(5)
40 1000GH-025
25.0 18.5 53 60
AK-R2-120P1K2
(5)
40 1000GH-040
30.0 22.0 34 40
AK-R2-120P1K2
(6)
40 1000GH-040
(1) The resistors that are listed in this table are rated for 5% duty cycle.
(2) Use of Rockwell Automation resistors is always recommended. The resistors that are listed have been carefully selected to
optimize performance in various applications. Alternative resistors may be used, however, care must be taken when making
a selection. See the PowerFlex Dynamic Braking Resistor Calculator Application Technique, publication PFLEX-AT001
.
(3) Connect a 1000V DC fuse links at BR+ terminal in series with the dynamic brake resistor.
(4) PV-xxxxxx fuses are from Bussman. 1000GH-xxx fuses are from Hinode.
(5) Requires two resistors that are wired in parallel.
(6) Requires three resistors that are wired in parallel.
EMC Line Filters
Short-circuit Current Rating = 100 kA
Drive Ratings
Frame Size
For 100 m
Catalog No.
For 150 m
(1)
Catalog No.
Input Voltage HP kW Current (A)
100...120V
50/60 Hz
1-Phase
0.25 0.2 1.6 A 25-RF011-AL
0.5 0.4 2.5 A 25-RF011-AL
1.0 0.75 4.8 B 25-RF023-BL
1.5 1.1 6.0 B 25-RF023-BL
Dynamic Brake Resistors (Continued)
Drive Ratings Minimum
Resistance,
Ω ±10%
Resistance,
Ω ±5%
Catalog No.
(1)(2)
Dynamic Brake
Fuse Rating, A
(3)
Fuse Model
Number
(4)
Input Voltage HP kW
140 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
200...240V
50/60 Hz
1-Phase
0.25 0.2 1.6 A 25-RF011-AL
0.5 0.4 2.5 A 25-RF011-AL
1.0 0.75 4.8 A 25-RF011-AL
2.0 1.5 8.0 B 25-RF023-BL
3.0 2.2 11.0 B 25-RF023-BL
200...240V
50/60 Hz
3-Phase
0.25 0.2 1.6 A 25-RF014-AL 25-RF021-BL
0.5 0.4 2.5 A 25-RF014-AL 25-RF021-BL
1.0 0.75 5.0 A 25-RF014-AL 25-RF021-BL
2.0 1.5 8.0 A 25-RF014-AL 25-RF021-BL
3.0 2.2 11.0 A 25-RF014-AL 25-RF021-BL
5.0 4.0 17.5 B 25-RF021-BL
7.5 5.5 24.0 C 25-RF027-CL
10.0 7.5 32.2 D 25-RF035-DL
15.0 11.0 48.3 E 25-RF056-EL
20.0 15.0 62.1 E 25-RF056-EL
380...480V
50/60 Hz
3-Phase
0.5 0.4 1.4 A 25-RF7P5-AL 25-RF014-BL
1.0 0.75 2.3 A 25-RF7P5-AL 25-RF014-BL
2.0 1.5 4.0 A 25-RF7P5-AL 25-RF014-BL
3.0 2.2 6.0 A 25-RF7P5-AL 25-RF014-BL
5.0 4.0 10.5 B 25-RF014-BL
7.5 5.5 13.0 C 25-RF018-CL
10.0 7.5 17.0 C 25-RF018-CL
15.0 11.0 24.0 D 25-RF033-DL
20.0 15.0 30.0 D 25-RF033-DL
25.0 18.5 37.0 E 25-RF039-EL
30.0 22.0 43.0 E 25-RF039-E
525...600V
50/60 Hz
3-Phase
0.5 0.4 0.9 A
25-RF8P0-BL
(2)
1.0 0.75 1.7 A
25-RF8P0-BL
(2)
2.0 1.5 3.0 A
25-RF8P0-BL
(2)
3.0 2.2 4.2 A
25-RF8P0-BL
(2)
5.0 4.0 6.6 B 25-RF8P0-BL
7.5 5.5 9.9 C 25-RF014-CL
10.0 7.5 12.0 C 25-RF014-CL
15.0 11.0 19.0 D 25-RF027-DL
20.0 15.0 22.0 D 25-RF027-DL
25.0 18.5 27.0 E 25-RF029-EL
30.0 22.0 32.0 E 25-RF029-EL
(1) Requires Series B filters to achieve 150 m rating.
(2) The 600V drive rating must be matched with a frame B Line Filter.
EMC Plates
Item Description
Frame
Size
Catalog No.
EMC Plate Optional grounding plate for shielded cables.
A 25-EMC1-FA
B 25-EMC1-FB
C 25-EMC1-FC
D 25-EMC1-FD
E 25-EMC1-FE
EMC Line Filters (Continued)
Short-circuit Current Rating = 100 kA
Drive Ratings
Frame Size
For 100 m
Catalog No.
For 150 m
(1)
Catalog No.
