I·
carried out. As a result of non-implementation of
complete transformer oil analysis programme, the
following problems were observed.
• Deposition of excessive carbon resulted in the
flashing of OLTCof power transformer.
• Burning of 1.5 MV A Transformer due to excessive
sludge and ageing of cellulose paper.
Keeping in view the recurring nature of above problems
resulting in breakdowns ABC paper decided to start
complete oil analysis. To start with, the transformer oil
ofallthe transformers were dehydrated to remove sludge
&
moisture. Afterwards oil.of three transformers was
completely replaced and the transformer windings were
also cleaned during annual shutdown with hot
pressurized oil to remove sludge and other foreign
particles. Sincethen the transformer oil analysis is being
regularly carried out and approximately Rs. 50000/-
are being spent annually for implementation of oil
analysis programme. Some of the advantages offered by
transformer oil analysis in ABC paper are as follows:
• Smooth running of transformers without
overheating
• Dielectricstrength has gone above 50 KVat 2.5
mm gap in comparison to earlier 20-25KV
•
Improvement in IR values
DISCUSSION
I
Sincethe lifeof a transformer is dependent on the life of
the insulating medium used, therefore proper analysis
of the oil can help to identify the deterioration problem"
beforeit becomes too criticaland severe. Thebreakdown
voltage is indicative of the amount of contaminant in
the oil. The minimum accepted dielectric strength is 30
kV and 25 kV for transformers with a high-voltage
rating 287.5kV
&
above and transformers with a ~gh-
voltage rating below 287.5 kV respectively. No single
test determines the actual condition ofthe oilforexample
oil is not necessarily in good condition even when the
dielectricstrength is adequate because this tells nothing
about the presence of acids and sludge: Therefore a
outcomeofallthe test should be considered whilemaking
a recommendation
Acid number value of 0.4is considered to be the normal
service limit and sludging has been found to start when
acid number exceeds 9.4. However different types of
transformers would take different period of time for
appearance of sludge ranging from 10 years for
transformers with free air access to 67 years for
transformers with nitrogen over oil.
The limit for power factor ofnew oilis 0.05%at 25
"C,
A
high power factor in used oil indicates deterioration or
contamination or both. Operational hazard is expected
from transformer oil with a power factor in excessof 2.0
percent and therefore requires reconditioning or
replacement.
Since,the acidity test alone determines only conditions
under which sludge may form but does not necessarily
indicate that actual sludging conditions exist for which
Iff test is required to be performed. Transformer oils
with Iff values in the range of 0.015to 0.022N/m (15to
22dyn/ cm) are required to be scheduled for reclaiming
irrespective of acidity values. The equipment operating
for 10 years or older should be tested for oxidation
inhibitor concentration when the physical tests are
performed. If the level of DBPC drops below 0.08%,
oxidation inhibitor should be added
The integration of the results of all the tests determines
the actual condition of the transformer oil and gives an
indication of discarding and replacement of oil.
CONCLUSION
It may be concluded that transformer oil analysis is an
important indicator of the transformer problems much
before they actually arise and cause breakdown.
Therefore, proper understanding, designing, training
and implementation of transformer oil analysis
programme in industrial operations is an essential
requirement for improved plant reliability.
ACKNOWLEDGEMENT
Authors are extremely grateful to the Management of
ABCPaper for granting their permission to present this
paper in the IPPTA Zonal Seminar.
IPPTA
I.
VoL 17, No.1
Ian
2005
85