Input Voltage HP kW Current (A)
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 141
Appendix B Accessories and Dimensions
Replacement Parts
IP 30/NEMA 1/UL Type 1 Kit
Item Description
Frame
Size
Catalog No.
IP 30/NEMA 1/UL Type 1 Kit
Field installed kit. Converts drive to IP 30/NEMA 1/UL Type 1
enclosure. Includes conduit box with mounting screws and
plastic top panel.
A25-JBAA
B25-JBAB
C25-JBAC
D25-JBAD
E25-JBAE
Control Module Fan Kit
Item Description
Frame
Size
Catalog No.
Control Module Fan Kit
For use with drive in environments with ambient
temperatures up to 70 °C or horizontal mounting.
A…D 25-FAN1-70C
E 25-FAN2-70C
Incremental Encoder Input Option
Item Description Catalog No.
Incremental Encoder
Board
Interface to an external incremental encoder. 25-ENC-2
Bulletin 160 to PowerFlex 527 Mounting Adapter Plate
Item Description
B160
Frame
Size
Catalog No.
Mounting Adapter Plate
For use with drive when replacing Bulletin 160 drives in
existing installations to a PowerFlex 520-Series drive. Select
the catalog number based on the frame size of your Bulletin
160 drive.
A25-MAP-FA
B25-MAP-FB
PowerFlex 527 Power Module
Item Description
PowerFlex 527
Power Module
Replacement power module for use with PowerFlex 527 drive.
Includes:
Power Module
Power Module Front Cover
Power Terminal Guard
•Heatsink Fan
PowerFlex 527 Power Module
Output Ratings
Input
Voltage Range
Frame
Size
Catalog No.Normal Duty Heavy Duty
Output
Current (A)
HP kW HP kW
100...120V AC (-15%, +10%) – 1-Phase Input, 0...230V 3-Phase Output
0.5 0.4 0.5 0.4 2.5 85…132 A 25-PM1-V2P5
1.0 0.75 1.0 0.75 4.8 85132 B 25-PM1-V4P8
1.51.1 1.51.1 6.0 85132B25-PM1-V6P0
200240V AC (-15%, +10%) – 1-Phase Input, 0230V 3-Phase Output
0.5 0.4 0.5 0.4 2.5 170…264 A 25-PM1-A2P5
1.0 0.75 1.0 0.75 4.8 170264 A 25-PM1-A4P8
2.0 1.5 2.0 1.5 8.0 170…264 B 25-PM1-A8P0
3.0 2.2 3.0 2.2 11.0 170…264 B 25-PM1-A011
200240V AC (-15%, +10%) – 1-Phase Input with EMC Filter, 0230V 3-Phase Output
0.5 0.4 0.5 0.4 2.5 170…264 A 25-PM2-A2P5
1.0 0.75 1.0 0.75 4.8 170264 A 25-PM2-A4P8
142 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
2.0 1.5 2.0 1.5 8.0 170…264 B 25-PM2-A8P0
3.0 2.2 3.0 2.2 11.0 170…264 B 25-PM2-A011
200240V AC (-15%, +10%) – 3-Phase Input, 0230V 3-Phase Output
0.5 0.4 0.5 0.4 2.5 170…264 A 25-PM1-B2P5
1.0 0.75 1.0 0.75 5.0 170…264 A 25-PM1-B5P0
2.0 1.5 2.0 1.5 8.0 170…264 A 25-PM1-B8P0
3.0 2.2 3.0 2.2 11.0 170…264 A 25-PM1-B011
5.0 4.0 5.0 4.0 17.5 170…264 B 25-PM1-B017
7.5 5.5 7.5 5.5 24.0 170…264 C 25-PM1-B024
10.0 7.5 10.0 7.5 32.2 170…264 D 25-PM1-B032
15.0 11.0 10.0 7.5 48.3 170264 E 25-PM1-B048
20.0 15.0 15.0 11.0 62.1 170264 E 25-PM1-B062
380480V AC (-15%, +10%) – 3-Phase Input, 0...460V 3-Phase Output
0.5 0.4 0.5 0.4 1.4 323…528 A 25-PM1-D1P4
1.0 0.75 1.0 0.75 2.3 323…528 A 25-PM1-D2P3
2.0 1.5 2.0 1.5 4.0 323…528 A 25-PM1-D4P0
3.0 2.2 3.0 2.2 6.0 323…528 A 25-PM1-D6P0
5.0 4.0 5.0 4.0 10.5 323…528 B 25-PM1-D010
7.5 5.5 7.5 5.5 13.0 323528 C 25-PM1-D013
10.0 7.5 10.0 7.5 17.0 323528 C 25-PM1-D017
15.0 11.0 15.0 11.0 24.0 323528 D 25-PM1-D024
20.0 15.0 15.0 11.0 30.0 323528 D 25-PM1-D030
380480V AC (-15%, +10%) – 3-Phase Input with EMC Filter, 0...460V 3-Phase Output
0.5 0.4 0.5 0.4 1.4 323…528 A 25-PM2-D1P4
1.0 0.75 1.0 0.75 2.3 323…528 A 25-PM2-D2P3
2.0 1.5 2.0 1.5 4.0 323…528 A 25-PM2-D4P0
3.0 2.2 3.0 2.2 6.0 323…528 A 25-PM2-D6P0
5.0 4.0 5.0 4.0 10.5 323…528 B 25-PM2-D010
7.5 5.5 7.5 5.5 13.0 323528 C 25-PM2-D013
10.0 7.5 10.0 7.5 17.0 323528 C 25-PM2-D017
15.0 11.0 15.0 11.0 24.0 323528 D 25-PM2-D024
20.0 15.0 15.0 11.0 30.0 323528 D 25-PM2-D030
25.0 18.5 20.0 15.0 37.0 323528 E 25-PM2-D037
30.0 22.0 25.0 18.5 43.0 323528 E 25-PM2-D043
525600V AC (-15%, +10%) – 3-Phase Input, 0575V 3-Phase Output
0.5 0.4 0.5 0.4 0.9 446…660 A 25-PM1-E0P9
1.0 0.75 1.0 0.75 1.7 446660 A 25-PM1-E1P7
2.0 1.5 2.0 1.5 3.0 446…660 A 25-PM1-E3P0
3.0 2.2 3.0 2.2 4.2 446…660 A 25-PM1-E4P2
5.0 4.0 5.0 4.0 6.6 446…660 B 25-PM1-E6P6
7.5 5.5 7.5 5.5 9.9 446…660 C 25-PM1-E9P9
10.0 7.5 10.0 7.5 12.0 446…660 C 25-PM1-E012
15.0 11.0 15.0 11.0 19.0 446660 D 25-PM1-E019
20.0 15.0 15.0 11.0 22.0 446660 D 25-PM1-E022
25.0 18.5 20.0 15.0 27.0 446660 E 25-PM1-E027
30.0 22.0 25.0 18.5 32.0 446660 E 25-PM1-E032
PowerFlex 527 Power Module (Continued)
Output Ratings
Input
Voltage Range
Frame
Size
Catalog No.Normal Duty Heavy Duty
Output
Current (A)
HP kW HP kW
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 143
Appendix B Accessories and Dimensions
PowerFlex 527 Control Module
Item Description
Frame
Size
Catalog No.
PowerFlex 527
Control Module
Replacement control module for use with PowerFlex 527 drives.
Includes:
Control Module
Control Module Front Cover
A…E 25C-CTM1
Other Parts
Item Description
Frame
Size
Catalog No.
PowerFlex 527 Control
Module Front Cover
Replacement cover for the control module I/O terminals and
EtherNet/IP ports.
A...E 25C-CTMFC1
PowerFlex 520-Series
Power Module Front
Cover
Replacement cover for the PowerFlex 520-Series power
module.
B25-PMFC-FB
C25-PMFC-FC
D25-PMFC-FD
E25-PMFC-FE
PowerFlex 520-Series
Power Terminal Guard
Replacement finger guard for power terminals.
A25-PTG1-FA
B25-PTG1-FB
C25-PTG1-FC
D25-PTG1-FD
E25-PTG1-FE
PowerFlex 527
Removable Terminal
Blocks Kit
Replacement terminal blocks for control wiring. A…E 25C-RCTB
PowerFlex 527 Control
Module Internal Fan Kit
Replacement internal fan for the control module. A…E 25C-FAN2-INT
PowerFlex 520-Series
Heatsink Fan Kit
Replacement fan for drive power module.
A25-FAN1-FA
B25-FAN1-FB
C25-FAN1-FC
D25-FAN1-FD
E25-FAN1-FE
Bulletin 1321-3R Series Line Reactors
Output Ratings
(1)
Input Line Reactor
(2)(3)
Output Line Reactor
Normal Duty Heavy Duty
IP00
(Open Style)
IP11
(NEMA/UL Type 1)
IP00
(Open Style)
IP11
(NEMA/UL Type 1)
HP kW HP kW Catalog No. Catalog No. Catalog No. Catalog No.
200…240V 50/60 Hz 1-Phase
(4)
0.25 0.2 0.25 0.2 1321-3R4-A 1321-3RA4-A 1321-3R2-D 1321-3RA2-D
0.5 0.4 0.5 0.4 1321-3R8-A 1321-3RA8-A 1321-3R2-D 1321-3RA2-D
1.0 0.75 1.0 0.75 1321-3R8-A 1321-3RA8-A 1321-3R4-A 1321-3RA4-A
2.0 1.5 2.0 1.5 1321-3R18-A 1321-3RA18-A 1321-3R8-A 1321-3RA8-A
3.0 2.2 3.0 2.2 1321-3R18-A 1321-3RA18-A 1321-3R12-A 1321-3RA12-A
200...240V 50/60 Hz 3-Phase
0.25 0.2 0.25 0.2 1321-3R2-D 1321-3RA2-D 1321-3R2-D 1321-3RA2-D
0.5 0.4 0.5 0.4 1321-3R2-D 1321-3RA2-D 1321-3R2-D 1321-3RA2-D
1.0 0.75 1.0 0.75 1321-3R4-A 1321-3RA4-A 1321-3R4-A 1321-3RA4-A
2.0 1.5 2.0 1.5 1321-3R8-A 1321-3RA8-A 1321-3R8-A 1321-3RA8-A
3.0 2.2 3.0 2.2 1321-3R12-A 1321-3RA12-A 1321-3R12-A 1321-3RA12-A
5.0 4.0 5.0 4.0 1321-3R18-A 1321-3RA18-A 1321-3R18-A 1321-3RA18-A
7.5 5.5 7.5 5.5 1321-3R25-A 1321-3RA25-A 1321-3R25-A 1321-3RA25-A
10.0 7.5 10.0 7.5 1321-3R35-A 1321-3RA35-A 1321-3R35-A 1321-3RA35-A
15.0 11.0 10.0 7.5 1321-3R45-A 1321-3RA45-A 1321-3R45-A 1321-3RA45-A
144 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
Product Dimensions The PowerFlex 527 drive is available in five frame sizes. See the PowerFlex 527
Drive Ratings on page 137 for information on power ratings.
20.0 15.0 15.0 11.0
1321-3R55-A (ND)
1321-3R45-A (HD)
1321-3RA55-A (ND)
1321-3RA45-A (HD)
1321-3R55-A (ND)
1321-3R45-A (HD)
1321-3RA55-A (ND)
1321-3RA45-A (HD)
380480V 50/60 Hz 3-Phase
0.5 0.4 0.5 0.4 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B
1.0 0.75 1.0 0.75 1321-3R4-C 1321-3RA4-C 1321-3R4-C 1321-3RA4-C
2.0 1.5 2.0 1.5 1321-3R4-B 1321-3RA4-B 1321-3R4-B 1321-3RA4-B
3.0 2.2 3.0 2.2 1321-3R8-C 1321-3RA8-C 1321-3R8-C 1321-3RA8-C
5.0 4.0 5.0 4.0 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B
7.5 5.5 7.5 5.5 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B
10.0 7.5 10.0 7.5 1321-3R18-B 1321-3RA18-B 1321-3R18-B 1321-3RA18-B
15.0 11.0 15.0 11.0 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B
20.0 15.0 15.0 11.0
1321-3R35-B (ND)
1321-3R25-B (HD)
1321-3RA35-B (ND)
1321-3RA25-B (HD)
1321-3R35-B (ND)
1321-3R25-B (HD)
1321-3RA35-B (ND)
1321-3RA25-B (HD)
25.0 18.5 20.0 15.0 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B
30.0 22.0 25.0 18.5
1321-3R45-B (ND)
1321-3R35-B (HD)
1321-3RA45-B (ND)
1321-3RA35-B (HD)
1321-3R45-B (ND)
1321-3R35-B (HD)
1321-3RA45-B (ND)
1321-3RA35-B (HD)
525600V 50/60 Hz 3-Phase
0.5 0.4 0.5 0.4 1321-3R1-C 1321-3RA1-C 1321-3R1-C 1321-3RA1-C
1.0 0.75 1.0 0.75 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B
2.0 1.5 2.0 1.5 1321-3R4-C 1321-3RA4-C 1321-3R4-C 1321-3RA4-C
3.0 2.2 3.0 2.2 1321-3R4-B 1321-3RA4-B 1321-3R4-B 1321-3RA4-B
5.0 4.0 5.0 4.0 1321-3R8-C 1321-3RA8-C 1321-3R8-C 1321-3RA8-C
7.5 5.5 7.5 5.5 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B
10.0 7.5 10.0 7.5 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B
15.0 11.0 15.0 11.0 1321-3R18-B 1321-3RA18-B 1321-3R18-B 1321-3RA18-B
20.0 15.0 15.0 11.0
1321-3R25-B (ND)
1321-3R18-B (HD)
1321-3RA25-B (ND)
1321-3RA18-B (HD)
1321-3R25-B (ND)
1321-3R18-B (HD)
1321-3RA25-B (ND)
1321-3RA18-B (HD)
25.0 18.5 20.0 15.0
1321-3R35-C (ND)
1321-3R25-C (HD)
1321-3RA35-C (ND)
1321-3RA25-C (HD)
1321-3R35-C (ND)
1321-3R25-C (HD)
1321-3RA35-C (ND)
1321-3RA25-C (HD)
30.0 22.0 25.0 18.5
1321-3R35-C (ND)
1321-3R25-B (HD)
1321-3RA35-C (ND)
1321-3RA25-B (HD)
1321-3R35-C (ND)
1321-3R25-B (HD)
1321-3RA35-C (ND)
1321-3RA25-B (HD)
(1) Normal Duty and Heavy Duty ratings for 15 HP (11 kW) and below are identical except for 200240V 3-Phase 15 HP (11 kW)
drive.
(2) Catalog numbers that are listed are for 3% impedance at 60 Hz. 5% impedance reactor types are also available. See the 1321
Power Conditioning Products Technical Data, publication 1321-TD001.
(3) Input line reactors were sized based on the NEC fundamental motor amps. Output line reactors were sized based on the VFD
rated output currents.
(4) Standard 3-phase reactors can be used for 1-phase applications by routing each of the two supply conductors through an
outside coil and leaving the center open.
Bulletin 1321-3R Series Line Reactors (Continued)
Output Ratings
(1)
Input Line Reactor
(2)(3)
Output Line Reactor
Normal Duty Heavy Duty
IP00
(Open Style)
IP11
(NEMA/UL Type 1)
IP00
(Open Style)
IP11
(NEMA/UL Type 1)
HP kW HP kW Catalog No. Catalog No. Catalog No. Catalog No.
PowerFlex 527 Drive Weight
Frame Size Weight (kg/lb)
A1.1 / 2.4
B1.6 / 3.5
C2.3 / 5.0
D3.9 / 8.6
E 12.9 / 28.4
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 145
Appendix B Accessories and Dimensions
IP 20/Open Type – Frame A
IP 20/Open Type – Frame B
72.0 (2.83)
57.5 (2.26)
172.0 (6.77)
140.0 (5.51)
152.0 (5.98)
92.7 (3.65)
6.0 (0.24)
Dimensions are in millimeters and (inches)
87.0 (3.43)
72.5 (2.85)
172.0 (6.77)
6.0 (0.24)
92.7 (3.65)
168.0 (6.61)
180.0 (7.09)
Dimensions are in millimeters and (inches)
146 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
IP 20/Open Type – Frame C
IP 20/Open Type – Frame D
109.0 (4.29)
90.5 (3.56)
207.0 (8.15)
220.0 (8.66)
184.0 (7.24)
6.0 (0.24)
92.7 (3.65)
Dimensions are in millimeters and (inches)
130.0 (5.12)
116.0 (4.57)
247.0 (9.72)
260.0 (10.24)
6.0 (0.24)
212.0 (8.35)
Dimensions are in millimeters and (inches)
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 147
Appendix B Accessories and Dimensions
IP 20/Open Type – Frame E
185.0 (7.28)
160.0 (6.30)
279.0 (10.98)
280.0 (11.02)
300.0 (11.81)
7.6 (0.30)
Dimensions are in millimeters and (inches)
148 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
Control Module Fan Kit
IP 20/Open Type with Control Module Fan Kit – Frame A...C
Specifications 25-FAN1-70C 25-FAN2-70C
Rated Voltage 24V DC
Operation Voltage 14…27.6V DC
Input Current 0.1 A 0.15 A
Speed (Reference) 7000 rpm 4500 ± 10% rpm
Maximum Air Flow (At zero static pressure)
0.575 m
3
/min 1.574 m
3
/min
Maximum Air Pressure (At zero air flow)
7.70 mmH
2
O 9.598 mmH
2
O
Acoustical Noise 40.5 dBA 46.0 dBA
Insulation Type UL Class A
Frame Size Frame A…D Frame E
Wire Size
0.32 mm
2
(22 AWG)
Torque 0.29…0.39 N•m (2.6…3.47 lb•in)
25-FAN1-70C 25-FAN2-70C
72.0 (2.83)
32.0 (1.26)
140.0 (5.51)
152.0 (5.98)
57.5 (2.26)
87.0 (3.43)
32.0 (1.26)
180.0 (7.09)
168.0 (6.61)
72.5 (2.85)
109.0 (4.29)
32.0 (1.26)
220.0 (8.66)
207.0 (8.15)
90.5 (3.56)
Frame A Frame B
Dimensions are in millimeters and (inches)
Frame C
IMPORTANT An external 24V DC power source is required when
using the Control Module Fan Kit with drive frames
A, B, and C.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 149
Appendix B Accessories and Dimensions
IP 20/Open Type with Control Module Fan Kit – Frame D…E
130.0 (5.12)
32.0 (1.26)
260.0 (10.24)
247.0 (9.72)
116.0 (4.57)
185.0 (7.28)
196.0 (7.72)
52.0 (2.05)
300.0 (11.81)
280.0 (11.02)
160.0 (6.30)
Dimensions are in millimeters and (inches)
Frame D Frame E
IMPORTANT Remove the label to access the built-in 24V supply on drive frames D and E for use with the
Control Module Fan Kit.
150 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
IP 30/NEMA 1/UL Type 1 – Frame A
72.0 (2.83)
172.0 (6.77)
6.0 (0.24)
51.1 (2.01)
21.0 (0.82)
57.5 (2.26)
15.0 (0.59)
219.0 (8.62)
92.7 (3.65)
140.0 (5.51)
135.4 (5.33)
111.9 (4.41)
88.2 (3.47)
64.7 (2.55)
152.0 (5.98)
ø21.5 (ø0.85)
Dimensions are in millimeters and (inches)
IP 30/NEMA 1/ UL Type 1 conduit box
IP 30/NEMA 1/ UL Type 1 top panel
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 151
Appendix B Accessories and Dimensions
IP 30/NEMA 1/UL Type 1 – Frame B
87.0 (3.43)
172.0 (6.77)
6.1 (0.24)
72.5 (2.85)
66.1 (2.60)
63.1 (2.48)
33.5 (1.32)
23.9 (0.94)
15.0 (0.59)
92.7 (3.65)
218.0 (8.58)
180.0 (7.09)
168.0 (6.61)
128.5 (5.06)
108.5 (4.27)
88.3 (3.48)
67.3 (2.65)
ø21.5 (ø0.85)
ø27.5 (ø1.08)
Dimensions are in millimeters and (inches)
IP 30/NEMA 1/ UL Type 1 conduit box
IP 30/NEMA 1/ UL Type 1 top panel
152 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
IP 30/NEMA 1/UL Type 1 – Frame C
109.0 (4.29)
184.0 (7.24)
15.0 (0.59)
207.0 (8.15)
123.3 (4.85)
82.2 (3.24)
222.0 (8.66)
92.7 (3.65)
255.0 (10.04)
90.5 (3.56)
80.5 (3.17)
66.5 (2.62)
34.5 (1.36)
26.5 (1.04)
6.0 (0.24)
ø21.5 (ø0.85)
ø27.5 (ø1.08)
Dimensions are in millimeters and (inches)
IP 30/NEMA 1/ UL Type 1 conduit box
IP 30/NEMA 1/ UL Type 1 top panel
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 153
Appendix B Accessories and Dimensions
IP 30/NEMA 1/UL Type 1 – Frame D
130.0 (5.12)
212.0 (8.35)
6.0 (0.24)
260.0 (10.24)
295.0 (11.61)
15.0 (0.59)
247.0 (9.72)
109.8 (4.32)
153.3 (6.04)
116.0 (4.57)
96.0 (3.78)
44.0 (1.73)
30.0 (1.18)
70.0 (2.76)
ø21.5 (ø0.85)
ø33.5 (ø1.32)
Dimensions are in millimeters and (inches)
IP 30/NEMA 1/ UL Type 1 top panel
IP 30/NEMA 1/ UL Type 1 conduit box
154 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
IP 30/NEMA 1/UL Type 1 – Frame E
185.0 (7.28)
160.0 (6.30)
127.5 (5.02)
82.5 (3.25)
62.5 (2.46)
42.5 (1.67)
279.0 (10.98)
15.0 (0.59)
350.0 (13.78)
300.0 (11.81)
280.0 (11.02)
212.0 (8.35)
181.0 (7.13)
164.0 (6.46)
7.6 (0.30)
ø21.5 (ø0.85)
ø43.7 (ø1.72)
Dimensions are in millimeters and (inches)
IP 30/NEMA 1/ UL Type 1 conduit box
IP 30/NEMA 1/ UL Type 1 top panel
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 155
Appendix B Accessories and Dimensions
EMC Line Filter – Frame A
EMC Line Filter – Frame B
ø5.5 (ø0.22)
72.0 (2.83)
54.0 (2.13)
5.5 (0.22)
54.0 (2.13)
23.0 (0.91)20.0 (0.79)
30.0 (1.18)
55.0 (2.17)
234.0
(9.21)
223.0
(8.78)
223.0
(8.78)
Dimensions are in millimeters and (inches) Filter can be mounted onto the back of the drive.
ø5.5 (ø0.22)
87.0 (3.43)
58.0 (2.28)
270.0
(10.63)
58.0 (2.28)
5.5 (0.22)
258.0
(10.16)
258.0
(10.16)
24.0 (0.94)25.0 (0.98)
35.0 (1.38)
70.0 (2.76)
Dimensions are in millimeters and (inches) Filter can be mounted onto the back of the drive.
156 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
EMC Line Filter – Frame C
EMC Line Filter – Frame D
ø5.5 (ø0.22)
263.0
(10.35)
263.0
(10.35)
25.0 (0.98) 28.0 (1.10)
76.0 (2.99)
5.5 (0.22)
275.0
(10.83)
109.0 (4.29)
70.0 (2.76)
76.0 (2.99)
37.0 (1.46)
Dimensions are in millimeters and (inches) Filter can be mounted onto the back of the drive.
ø5.5 (ø0.22)
80.0 (3.15)
130.0 (5.12)
90.0 (3.54)
33.0 (1.30)
33.0 (1.30)
28.0 (1.10)
28.0 (1.10)
298.0
(11.73)
298.0
(11.73)
310.0
(12.20)
90.0 (3.54)
5.5 (0.22)
Dimensions are in millimeters and (inches) Filter can be mounted onto the back of the drive.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 157
Appendix B Accessories and Dimensions
EMC Line Filter – Frame E
Replacing the PowerFlex 527 Control Module Internal Fan
To replace the internal fan, you must separate the control module from the
power module. Do not perform this operation while the drive is running. See
the PowerFlex 527 Control Module Internal Fan Kit Installation Instructions,
publication 520-IN014
for detailed instructions.
ATTENTION:
Temperature inside the control module may exceed 80 °C (176 °F) when the
internal fan is not working. Wait for the control module to cool down before
replacing the internal fan.
Take caution when replacing the internal fan as static damage may occur to
sensitive components inside the drive.
80.0 (3.15)
28.0 (1.10)
155.0 (6.10)
110.0 (4.33)
110.0 (4.33)
33.0 (1.30)
28.0 (1.10)33.0 (1.30)
375.0
(14.76)
375.0
(14.76)
390.0
(15.35)
ø5.5 (ø0.22)
5.5 (0.22)
Dimensions are in millimeters and (inches)
158 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix B Accessories and Dimensions
Notes:
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 159
Appendix
Appendix C
Out-of-Box Configuration
This section describes the recommended settings for configuring your
PowerFlex 527 drive to obtain the best performance from the drive. You should
apply these out-of-box settings first before configuring for your application.
Recommended Out-of-Box
Settings
Out-of-Box Settings
Setting in Logix Designer Example Recommended Configuration
Ramp Velocity Limits
120% of Motor Rated Speed for induction
motors
Current Vector Limit 180% of Motor Rated Current
160 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix C Out-of-Box Configuration
Torque Limits 200% of Motor Rated Torque
Velocity Error Tolerance Change Action to Alarm
Feedback Tap 16
Out-of-Box Settings (Continued)
Setting in Logix Designer Example Recommended Configuration
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 161
Appendix C Out-of-Box Configuration
Application Type setting in
Velocity Loop
Constant Speed
Motion Group Base Update Rate 4 ms
Out-of-Box Settings (Continued)
Setting in Logix Designer Example Recommended Configuration
162 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix C Out-of-Box Configuration
Setting the ACO/AVO
Attribute
The attribute ACO/AVO (Analog Current Output/Analog Voltage Output) can
be used to set the analog output of the PowerFlex 527 drive to either
current (mA) or voltage (V).
Verify that the Analog Out jumper (J2) is also set to the same value. See Analog
Output on page 36 for instructions.
ACO/AVO: MSG
Parameter Value Description
Service Code 0x10 Set Attribute Single
Class 0x42 Analog Output
Instance 1
Attribute 0xA64 Voltage/Current Mode
Data Type SINT Unsigned Short Integer
ACO/AVO: Values
Value Definition
0 Voltage (V)
1Current (mA)
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 163
Appendix
Appendix D
Encoder Option Card Usage
Installing the Encoder
Option Card
To install the encoder option card:
1. Separate the power module and control module. See Separating the
Power and Control Module on page 26 for instructions.
2. Place the encoder option card on the back of the control module. Verify
that the tabs on the encoder option card are aligned with the slots on the
control module.
3. Press down firmly on the encoder option card until it snaps together with
the control module.
164 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix D Encoder Option Card Usage
Removing the Encoder
Option Card
To remove the encoder option card:
1. Hold the top of the encoder option card firmly as shown below and pull
out to remove.
Encoder Option Card Usage PowerFlex 527 drives support an optional encoder card. The encoder supports
up to 250 kHz dual channel at 5V, 12V, or 24V and requires the optional
encoder board to be installed.
When the axis configuration is set to Position or Velocity loop, the Feedback
Configuration is enabled.
IMPORTANT Do not remove the encoder option card from the bottom as it may
damage the card and the locking mechanism on the control module.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 165
Appendix D Encoder Option Card Usage
In the Motor Feedback configuration, enter the resolution of the encoder used.
Encoder Interface
The incremental encoder option card can source 5V or 12V power and accept
5V, 12V, or 24V single ended or differential inputs. See Appendix B for ordering
information.
+V
Cm
B-
B
Z-
Z
A-
A
12V 5V
HTL TTL (ON)
No. Signal Description
+V
5...12V Power
(1)(2)
(1) When using 12V Encoder power, 24V I/O power, maximum output current at I/O Terminal 11 is 50 mA.
(2) If Encoder requires 24V power, it must be supplied by an external power source.
Internal power source 250 mA (isolated).
Cm Power Return
Z- Marker Z (NOT)
Marker pulse
ZMarker Z
B- Encoder B (NOT)
Quadrature B input.
BEncoder B
A- Encoder A (NOT)
Quadrature A input.
AEncoder A
Output
DIP switch selects 12V or 5V power that is supplied at terminals “+V” and
“Cm” for the encoder.
HTL/TTL DIP
switches
Set the position of the DIP switches based on the type of encoder signal
used. You must set all switches to the same position.
IMPORTANT A quadrature encoder provides rotor speed and direction. Therefore, the
encoder must be wired such that the forward direction matches the
motor forward direction. If the drive is reading encoder speed but the
position regulator or other encoder function is not working properly,
remove power to the drive and swap the A and A (NOT) encoder channels
or swap any two motor leads.
166 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Appendix D Encoder Option Card Usage
HTL/TTL DIP Switches
This feature is only available on 25-ENC-2/B encoders. Set the three switches to
HTL (default) or TTL (On) based on the type of encoder signal you are using in
your application. You must set all switches to the same position.
Wiring Notes The encoder option card can supply 5V or 12V power (250 mA maximum) for an
encoder. Verify that the DIP switch is set properly for the encoder. In general,
12V provides higher noise immunity.
The encoder can handle 5V, 12V, or 24V inputs. The inputs automatically adjust
to the voltage applied and no additional drive adjustment is necessary.
Encoder Wiring Examples
I/O Connection Example I/O Connection Example
Encoder Power
– Internal Drive
Power
Internal (drive)
12V DC, 250 mA
Encoder Power
– External
Power Source
Encoder Signal
– Single-Ended,
Dual Channel
Encoder Signal
– Differential,
Dual Channel
Compatible Encoder Output Voltage
Switch Position Low Level (UL) High Level (UH)
TTL <1.5V >2.5V
HTL <3.5V >5V
Common
+12V DC
(250 mA)
A
A-
B
B-
Z
Z-
Cm
+V
to SHLD
+
Common
External
Power
Supply
to
SHLD
Marker Z
A
B
Marker
Z NOT
to SHLD
to Power Supply
Common
A
A-
B
B-
Z
Z-
Cm
+V
to SHLD
A NOT
B
A
B NOT
Marker
Z NOT
Marker Z
A
A-
B
B-
Z
Z-
Cm
+V
IMPORTANT A quadrature encoder provides rotor speed and direction. Therefore, the
encoder must be wired such that the forward direction matches the
motor forward direction. If the drive is reading encoder speed but the
position regulator or other encoder function is not working properly,
remove power to the drive and swap the A and A (NOT) encoder channels
or swap any two motor leads.
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 167
Index
A
accessing
control terminals
29
power terminals
29
auxiliary contact
drive
32
B
basic operation
drive
45
C
circuit breakers
inputs
20
ratings 20
control terminals
accessing
29
D
derating
temperature
15
dimensions
mounting
14, 144
disconnect
output
32
drive
auxiliary contact
32
basic operation 45
mount
13
programming
51
drive damage
preventing
17
ungrounded distribution systems
17
E
encoder
wiring
166
environment
storage
16
F
fault monitoring
ground
18
fuses
rating
20
G
ground
fault monitoring
18
motor
19
RFI filter
19
safety
19
shielding
19
I
inputs
circuit breakers
20
power
18
M
motor
ground
19
start 32
stop
32
mount
drive
13
mounting
dimensions
14, 144
N
noise immunity
wiring
34
O
output
disconnect
32
P
power
inputs
18
power and control module
separating
26
power terminals
accessing
29
preventing
drive damage
17
programming
drive
51
tools
51
R
rating
fuses
20
ratings
circuit breakers
20
recommended
wiring
33, 34
reflected
wave protection
32
RFI filter
ground
19
S
safety
ground
19
separating
power and control module
26
168 Rockwell Automation Publication 520-UM002D-EN-E - January 2023
Index
shielded
wiring
31
shielding
ground
19
start
motor
32
stop
motor
32
storage
environment
16
T
temperature
derating
15
wiring
30
tools
programming
51
U
unshielded
wiring
31
V
voltage reflections
wiring
32
W
wave protection
reflected
32
wiring
encoder
166
noise immunity
34
recommended
33, 34
shielded 31
temperature
30
unshielded
31
voltage reflections 32
Rockwell Automation Publication 520-UM002D-EN-E - January 2023 169
PowerFlex 527 Adjustable Frequency AC Drive User Manual
Publication 520-UM002D-EN-E - January 2023
Supersedes Publication 520-UM002C-EN-E - July 2019 Copyright © 2023 Rockwell Automation, Inc. All rights reserved.
Rockwell Automation Support
Use these resources to access support information.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback
.
Waste Electrical and Electronic Equipment (WEEE)
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Technical Support Center
Find help with how-to videos, FAQs, chat, user forums, Knowledgebase, and product
notification updates.
rok.auto/support
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Technical Documentation Center
Quickly access and download technical specifications, installation instructions, and user
manuals.
rok.auto/techdocs
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center
(PCDC)
Download firmware, associated files (such as AOP, EDS, and DTM), and access product
release notes.
rok.auto/pcdc
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur
Allen-Bradley, CompactLogix, ControlLogix, expanding human possibility, FactoryTalk, GuardLogix, Logix 5000, PowerFlex, Rockwell Automation, RSLinx, RSLogix 5000, Studio 5000,
Studio 5000 Automation Engineering & Design Environment, Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc.
CIP, CIP Motion, CIP Safety, CIP Sync, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.